Loading...
HomeMy WebLinkAboutMP2.0( D I f MECHANICAL REOUIREMENTS: PROVIDE (5) GA5 FIRED INFRARED HEATERS, 1300W STUN UNITS SPACE RAY LTU SERIES OR EQUAL. ' r� PROVIDE (4) GREENHECK MODEL GB- 220 -15 OR EQUAL MOUNED ON ROOF. UNITS l \��J�// TO PROVIDE 6300 C.F.M. AT 0315' SP. EACH HAVING A 1 -1/2 NP MOTOR LOUVERS TO LET AIR INTO SPACE REQUIRE 36 5F. FREE AREA, OR 4 LOUVRS AT 12'x36'. THE LOUVER WOULD BE FITTED WITH DAMPERS WITH ELECTRONIC DAMPERS MOTORS TO CLOSE WHEN THE FANS ARE SHUT DOWN. THIS SYSTEM WOULD SERVE AS THE SMOKE REMOVAL SYSTEM. PROVIDE A 20 TON SPLIT SYSTEM FOR OFFICE AREA AND BREAK ROOM. THE GAS LOAD FOR THE BUILDING BASED ON THE RADIANT HEATING AND PAKAGED SYSTEM FOR THE OFFICE AREA WOULD REQUIRE A 2' GAS MAIN AT 10 -14' WC GAS PRESSURE, THE ENTIRE BUILDING TO BE FULLY SPRINKLED MECHANICAL NOTES 1. RECTANGULAR DUCTWORK, SUPPLY AND RETURN, SHALL BE SNEETMETAL, AND SHALL BE LINED WITH I' DUCT LINER ROUND DUCTWORK SHALL BE 5HEETMETAL, AND WRAPPED WITH I' DUCT WRAP. EXHAUST DUCTWORK SHALL BE SWEET METAL, AND SHALL BE UNLINED, ALL DUCTWORK SHALL MEET OR EXCEED SMAGNA STANDARDS FOR 2' PRESSURE CLASSIFICATION. GIVEN DIMENSIONS ARE INSIDE DIMENSIONS. ALL DUCTWORK SHALL BE SEALED AIRTIGHT WITH DUCT SEALANT AND SHALL GONFORM TO LOCAL BUILDING CODES. 2. FLEXIBLE DUCTWORK SHALL BE INSULATED, AND SHALL BE THE SAME SIZE AS THE NECT OF THE DIFFUSER FLEX DUCT SHALL NOT EXCEED 8' -0' IN LENGTH, AND SHALL CONFORM TO LOCAL BUILVX44 ;UDES. 3. ALL SPIN -IN FITTINGS SHALL BE CONICAL, AND SHALL HAVE MANUAL VOLUME DAMPERS. 4. RECTANGULAR BRANCH DUCT TAKE -OFFS 544ALL HAVE 45 1/13 TAKE-OFF5, AND ROUND DUCT TAKE -OFFS SHALL BE CONICAL. 5. ALL ELBOWS, BOTH HORIZONTAL AND VERTICAL, 5HALL BE LONG RADIUS ELBOWS WHEREVER POSSIBLE, OR SHALL HAVE TURNING VANES WHERE SHOWN. 6. BALANCE AIR SYSTEM TO QUANTITIES SHOWN, AND SUBMIT A BALANCE REPORT TO THE ARCHITECT/ENGINEER FOR REVIEW. 1. COORDINATE LOCATIONS OF THERMOSTATS WITH ARCHITECT PRIOR TO INSTALLATION. 8. CONTRACTOR SHALL INSPECT SITE TO THOROUGHLY FAMILIARIZE HIMSELF WITH THE AREA OF WORK THESE DOCUMENTS DO NOT REFLECT AS -BUILT CONDITIONS. ANY DISCREPANCIES BETWEEN THESE DOCUMENTS AND ACTUAL CONDITIONS SHALL BE REPORTED TO THE ARCHITECT.- `ENGINEER FOR RESOLUTION PRIOR TO BID PRICING. NO EXTRAS WILL BE ALLOWED DUE TO LACK OF KNOWLEDGE OF EXISTING CONDITIONS. 9. VACUUM CLEAN ALL COMPONENTS OF AIR HANDLING UNIT. STEAM CLEAN EXISTING COOLING COILS, REPAIR DAMAGED FINS OF COOLING COILS AND CONDENSING COILS, INSTALL NEW FILTERS. 10. REPAIR CONDENSATE DRAIN PIPING AS REQUIRED. ll. INSPECT AND TEST EXISTING UNITS FOR NECESSARY REPAIRS AND REGALIBR4TIONS. CLEAN ALL COMPONENTS OF BUILT UP DIRT AND OIL /GREASE. LUBRICATE ALL MOVING COMPONENTS AND BEARINGS AS PER MANUFACTURER'S MAINTENANGEC DITRUCTIONS. CHECK REFRIGERANT AND OIL LEVELS AND ADD AS REQUIRED, REPAIR ANY LEAKS. TAKE PRESSURE READING AND COMPARE WITH MANUFACTURER'S INFORMATION, REPORT ANY DEFICIENCIES TO OWNER'S RESENTATI VE. 12. REPLACE DRIVE BELTS FOR ALL BELT DRIVEN MACHINERY AND LUBRICATE ALL BEARINGS TO INCLUDE SUPPLY FANS, PUMPS, COMPRESSOR, ETC. 13. CLEAN, LUBRICATE AND EXERCISE THE DAMPERS FOR THE OUTSIDE AIR INTAKE DAMPER AND RETURN AIR DAMPER CHECK DAMPERS FOR PROPER OPERATION. CLEAN OUTSIDE AIR INTAKE LOUVER AND RELIEF AIR LOUVER 14. RECALIBRATE, REPAIR AND /OR REPLACE AUTOMATIC TEMPERATURE CONTROL 5Y5TEM5 COMPONENTS AS REQUIRED FORA COMPLETE OPERATIONAL SYSTEM. B. EXAMINE ALL FIRE DAMPERS AND SMOKE DAMPERS FOR PROPER OPERATION WITHOUT BINDING AND VERIFY THAT THE FUSIBLE LINK5 ARE WITH THE PROPER TEMPERATURE RATING. REPAIR, REPLACE AND /OR CLEAN AS REQUIRED, 16. DISCONNECT ALL RETURN AIR AND OUTSIDE AIR DAMPERS AND MANUALLY LOCK OPEN. 11. ADJUST PULLEYS AND BELTS TO OBTAIN REQUIRE `1 WITH 15% OUTSIDE AIR 18. CONNECT COMBUSTION AIR INLET AND FLUE GAS EXHAUST TO FURNACES. SIZE SCHEDULE 40 PIPE PER MANUFACTURER'S INSTRUCTIONS IS. CONNECT COMBUSTION AIR INLET AND FLUE GAS TO CONCENTRIC ONE PIPE ROOF TERMINATION 20. DIFFUSER 4 GRILLE LOCATIONS ARE APPROXIMATE MECHANICAL CONTRACTOR SHALL COORDINATE 21. MECHANICAL CONTRACTOR TO VENT WATER HEATER 0 6 1 1 I r—I I 0 .MAZ 7 I EF -2 0 c- MECHANICAL PLAN - MAIN LEVEL SCALE: 3/32' =I' -0' PLUMBING WASTE RISER DIAGRAM SCALE: NOT TO SCALE SCALE: 3/32' =1' -0' No. % t ' AR19= 43 mar P T 0 N A C 984 Lovan Stree 10 Nublesrille. IN 4COK USA t t: 1 3 1 7 7 1 0 9.7 1 4 f a x 3 1 7 7 7 0 9 7 1 8 en I so; ;ojp &cuailuRerte um Tw CORPORATION Commercial • Industrial • Instititutional 3641 West Morris Street Indianapolis, Indiana 46241-0267 P.O. Box 42267 Indianapolis, Indiana 46242 -0267 Phone (317) 244 -7637 Fa* (317) 244-6348 TO CONTRACTOR FOR PRICING FE5RUARY IS, 20M co ' A A A A A V NA DRAWN BY: Cl) CHECKED BY: D. PETERSON PROJECT NUMBER: C55M MECH/PL M5. W MP280 Er W v♦ r� T- 0. Cr O� O tv W W z °C !- C 0 _ Z Q �j J W I Cf) � } Z Z W Z 0 O t-4 0 � ac Q W V TO CONTRACTOR FOR PRICING FE5RUARY IS, 20M REVISIONS A A A A A PLOT DATE: NA DRAWN BY: S. BOYLE CHECKED BY: D. PETERSON PROJECT NUMBER: C55M MECH/PL M5. PLC MP280 'Ncs arc y'4s F. � J� 7� \� PMRSON ARCNITE , P.C. %0 �1'11Erc at "f"i :u° C `` iT FIE --:G= TUBE, PAC.