HomeMy WebLinkAbout1126.95.1MECHANICAL EQUIPMENT SCHEDULE
1. SPLIT SYSTEM HEATING AND AIR CONDITIONING SYSTEMS CONSISTS
OF AIR HANDLING UNIT WITH ELECTRIC HEAT AND AIR COOLED
CONDENSING UNIT. CARRIER, TRANE OR EQUAL. PROVIDE WITH
ACCESSORY THERMOSTAT HAVING HEAT -OFF -COOL AND FAN SUB BASE.
PROVIDE LOCKING COVER COMPLETE WITH ALL OPERATING AND SAFETY
CONTROLS. TWO STAGE HEATING WHERE INDICATED. SYSTEM 2000
CFM AND ABOVE SHALL BE PROVIDED WITH RETURN AIR SMOKESTAT
FOR SYSTEM SHUTDOWN PER N.F.P.A. REFRIG PIPING SHALL BE
SIZED AND INSTALLED PER MANUFACTURER RECOMMENDATIONS.
INSTALL TRAPPED CONDENSATE DRAIN TO PLUMBING DRAINS.
COORDINATE WITH PLUMBING CONTRACTOR.
SYSTEM NO. 1: TRANE MODEL TWE090Al NOM. 7 -1/2 TONS COOL
CAPACITY AT A.R.I. CONDITIONS 3000 CFM. 2 H.P. EVAP FAN
MOTOR, 18 KW, 2 -STAGE ELECTRIC HEATER AT 480/3/ CONDITIONING
UNIT: TRANE MODEL TTA090A AT 480/3/.
2. CORRIDOR 100% FRESH AIR UNIT - AAON MODEL RE -08 1700 CFM AT
0.5" E.S.P. COOL E.A.T. 94/78 L.A.T. 64.7/64.6 TOTAL COOL
CAPACITY = 90,243 BTU /HR SENS = 54,044 BTU /HR NAT GAS HEAT
INPUT = 173 MBH OUTPUT = 140 MBH HEAT E.A.T. -2/ L.A.T.
74/ 1 H.P. EVAP FAN MOTOR UNIT MCA AT 44A AT 208/30 FACTORY
SINGLE PKG. PIPED WIRED AND TESTED. DUAL COMP. CKTS NTH
ROW SPLIT DX COIL. HOT GAS BYPASS, 5 MIN. ANTI RECYCLE
TIMERS AND 20 SEC. TIMER BETWEEN COMP ADJ COMP LOCKOUT
THERMOSTAT EACH CIRCUIT, CRANKCASE HEATERS. MAN H1 RESET AND
AUTO LOW RESET, 2 -STAGE SS HEAT EXCHANGER, 2 -STAGE DISCH.
HEATING OVERRIDE THERMOSTAT, HEATING /COOL LOCKOUT INTERLOCK,
ADJ V -BELT DRIVE BLOWER, SUPPLY AIR SMOKE DETECTOR. 100%
O.S.A. HOOD WITH BIRD SCREEN, 30% PLEATED FILTERS, HOT GAS
REHEAT COIL FOR HUMIDITY CONTROL, 30" FACTORY INSULATED 5
YEAR WARRANTY AND PRO RATED 6 TO 10 YEARS. ALL CONTROLS FOR
COMPLETE OPERATION INSTALLED BY MANUFACTURER. FURNISH FOR
FIELD MOUNTING T874 D THERMOSTAT, Q674C SUB BASE WITH LOCK
COVER AND HUMIDISTAT WITH LOCK COVER. FOR ADDITIONAL
INFORMATION ON THIS UNIT CONTACT GORHAM /SCHAFFLER INC.,
MEMPHIS, TENNESSEE AT 901- 345 -6100.
3. INDIVIDUAL ROOM TYPE HEATING AND AIR CONDITIONING UNITS -
(PTAC) MCQUAY SUITE OR EQUAL SERIES 09 208/10 (TYPE "A "2 NOM
9000 BTU /HR COOLING WITH 30 KW ELECTRIC HEATER. (TYPE B ")
NOM 14000 BTU /HR PROVIDE WITH SUB BASE AND INTERNAL DRAIN
KIT.
4. GAS UNIT HEATER NO. 1 - STERLING OR EQUAL PROP TYPE NAT GAS
INPUT 30 MBH 120V.
5. EXHAUST FANS - GREENHECK OR EQUAL ALUMINUM CENTRIFUGAL
EXHAUSTERS 120V NOM PROVIDE WITH B.D. DMPR, BIRD SCREEN AND
DISC. SWITCH. PROVIDE ROOF CURBS FOR ROOF FANS.
4
FAN NO.
CFM
3 -P
TYPE
MODEL
REMARKS
1 THRU 4
600
.250
ROOF
GB -90 -4
BATHROOMS
5
650
.250
ROOF
GB -90 -4
BATHROOMS
6
600
.250
ROOF
GB -90 -4
BATH & PREP
7
450
.250
ROOF
GB -90 -4
BATHROOMS
8
900
.250
ROOF
GB -90 -4
BATHROOMS
W1
660
.250
WALL
GW -90 -D
PUB. TOILETS
W2
1200
.250
WALL
GW -90 -A
LAUNDRY
/ /C/??& 0 9 Z""'
1
;.