MECHANICAL REOUIREMENTS:
PROVIDE (5) GA5 FIRED INFRARED HEATERS, 1300W STUN UNITS SPACE RAY LTU
SERIES OR EQUAL. ' r�
PROVIDE (4) GREENHECK MODEL GB- 220 -15 OR EQUAL MOUNED ON ROOF. UNITS l \��J�//
TO PROVIDE 6300 C.F.M. AT 0315' SP. EACH HAVING A 1 -1/2 NP MOTOR LOUVERS
TO LET AIR INTO SPACE REQUIRE 36 5F. FREE AREA, OR 4 LOUVRS AT 12'x36'. THE LOUVER
WOULD BE FITTED WITH DAMPERS WITH ELECTRONIC DAMPERS MOTORS TO CLOSE WHEN
THE FANS ARE SHUT DOWN. THIS SYSTEM WOULD SERVE AS THE SMOKE REMOVAL SYSTEM.
PROVIDE A 20 TON SPLIT SYSTEM FOR OFFICE AREA AND BREAK ROOM.
THE GAS LOAD FOR THE BUILDING BASED ON THE RADIANT HEATING AND PAKAGED SYSTEM
FOR THE OFFICE AREA WOULD REQUIRE A 2' GAS MAIN AT 10 -14' WC GAS PRESSURE,
THE ENTIRE BUILDING TO BE FULLY SPRINKLED
MECHANICAL NOTES
1. RECTANGULAR DUCTWORK, SUPPLY AND RETURN, SHALL BE SNEETMETAL, AND SHALL BE LINED
WITH I' DUCT LINER ROUND DUCTWORK SHALL BE 5HEETMETAL, AND WRAPPED WITH I' DUCT WRAP.
EXHAUST DUCTWORK SHALL BE SWEET METAL, AND SHALL BE UNLINED, ALL DUCTWORK SHALL
MEET OR EXCEED SMAGNA STANDARDS FOR 2' PRESSURE CLASSIFICATION. GIVEN DIMENSIONS
ARE INSIDE DIMENSIONS.
ALL DUCTWORK SHALL BE SEALED AIRTIGHT WITH DUCT SEALANT AND SHALL GONFORM TO LOCAL
BUILDING CODES.
2. FLEXIBLE DUCTWORK SHALL BE INSULATED, AND SHALL BE THE SAME SIZE AS THE NECT OF THE
DIFFUSER FLEX DUCT SHALL NOT EXCEED 8' -0' IN LENGTH, AND SHALL CONFORM TO LOCAL
BUILVX44 ;UDES.
3. ALL SPIN -IN FITTINGS SHALL BE CONICAL, AND SHALL HAVE MANUAL VOLUME DAMPERS.
4. RECTANGULAR BRANCH DUCT TAKE -OFFS 544ALL HAVE 45 1/13 TAKE-OFF5, AND ROUND DUCT TAKE -OFFS
SHALL BE CONICAL.
5. ALL ELBOWS, BOTH HORIZONTAL AND VERTICAL, 5HALL BE LONG RADIUS ELBOWS WHEREVER POSSIBLE,
OR SHALL HAVE TURNING VANES WHERE SHOWN.
6. BALANCE AIR SYSTEM TO QUANTITIES SHOWN, AND SUBMIT A BALANCE REPORT TO THE
ARCHITECT/ENGINEER FOR REVIEW.
1. COORDINATE LOCATIONS OF THERMOSTATS WITH ARCHITECT PRIOR TO INSTALLATION.
8. CONTRACTOR SHALL INSPECT SITE TO THOROUGHLY FAMILIARIZE HIMSELF WITH THE AREA OF WORK
THESE DOCUMENTS DO NOT REFLECT AS -BUILT CONDITIONS. ANY DISCREPANCIES BETWEEN THESE
DOCUMENTS AND ACTUAL CONDITIONS SHALL BE REPORTED TO THE ARCHITECT.- `ENGINEER FOR
RESOLUTION PRIOR TO BID PRICING. NO EXTRAS WILL BE ALLOWED DUE TO LACK OF KNOWLEDGE
OF EXISTING CONDITIONS.
9. VACUUM CLEAN ALL COMPONENTS OF AIR HANDLING UNIT. STEAM CLEAN EXISTING COOLING COILS,
REPAIR DAMAGED FINS OF COOLING COILS AND CONDENSING COILS,
INSTALL NEW FILTERS.
10. REPAIR CONDENSATE DRAIN PIPING AS REQUIRED.
ll. INSPECT AND TEST EXISTING UNITS FOR NECESSARY REPAIRS AND REGALIBR4TIONS. CLEAN ALL
COMPONENTS OF BUILT UP DIRT AND OIL /GREASE. LUBRICATE ALL MOVING COMPONENTS AND
BEARINGS AS PER MANUFACTURER'S MAINTENANGEC DITRUCTIONS. CHECK REFRIGERANT AND OIL
LEVELS AND ADD AS REQUIRED, REPAIR ANY LEAKS. TAKE PRESSURE READING AND COMPARE
WITH MANUFACTURER'S INFORMATION, REPORT ANY DEFICIENCIES TO OWNER'S RESENTATI VE.
12. REPLACE DRIVE BELTS FOR ALL BELT DRIVEN MACHINERY AND LUBRICATE ALL BEARINGS TO INCLUDE
SUPPLY FANS, PUMPS, COMPRESSOR, ETC.
13. CLEAN, LUBRICATE AND EXERCISE THE DAMPERS FOR THE OUTSIDE AIR INTAKE DAMPER AND RETURN
AIR DAMPER CHECK DAMPERS FOR PROPER OPERATION. CLEAN OUTSIDE AIR INTAKE LOUVER AND
RELIEF AIR LOUVER
14. RECALIBRATE, REPAIR AND /OR REPLACE AUTOMATIC TEMPERATURE CONTROL 5Y5TEM5 COMPONENTS
AS REQUIRED FORA COMPLETE OPERATIONAL SYSTEM.
B. EXAMINE ALL FIRE DAMPERS AND SMOKE DAMPERS FOR PROPER OPERATION WITHOUT BINDING
AND VERIFY THAT THE FUSIBLE LINK5 ARE WITH THE PROPER TEMPERATURE RATING.
REPAIR, REPLACE AND /OR CLEAN AS REQUIRED,
16. DISCONNECT ALL RETURN AIR AND OUTSIDE AIR DAMPERS AND MANUALLY LOCK OPEN.
11. ADJUST PULLEYS AND BELTS TO OBTAIN REQUIRE `1 WITH 15% OUTSIDE AIR
18. CONNECT COMBUSTION AIR INLET AND FLUE GAS
EXHAUST TO FURNACES. SIZE SCHEDULE 40 PIPE
PER MANUFACTURER'S INSTRUCTIONS
IS. CONNECT COMBUSTION AIR INLET AND FLUE GAS TO
CONCENTRIC ONE PIPE ROOF TERMINATION
20. DIFFUSER 4 GRILLE LOCATIONS ARE APPROXIMATE
MECHANICAL CONTRACTOR SHALL COORDINATE
21. MECHANICAL CONTRACTOR TO VENT WATER HEATER
0
6 1 1
I r—I
I
0
.MAZ
7
I EF -2
0
c-
MECHANICAL PLAN - MAIN LEVEL
SCALE: 3/32' =I' -0'
PLUMBING WASTE RISER DIAGRAM
SCALE: NOT TO SCALE
SCALE: 3/32' =1' -0'
No. %
t ' AR19= 43
mar
P T 0 N
A C
984 Lovan Stree 10 Nublesrille. IN 4COK USA
t t: 1 3 1 7 7 1 0 9.7 1 4
f a x 3 1 7 7 7 0 9 7 1 8
en I so; ;ojp &cuailuRerte um
Tw
CORPORATION
Commercial • Industrial • Instititutional
3641 West Morris Street
Indianapolis, Indiana 46241-0267
P.O. Box 42267
Indianapolis, Indiana 46242 -0267
Phone (317) 244 -7637
Fa* (317) 244-6348
TO CONTRACTOR FOR PRICING
FE5RUARY IS,
20M
co
'
A
A
A
A
A
V
NA
DRAWN BY:
Cl)
CHECKED BY:
D. PETERSON
PROJECT NUMBER:
C55M
MECH/PL
M5.
W
MP280
Er
W
v♦
r�
T-
0.
Cr
O�
O
tv
W
W
z
°C !-
C
0
_
Z
Q
�j
J W
I
Cf)
�
}
Z
Z
W
Z
0
O
t-4
0
�
ac
Q
W
V
TO CONTRACTOR FOR PRICING
FE5RUARY IS,
20M
REVISIONS
A
A
A
A
A
PLOT DATE:
NA
DRAWN BY:
S. BOYLE
CHECKED BY:
D. PETERSON
PROJECT NUMBER:
C55M
MECH/PL
M5.
PLC
MP280
'Ncs arc y'4s F. � J� 7� \�
PMRSON ARCNITE , P.C.
%0 �1'11Erc at "f"i :u° C `` iT FIE --:G=
TUBE, PAC.