HomeMy WebLinkAboutE-2EXISTING PAD MOUNTED XFRMR, COORDINATE
WITH LOCAL POWER COMPANY, REFER TO SIT
DRAWING FOR EXACT LOCATION
TRENCHING CONDUIT AND BACKFILL
U � i
�i
a �E
SECOND FLOOR POWER
ADA PUSHBUTTON +36" ® SCALE: 1/8 " =1' -0"
BY E.C. COORDINATE WITH LOCAL MOUNT TO 4 °x4° DOOR STRIKE
POWER COMPANY FOR ALL FEES TO STEEL POST WITH (P1 -34)
BE INCLUDED IN BID. REFER TO SITE TOP CAP /- SECURITY KEYPAD +48°
UTILITIES DRAWINGS
ELECTRICAL GENERAL NOTES:
FIRST FLOOR POWER
SCALE: 1/8 " =1' -0"
A. ALL ELECTRICAL INSTALLATION SHALL MEET THE LATEST EDITION OF THE N.E.C., AND ALL LOCAL, STATE,
AND FEDERAL CODES HAVING JURISDICTION AND AUTHORITY.
B. COORDINATE WITH ALL TRADES AND NOTIFY ENGINEER OF ANY COORDINATION ISSUE PRIOR TO INSTALLATION.
C. FIRE STOP ALL FIRE RATED BARRIER PENETRAIONS.
D. DO NOT ROUTE ANY PIPES DIRECTLY OVER ELECTRICAL PANELS OR THROUGH DEDICATED ELEVATOR SPACES.
E. ALL CIRCUITS SHALL BE MINIMUM #12 AWG, MC CABLE WITH EQUIPMENT GROUND UNLESS NOTED OTHERWISE.
ALL RECEPTACLES SHALL BE MOUNTED +/- 18" A.F.F. UNLESS ABOVE COUNTER SPACE, COORDINATE WITH OWNER,
F. PROVIDE ALL PANEL(S) AND BREAKERS NECESSARY FOR AN OPERATING SYSTEM.
G. PROVIDE TWO SMOKE DETECTORS IN EACH AIR HANDLING SYSTEM INTERLOCKED TO THAT AIR HANDLING SYSTEM,
INSTALLED IN FOR EMERGENCY SHUTDOWN OF SYSTEM.
H. PROVIDE DISCONNECTS AT ALL EQUIPMENT REQUIRING DISCONNECTS.
I. PROVIDE TWO DEDICATED 1 PHASE, 120 VOLT CIRCUITS TO ELEVATOR EQUIPMENT ROOM. PROVIDE PRIMARY
ELEVATOR EQUIPMENT VOLTAGE AS INDICATED, COORDINATE WITH ELEVATOR CONTRACTOR PRIOR TO INSTALLATION FOR
EXACT INSTALLATION REQUIREMENTS.
J. COMBINATION TELEPHONE/DATA JUNCTION BOXES SHALL HAVE 3 /a" CONDUIT ROUTED TO ABOVE CEILING OR BELOW
FLOOR WITH PULL WIRE.
K. ALL OUTLETS ARE MOUNTED WITH BOTTOM OF BOXES AT +18" A.F.F. UNLESS NOTED OTHERWISE.
FIRE ALARM SYSTEM:
PROVIDE PULL STATIONS AT ALL BUILDING EXIT DOORS, PROVIDE SMOKE DETECTORS AT NFPA MAXIMUM SPACING IN COORIDORS.
PROVIDE COMBINATION HORN /STROBE IN EACH COORIDOR AT NFPA MAXIMUM SPACING AND ONE IN EACH OCCUPIED ROOM.
PROVIDE STROBE NOTIFICATION ONLY IN ALL TOILET ROOMS. PROVIDE ONE CENTRAL FIRE ALARM PANEL AT FRONT ENTRANCE
VESTIBULE OR WHERE THE LOCAL FIRE DEPARTMENT REQUIRES. INCLUDE LOCATION COORDINATION WITH LOCAL FIRE MARSHALL.
INTERLOCK TO ALL ELEVATOR CONTROL PANEL(S). PROVIDE HEAT DETECTORS IN KITCHEN AREAS. PROVIDE SHOP DRAWINGS OF
FIRE ALARM SYSTEM PRIOR TO INSTALLAION. THE FIRE ALARM SYSTEM MUST BE UL RATED, AND MEET ALL FEDERAL, STATE, AND
LOCAL REVIEWING AGENCIES.
� o
3 �
h
lc:"
¢E
' � N
� 0 N
M
s o
i x
� w
o F
Copyright 2002
All designs appearing
herein shall not be
duplicated, produced,
or otherwise used
without the written
consent of
DKO Architecture, PC.
a
O
'
U '
0
4. -+Cn
� 00 nO
�MC7� •�
�a
t
•
•
•
O
O � �
O
O
A
\ \ \�Illilllll „ /,,
920246 � a
11*1 Sze)
Phase Date
CD 04/18/05
0 j
0
0
A
Project No.
Drawn by:
0410
MJHAROLD
E2