HomeMy WebLinkAbout028 MT102.pdfRJS MT102HVAC DETAILS EXHAUST OUTLET RTU PRESS TRTD 4x4 ERV INTAKE BOLT TO 4x4 ADJUSTABLE LEGS WITH ERV. NO SCALE SINGLE PLY ROOFING SLIP SHEET ERV SUPPORT TRUSS. TYPICAL METAL OR WOOD NO SCALE KITCHEN HOOD DETAIL THE SYSTEM TO A RAINPROOF COLLECTION WEATHER PROTECTED OPENING UPBLAST FAN NFPA-96 (7.5.1) MATERIALS- DUCTS SHALL BE CONSTRUCTED OF & SUPPORTED BY CARBON STEEL NOT LESS THAN .054"(NO. 16 MSG) OR STAINLESS STEEL NOT LESS THAN .043" (NO. 18 MSG) IN THICKNESS NFPA-96 (4.2.1) 0" TO NONCOMBUSTIBLES 3" TO LIMITED-COMBUSTIBLES, 18" CLEARANCE TO COMBUSTIBLES UNLESS PROTECTED IN 4 0 " M IN . NFPA-96 (7.8.2.1) THE ABILITY TO DRAIN GREASE OUT OF ANY TRAPS OR LOW POINTS FORMED IN THE FAN OR DUCT NEAR THE TERMINATION OF THRU 4.2.3.3 ACCORDANCE W/ EXCEPTIONS NO. 4.2.1 NFPA-96 (4-2.1) 0" TO NONCOMBUSTIBLES 3" TO LIMITED-COMBUSTIBLES, 18" CLEARANCE TO COMBUSTIBLES UNLESS PROTECTED IN THRU 4.2.3.3 ACCORDANCE W/ EXCEPTIONS NO. 4.2.1 NFPA-96 (7.-7.1) 2 MIN. OF 40" ABOVE ROOF SURFACE NFPA-96 (7.8.2.1.8) EXHAUST FLOW CONTAINER. NFPA-96 (7.8.2.1) GREASE COLLECTOR ASSEMBLY ROOF FOR COMMERCIAL COOKING EQUIPMENT, PROVIDED THE CABLE & SERVICE HOLD-OPEN RETAINER TO PERMIT PROPER INSPECTION & CLEANING & THAT IS LISTED DUCTWORK EXTENDS A MINIMUM OF 18" ABOVE THE ROOF SURFACE, & THE FAN DISCHARGES A MINIMUM 40" ABOVE THE ROOF SURFACE SUPPLIED W/ FLEXIBLE WEATHERPROOF ELECTRICAL NFPA-96 (7.8.2.1.8) WITH A HINGED UP-DISCHARGE FAN 1 NO SCALE ROOF TOP UNIT MOUNTING DETAIL S D COUNTER FLASHING ROOF FLASHING & CANT STRIP BY OTHERS RIGID INSULATION BY OTHERS 2" x 2" TREATED PINE, SUPPLIED W/ CURB IS TO BE USED AS A FLASHING ANCHOR MASON INDUSTRIES TYPE NK NEOPRENE ISOLATION PADS 1" THICK, 2" WIDE CONTINUOUS AROUND CURB. DUCT RETURN TYPICAL ROOF TOP UNIT ( RTU ) FLEX CONN TYPICAL SUPPLY DUCT PROVIDE (2) LAYERS OF 5/8" DRYWALL INSTALLED BY DIVISION 16 AND COORDINATED WITH IN RETURN DUCT TO BE INSTALLED PER NOTE: COMBINATION SMOKE/HEAT DETECTOR DUCT MOUNTED OUTSIDE AIR TEMPERING SENSOR REQUIRED DISTANCE DOWNSTREAM FROM BEND OR INLETS AS RECOMMENDED BY EQUIPMENT MANUFACTURER. HVAC CONTRACTOR. NFPA-72E & NFPA-90A REQUIREMENTS & MOUNTED ROOF 1 8 " M IN CEILING -SUPPLY & RETURN DUCTS - FIRST 10 FT OF RUN UNITS BELOW 2000 CFM: -RETURN DUCT - FIRST 10 FT OF RUN -SUPPLY DUCT - FIRST 25 FT OF RUN UNITS 2000 CFM & GREATER: DUCT LINER THROUGHOUT INSIDE OF CURB & (1) LAYER OF 12" BATT INSULATION PER NFPA 90A. INSTALL PER MANUFACTURER’S INSTRUCTIONS AND DUCT SYSTEM FOR FIRE RATED (2HR) GREASE DUCT. PER ASTM E 2336. 3M FIRE BARRIER DUCT WRAP 15A WITH A FIELD-APPLIED DUCTWRAP ENCLOSURE SYSTEM THE GREASE DUCT SHALL BE COVERED IN ALL SIDES OR GREATER SYSTEMS OF 2000 CFM REQUIRED ON RETURN AIR W/ HVAC CONTRACTOR. CONTRACTOR & COORDINATED DETECTOR BY ELECTRICAL COMBINATION SMOKE & HEAT TO AIR INTAKES. A MINIMUM OF 12 FT CLEARANCE FROM OUTLET BUILDINGS & PROPERTY LINES. CLEARANCE FROM THE OUTLET TO ADJACENT NFPA-96 (7.8.2.1 WITH A MINUMUM OF 10 FT C U R B 1 4 " UNIT BY HVAC CONTRACTOR BLOCKING AS REQUIRED TO SHIM & SUPPORT ROOFTOP BOTTOM OF CURB TO HEIGHT OF TOP OF ROOF INSULATION) TREATED WOOD (4x4 MIN. OR AS REQUIRED TO RAISE METAL OR WOOD TRUSS. TYPICAL FLOOR BY OTHERS DRYER 4"‘ E FOR FIRE DAMPER RESET DUCT ACCESS PANEL NO SCALE AT FLOORLINE WALL ACCESS PANEL NO SCALE FLOOR 4"‘ E SIDE BY SIDE INSTALLATION STACKED UNIT INSTALLATION BY G.C. TYP. WALL BY OTHERS DRYER OR APPROVED EQUAL "SUPER-FLEX" 4"ß FLEX BY OTHERS WASHER BY G.C. TYP. WALL SPACE JOIST ASSEMBLY RATED FLOOR SLEEVE TYPICAL BREAK - AWAY JOINT FIRE DAMPER AT FLOORLINE SLEEVE NO SCALE DUCT ACCESS PANEL FIRE DAMPER VERTICAL INSTALLATION ASSEMBLY RATED WALL CEILING ACCESS PANEL SHAFT ASSEMBLY RATED WALL OR TYPICAL JOINT. BREAK-AWAY ( 2 HR MIN. ) SEE DRAWINGS FOR RATING. FIRE DAMPER. EXHAUST OR OUTSIDE AIR DUCT SUPPLY, RETURN, OR OUTSIDE AIR DUCT SUPPLY, RETURN, EXHAUST ( 2 HR MIN. ) SEE DRAWINGS FOR RATING. FIRE DAMPER. FIRE DAMPER NOTE NO SCALE RADIATION DAMPER MOUNTING DETAIL TYPICAL TRUSS AND TRUSS SECURE TO DUCT SUPPORT ANGLE. L 1 1/2 x 1 1/2 x 16 GA ASSEMBLY 1 HR. RATED BY HEATING CONTRACTOR WITHIN 2" OF TRUSS. BOARD PROTECTION IF DUCT IS PROVIDE 5/8" FIRE RATED GYPSUM OR OUTSIDE AIR DUCT SUPPLY, RETURN EXHAUST RADIATION DAMPER NOTE 3 MT102 MT102MT102 5 MT102 6 MT102 7 MT102MT102 8 THESE DEVICES, COORDINATE WITH GENERAL CONTRACTOR. REVIEW INSTALLATION PRIOR TO ANY DRYWALL ENCLOSURE OF INSPECTION. ARCHITECT/ENGINEER OR ARCHITECTS FINAL INSPECTOR TO GENERAL CONTRACTOR TO HAVE ON SITE FOR INSPECTORS FOR USE DURING FINAL ARCHITECT PRIOR TO INSTALLATION AND PROVIDE COPIES TO THE SUBMIT LEGIBLE INSTALLATION INSTRUCTIONS AND DETAILS TO THE THE MANUFACTURER AND THEIR APPROVAL AGENCY (UL, CSA, ETC.). DEVIATIONS FROM THESE DETAILS ARE ALLOWED UNLESS APPROVED BY (UL OR EQUIVALENT) INSTALLATION INSTRUCTIONS AND DETAILS; NO ALL CEILING RADIATION DAMPERS TO BE INSTALLED PER THE MANUFACTURERS SPACE JOIST ENCLOSURE OF THESE DEVICES, COORDINATE WITH GENERAL CONTRACTOR. INSPECTOR TO REVIEW INSTALLATION PRIOR TO ANY DRYWALL DURING FINAL INSPECTION. ARCHITECT/ENGINEER OR ARCHITECTS FINAL GENERAL CONTRACTOR TO HAVE ON SITE FOR INSPECTORS FOR USE ARCHITECT PRIOR TO INSTALLATION AND PROVIDE COPIES TO THE SUBMIT LEGIBLE INSTALLATION INSTRUCTIONS AND DETAILS TO THE THE MANUFACTURER AND THEIR APPROVAL AGENCY (UL, CSA, ETC.). THESE DETAILS ARE ALLOWED UNLESS APPROVED BY INSTALLATION INSTRUCTIONS AND DETAILS; NO DEVIATIONS FROM BE INSTALLED PER THE MANUFACTURERS (UL OR EQUIVALENT) ALL FIRE DAMPER AND SMOKE DAMPERS TO RADIATION DAMPER 1 HOUR RATED NO SCALE AIR INTAKE EXTENSION WITH INSECT SCREEN. OUTSIDE AIR INLET EXTENSION STAINLESS STEEL OUTSIDE SUPPORT W/ 20 GA. S. S. STRAP 3 6 " M IN . ROOF ROOF OUTSIDE AIR INTAKE EXTENSION HRV, ROOFTOP UNIT, ETC. TYPICAL ROOF MOUNTED EQUIPMENT, MT102 9 RECESSED DRYER BOX DETAIL CEILINGCEILING NO SCALE OUTSIDE AIR INLET HEAT RECOVERY VENTILATOR EXHAUST DISCHARGE COUNTER FLASHING ROOF FLASHING & CANT STRIP BY OTHERS RIGID INSULATION BY OTHERS 1" x 1 1/2 LB. DENSITY FIBERGLASS INSULATION W/ NEOPRENE COATING DUCT MAKE-UP AIREXHAUST DUCT 14 " ON ALL EXPOSED SURFACES. INSULATE VERTICAL EXHAUST DUCT ONLY. UNIT BY HVAC CONTRACTOR BLOCKING AS REQUIRED TO SHIM & SUPPORT BOTTOM OF CURB TO HEIGHT OF TOP OF ROOF INSULATION) TREATED WOOD (4x4 MIN. OR AS REQUIRED TO RAISE C U R B INSULATE ENTIRE RUN IF IN ATTIC SPACE INSULATE ENTIRE MAKE-UP AIR DUCT RUN. MA205 HEAT RECOVERY VENTILATOR MOUNTING DETAIL 4 2ND FLOORS USE ON 1ST & VENT UPWARD. DB-1 DRYER BOX USE ON 3RD FLOOR VENT DOWNWARD. DB-2 DRYER BOX 4"‘ RIGID 4"‘ RIGID SPACE JOIST CEILING FLOOR FLOOR FLOOR SPACE JOIST CEILING 4"‘ E4"‘ E USE ON 3RD FLOOR VENT DOWNWARD. DB-2 DRYER BOX OR APPROVED EQUAL "SUPER-FLEX" 4"ß FLEX 2ND FLOORS USE ON 1ST & VENT UPWARD. DB-1 DRYER BOX VIBRATION ISOLATOR PADS PVC COMBUSTION AIR INTAKE TYPICAL FURNACE INSTALLATION DETAIL SUPPLY PLENUM NO SCALE PVC EXHAUST FROM A/C COIL 3/4" CONDENSATE DRAIN SEE PLANS FOR RETURN TRUNK SIZES AND LOCATIONS. RETURN AIR DROP A/C PLENUM AND COILFLEXIBLE CONNECTION SIDE RETURN TYPICAL FURNACE WITH FLOOR 10 MT102 INSTALLATION INSTRUCTIONS. CONTRACTOR TO FOLLOW MANUFACTURER’S SIZES, DUCT RUN LOCATIONS & GRILLE LOCATIONS. SEE PLANS FOR ACTUAL FURNACE LOCATIONS & THIS DETAIL IS SCHEMATIC ONLY, NOTE: 0UTDOOR AIR INTAKE DUCT INSULATED VD (VOLUME DAMPER) FLEXIBLE CONNECTION WITH FILTER FILTER RACK SEE PLANS RISER OR SPILL ON GRADE. DRAINS TO FLOOR DRAIN, EXTEND CONDENSATE REVISIONS THIS DRAWING, ITS DESIGN CONCEPT AND ITS DETAIL ARE THE SOLE PROPERTY OF AG ARCHITECTURE, INC. AND SHALL NOT BE COPIED IN ANY FORM OR MANNER WITHOUT WRITTEN AUTHORIZATION OF ITS DESIGNER/CREATOR SHEET NO. DATE PROJECT DRAWN BY C o n t i n u i n g C a r e R e t i r e m e n t C a r m e l I n d i a n a 071101 T h e B a r r i n g t o n o f C a r m e l L : \ X Mw o r k s p a c e \ S t a n d a r d s \ p l t c f g \ a g p d f . p l t c f g L : \ X Mw o r k s p a c e \ S t a n d a r d s \ t a b l e s \ P e n \ a g . t b l P L O T P A R A ME T E R S : F I L E : K : \ 0 7 1 1 0 1 \ C A D D G N \ MT 1 0 2 . d g n 1 0 : 1 2 : 0 9 A M 8 / 1 / 2 0 1 1 P L O T T E D O N : 8 : 0 ’ : " / i n . L A S T S A V E : P E N T A B L E : 8 / 1 / 2 0 1 1 MO D E L : D e f a u l t r j s B Y U S E R : A T S C A L E : U S I N G D R I V E R :01 AUG 2011 FAX TEL