HomeMy WebLinkAbout0260.97.4MECHANICAL WORK ALL EXISTING ELECTRIC BASEBOARD HEATING UNITS AND SPACE THERMOSTATS SHALL BE REMOVED AND CIRCUIT WIRES RE- DIRECTED FOR NEW MECHANICAL EQUIPMENT OR DISCONNECTED AT POWER SOURCES AND ABANDONED. THE EXISTING ATTIC AIR CONDITIONING AIR HANDLING UNIT SHALL BE CONVERTED TO PROVIDE HEATING AND COOLING TO A PORTION OF THE BUILDING AS INDICATED ON THE DRAWINGS WITH THE ADDITION OF A 20 KW RESISTANCE HEAT COIL. THE MAIN COIL SHALL PROVIDE HEATING AND COOLING WITH A SPLIT SYSTEM EXTERIOR HEAT PUMP UNIT, 3 TON CAPACITY. A NEW (SECOND) ATTIC AIR HANDLING UNIT SHALL BE ADDED WITH A 3 TON CAPACITY AND A 20 KW RESISTANCE BACK -UP HEAT COIL AND A SECOND SPLIT - SYSTEM EXTERIOR HEAT PUMP. INCLUDE CONDENSATE DRAIN PIPING TO INTERIOR DRAIN. EXISTING DUCTWORK SHALL BE UTILISED WHERE POSSIBLE ADDING NEW FLEXIBLE, INSULATED DUCTS FOR NEW DIFFUSERS AND RETURN GRILLES. NEW DUCTWORK SHALL BE REQUIRED FOR THE NEW AIR HANDLING SYSTEM. PROVIDE NEW THERMOSTATS FOR EACH UNIT, LOCATED AS INDICATED. HEATING CONTRACTOR SHALL SIZE BRANCH DUCTWORK AND DIFFUSERS /GRILLES FOR THE REQUIRED CFM. PROVIDE SEPARATE DISCONNECT SWITCHES AT HEAT PUMPS AND AIR HANDLING UNITS. PLUMBING SPECIFICATIONS PLUMBING WASTE AND VENT PIPING SHALL CONSIST OF POLYVINYL - CHLORIDE (PVC) PIPE WITH SOLVENT WELDED JOINTS. CONNECTIONS TO EXISTING WASTE PIPING SHALL BE WITH COMPATIBLE MATERIALS. DOMESTIC WATER LINES ABOVE GRADE SHALL BE TYPE "L" COPPER WITH WROUGHT COPPER SOLDER FITTINGS. ALL WATER LINES ABOVE TEE CEILINGS OR IN EXTERIOR WALLS SHALL BE INSULATED WITS 3/4" FOAM TYPE PIPE INSULATION INCLUDING JOINTS AND FITTINGS. WATER PIPING, EXISTING AND NEW, SMALL BE FULLY CHLORINATED AND PURIFIED PRIOR TO COMPLETION. PROVIDE WATER TEMPERING VALVE(B) FOR ALL WATER LINES TO LAVATORIES TO INSURE WATER TEMPERATURES AT FAUCETS TO BE BETWEEN 100 DEGREES AND 120 DEGREES F. (EXCEPT KITCHEN AND CHANGING TABLE SINKS). ALTERNATIVE OF A SEPARATE MIXED TEMPERATE WATER SERVICE LINE IS ACCEPTABLE AT LAVATORIES. WATER CLOSETS SHALL BE PRE - SCHOOL SIZED WITH 10 INCH MAXIXUM BOWL HEIGHTS, FLOOR MOUNTED TANK TYPE FIXTURES WITE OPEN -END SEATS, COLOR WHITE. LAVATORIES WITHIN TOILET ROOMS SHALL BE COUNTER -TOP TYPE, OVAL SHAPED WITH SINGLE CONTROL FAUCETS AND WITHOUT DRAIN STOPS. LAVATORIES WITHIN CHILD - ACTIVITY ROOMS SHALL BE 1411 X 16" X 7" DEEP, 20 GA. STAINLESS STEEL WITS SINGLED FAUCET, PRE -MIXED WATER DELIVERY AND A COLD WATER BUBBLER OPPOSITE FAUCET AND NO DRAIN STOPS. COUNTER-TOP SINKS SHALL BE 14" X 1811 X 7" DEEP, 20 GA. STAINLESS STEEL WITH STANDARD FAUCET SET - NO BUBBLERS. SINKS SHALL HAVE DRAIN STOPS. UTILIZE EXISTING ELECTRIC WATER HEATER IN BASENENIT. EXISTING PLUMBING FIXTURES IN STAFF RESTROOM BEAM REMAIN- v,-w, eat r � _AV PLUMBING ISOMETRI WEST SIDE OF BLDG. %i NOS: ).. REMOVE ALL EXISTING BASEBOARD ELECTIC RADIATION WIND=S AND THERMOSTATS 2. REMOVE ALL EXISITNG DUPLEX OUTLETS DT INDICATED TO REMAIN. ALL CIRCUIT WIRES NOT REROUTED FOR XW DEVICES SMALL BE DIM CONNECTED AT JUNCTION BOXES OR AT PAEL. 3. ALL ELECTRICAL WORK SHALL BE IN COMLIANCE WITH TEE CURRENT NATIONAL ELECTRIC CODE. 4. ALL HEATING /COOLING EQUIPMENT SHALLIE PROVIDED WITH APPROVED DISCONNECT SWITCHES. S. HEATING CONTRACTOR SHALL SIZE EXISTIG AND NEW DUC29ORK TO PROVIDE MINIMUM CFM SUPPLY AND RETUR AIR TO SPACES AS INDICATED. 6. NEW WATER SERVICE LINES IN ATTIC SPA$ IIIIIIIALL BE ""IF INSULATED WITH 3/4" THICK FOAL[ TYPE XPE WRAP,INCL=ZN8 TEES AND JOINTS. STRAP INSULATED PIPITO CRILING NOIalM AV 41 O.C. AND COVER ALL PIPE,WITH 6" BX"P INSULATION. 7. NEW WATER SERVICE AND SANITARY SEWER►OR TODDLER >aCA SINKS SHALL BE EXTENDED FROM TEE BASUNT AREA PIPING. 8. NEW SANITARY BEWBR SERVICE SBALL BE QED II/S FED THE WEST AND NORTH SID88 OF THE FOUNLTIOIN -BEE BIT= PfiIN. ,LECTRICAL WORK NEW AND RENOVATED ELECTRICAL SYSTEMS AND WIRING SHALL BE :INSTALLED IN COMPLIANCE WITH THE CURRENT NATIONAL ELECTRICAL CODE 31D TEE IINDIAM STATE ELECTRICAL CODE. REMOVE ALL EXISTING LIGHT IXTURES, DEVICES AND WIRING WHERE CIRCUITS ARE DISCONTINUED, INCLUDING PAINEL CONNECTIONS. ALL NEW WIRING SHALL BE COPPER, WIN /TH10111 INSULATED, #12 AWG SIZE FOR OUTLETS AND POWER DEVICES, 14 AWG FOR LIGHT SWITCH CIRCUITS. FLUORESCENT LIGHT FIXTURES EiALL BE 20 X 40, SURFACE MOUNTED, 4 TUBE 40W WARM WHITE, ACRYLIC ZN8 FIXTURES. INCANDESCENT FIXTURES SHALL BE AS SELECTED BY THE 4=R. NEW CONVENIENCE OUTLETS SHALL BE REQUIRED FOR NEW AND MISTING DEVICE BOXES AND SHALL CONSIST OF TAMPER - RESISTANT *CEPTACLES, 2 POLE, 3 WIRE, GROUNDED 15 AMP, 125V, NEMA WD -1, NORM COLOR, IN COMPLIANCE WITH NATIONAL ELECTRIC CODE 517 -18. TELEPNONE WIRING AND DEVICES SHALL BE BY OTHERS. FIRE ALA= SYSTEM AND SMOKE DETECTORS SHALL COMPLY WITH NFPA M'ANDAiDS, TEE AMERICANS WITH DISABILITIES ACT AND THE INDIANA AECTRICAL CODE, MANUFACTURED BY SIMPLEX, NOTIFIER, EST, OR VPROVEND NQUAL. AUDIBLE AND STROBING ALARM SHALL BE ACTIVATED BY 'RE SHOM SENSORS OR THE MANUAL PULL STATION. 9t(E P(.OJ it i L M 3• E �e ISfING RETURN AIR ww, s TODDLI boo{ 100 - i 1 ?� YR. HILDRE0 , I loo IO+uG I �►Zr E__ Z" \ '.OxI(o 1 i I125 AMP I 120/240 V. 100 AMP IN SWITCH DISCONNECT EXISTING BASEBOARD HEATER CIRCUITS - RECONNECT NEW HVAC UNIT AND HEAT PUMPS SERVICE. USE SPARE 120V CIR- CUITS FOR NEW ADDITIONS LIGHTING AND POWER OUTLETS. EXISTING ELECTRICAL PAhIEL.B._ (IN BASEMENT) TO 3RkXAIN - - Ll j— -7 I � i w - low, i I el INFANTS 150 150 STOR. 1 , i f I LL� it PATIO SYMBOL LEGEND y EXISTING DIFFUSERS GNEW DIFFUSERS NEW RETURN AIR GRILLE EXISTING THERMOSTAT nT NEW THERMOSTAT NEW 21Y 41 ,4 40v FLOUR.LIGHT FIXTURE(OR EQUIV.F'IXTURES FOR SO fC ILLUMINATION -�} NEW INCANDESCENT LIGET FIXTURES TO BE SELECTED -2 100N LAMPS NEW EMERGENCY LIGHT FIXTURE UNITS EXISTING SWITCHES NEW SWITCHES EXISTING OUTLETS TO R=1IA1N- CONVERT 10 WOO= RES.TYPE DEVICES NEW OUTLETS - TAMPER RES . TYPE DIRVICEMS ONEW CLG. LIGHT /EXH. FAA EXISTING BASEBOARD HTR. - TO BE REMOVED EXISTING TELEPHONE OUTLETS TO REMAIN 1� EXISTING CABLE TV OUTLETS TO REMAIN Et1 NEW TELEPHONE OUTLET NEW SMOKE DETECTOR NEW FIRE ALARM HORN i FLASHER UNIT (LOCATE FIRE ALARM[ CONTROL PANEL IN BASEMENT) C7 re-S AAAM FUW, wYi6e I i EXISTING AIR HANDLING UNIT IN ATT C BPACE - CONVERT COOLING COIL TO FEAT PUMP UNIT A WD 20 KW ELECTRIC K =UP - EXAT COIL II 11 STAFF SERVING KITCHEN' S, I ,( E 0 » 3 WW SVU*-tYSTEM HEAT PtrAP UNITS, fiNWA PHASE WITS DISCONNECT ftlf� AM NOMMING PADS I I r a� -= = == HEAT PUMP FLUID ' LIN NS IN ATTIC � CHILDREN I iT� �ox10 RECEPTLON ' i s °- S — � - OFFIGE �pi 00- 1 \ (� loo OR. � G ' EXIST DEPT. KEY BOX ENTRY lox* -^E 1. 4/5 YR.0 Zoo REMOVE EXISTING BASEBOARD HEATERS 3 TONS AIR HANDLING UNIT IN ATTIC E WITH HEAT PUMP COIL i 20 KW C BACK -UP HEATING COIL � 1 I 4 �- HVAC,PLUMBING & ELECTRICAI`_P_LAN. SCALE -1 /4" =1'0' , INSULATED DUCTWORK z U a c� z a W COMM. rA SHEET