1. THIS WORK SHALL INCLUDE ALL HEATING, VENTILATING AND AIR
CONDITIONS SYSTEMS REQUIRED AS INDICATED ON THE DRAWINGS,
AND INCLUDES BUT IS NOT LIMITED TO HEATERS, FANS, FILTERS.
CONTROLS, DUCTS, DAMPERS, GRILLES, REGISTERS, DIFFUSERS,
DUCT INSULATION, AND ALL ITEMS REQUIRED FOR COMPLETE
AND OPERABLE SYSTEMS..
2. EQUIPMENT SUPPLIED AND INSTALLED TO THE PROJECT SHALL BE
OF THE MANUFACTURER AND CAPACITY AS NOTED ON THE PLANS
(OR EQUAL SUBSTITUTIONS WITH PRIOR WRITTEN APPROVAL ONLY).
THE MECHANICAL SYSTEMS HAS BEEN DESIGNED AS A COMPLETE
PACKAGE; MECHANICAL CONTRACTOR SHALL VERIFY THAT ALL
EQUIPMENT, CONTROLS, AND MISC. ITEMS BE SUPPLIED TO
PROVIDE A COMPLETE AND OPERABLE SYSTEM.
3. SUPPLY DUCTWORK TRUCKS:
SHALL BE SHEET METAL OF THE PROPER GAGE FOR THE DUCT
SIZE AND AIR VOLUME HANDLED. BRACE AS REQUIRED FOR
THE DUCT SIZE AND AIR VOLUME HANDLED.
SECONDARY SUPPLY DUCTWORK:
SHALL BE SHEET METAL, EXTERNALLY INSULATED, EXCEPT FOR
THE LAST T; EACH DIFFUSER CONNECTION TO BE INSULATED
FLEXDUCT. ALL ROUND SECONDARY DUCTS TO BE SECURELY
SUPPORTED WITHOUT SAGS OR KINKS, AND TO HAVE LOCKING
QUADRANT DAMPERS AT MAIN TRUNK CONNECTION.
4. RETURN AIR DUCTWORK
TRUNKS SHALL BE SHEET METAL OF THE PROPER GAGE FOR THE
DUCT SIZE AND AIR VOLUME HANDLED. BRACE AS REQUIRED FOR
THE DUCT SIZE AND AIR VOLUME HANDLED. RETURN AIR TRUNK
TO EXTEND MINIMUM OF 10' FROM UNIT CURB CONNECTION
AS INDICATED.
NOTE: ALL SYSTEMS ABOVE 2000 CFM SHALL HAVE RETURN AIR
FIRESTATS AS REQUIRED PER STATE AND LOCAL CODES
COMPLETELY INSTALLED AS A PART OF THIS WORK. ALL SYSTEMS
SHALL BE COMPLETE WITH ALL FIRE DAMPERS AS REQUIRED PER
STATE AND LOCAL CODES.
5. ALL DUCTWORK SHALL BE SECURELY HUNG AND FASTENED TO
PRIMARY OR SECONDARY STRUCTURAL MEMBERS ONLY.
6. PROVIDE ALL NECESSARY ISOLATORS, CONNECTORS, DAMPERS AND
VOLUME CONTROLS FOR A COMPLETE AND CONTROLLABLE
MECHANICAL SYSTEM.
7. GRILLES AND DIFFUSERS SHALL BE AS NOTED ON THE PLANS (OR
EQUAL SUBSTITUTIONS WITH PRIOR WRITTEN APPROVAL ONLY).
PROVIDE ALL NECESSARY SPIN -INS, TAKE -OFFS, DAMPERS
SUPPORTS, CONNECTORS AND MISC. ITEMS FOR A COMPLETE
INSULATION.
8. EXHAUST FANS SHALL BE AS NOTED ON THE PLANS (OR EQUAL
SUBSTITUTIONS WITH PRIOR WRITTEN APPROVAL ONLY). PROVIDE
ALL NECESSARY HOODS, FLASHING, DAMPERS, CONTROLS,
DUCTING, SUPPORTS, AND MISC. ITEMS FOR A COMPLETE
INSTALLATION.
9. MECHANICAL CONTRACTOR SHALL BE FAMILIAR WITH THE WORK OF
ALL TRADES AND VERIFY /COORDINATE HIS WORK WITH OTHER
TRADES PRIOR TO THE BEGINNING OF WORK.
10. START -UP AND BALANCING SHALL BE COMPLETED IMMEDIATELY
BEFORE OCCUPANCY OF THE FACILITY BY THE OWNER. A SIGNED
COPY OF THE BALANCING REPORT SHALL BE DELIVERED TO THE
OWNER UPON OCCUPANCY.
11. ALL ROOF TOP UNITS SHALL HAVE ECONOMIZERS SET TO 15%
MINIMUM FRESH AIR INTAKE.
12. MECHANICAL CONTRACTOR SHALL INCLUDE ALL CONTROLS, CONDUIT
AND CONTROL WIRING FOR ALL HVAC CONTROL SYSTEMS.
13. ALL REQUIRED PERMITS, LICENSES, INSPECTION AND TEST CODES
SHALL BE A PART OF THIS WORK.
14. ALL HEATING Ft COOLING SYSTEMS TO HAVE PROGRAMMABLE
MICROELECTRONIC THERMOSTATS WITH ACCESS CODE AND
FAN CONTROL FEATURE.
15. MECHANICAL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH
ITS UNDERWRITERS LABORATORY LABEL, THE MANUFACTURERS'
RECOMMENDATIONS, SPECIFICATIONS, AND GOOD ENGINEERING
PRACTICES.
16. ALL MECHANICAL EQUIPMENT SHALL BE OF AN APPROVED TYPE
AND SHALL BE LABELED FOR USE IN THE AREAS PROPOSED FOR
INSTALLATION.
PLUMBING EQUIPMENT SCHEDULE
1. PROVIDE FLOOR DRAINS OF THE FOLLOWING TYPE:
FD - CAST IRON DRAIN WITH INTRGAL TRAP, CLEANOUT, & FLASHING
COLLAR, NICKEL BRONZE ADJ. ROUND STRAINER HEAD.
2. PROVIDE CLEANOUTS OF THE FOLLOWING TYPES:
C.O. - FLOOR C.O.: EXPOSED FLUSH TYPE, STANDARD NON -SLIP SCORED
FINISH, SMITH #4043. AND SIM. w/ CARPET MARKER #4023Y.
W.C.O. - WALL C.O.: CAST IRON BODY ADAPTABLE TO PIPE w /CAST
CLEANOUT BRONZE OR BRASS PLUG; STAINLESS STEEL COVER INCL.
SCREWS, SMITH #4710.
MEA 3. PROVIDE WATER HAMMER ARRESTORS - SIZED AND INSTALLED BY P.C.
PLUMBING FIXTURE SCHEDULE
P -1 TANK TYPE WATER CLOSET - AMERICAN STANDARD MODEL #2124, 336: OR
APPROVED EQUAL 14" ROUGH, 18" RIM HEIGHT AND GRAB BARS, COMPLETE
WITH CHURCH SEAT AND ALL FITTINGS FOR USE AND WHITE COLOR (U.N.O.)
P -2 HDCP. WALL MNTD. SINK - AMERICAN STANDARD WHITMAN MODEL:
19" x 17" W.H. TYPE WITH BACKSPLASH AND 4" CENTERS: WHITE COLOR
(U.N.O.): HORITAGE TYPE FAUCETS AND FITTINGS COMPLETE FOR USE.
MOUNTING HEIGHT TO MEET A.D.A. AND CODE COMPLIANCES: ALSO
"P" TRAP AND SUPPLIES TO BE INSULATED PER CODE. (REINFORCE
WALL FOR PROPER MOUNTING.)
P -3 WATER HEATER - 20 GALLON ELECTRIC WATER HEATER WITH ALL, PIPING, FITTINGS,
P.& T. VALVE, LIMIT TO 105- WATER, INSULATE ALL PIPES, AND OVERFLOW PAN TO
DRAIN, COMPLETE FOR IMMEDIATE USE. AMERICAN STD. OR APPROVED EQUAL.
P -4 HDCP. COUNTER MNTD. SINK - STAINLESS STEEL COUNTER MOUNTED:
17" x 17"
MOUNTING HEIGHT TO MEET A.D.A. AND CODE COMPLIANCES: ALSO
"P" TRAP AND SUPPLIES TO BE INSULATED PER CODE. (REINFORCE
WALL FOR PROPER MOUNTING.)
P -J NITROUS OXIDE & OXYGEN MANIFOLD SYSTEM -
REQUIRES LPORSK COPPER LIINES USILVER SOLDERLDNTOATRUNK LINES MBER
RUNNING TO EACH TREATMENT ROOM. PRESSURE TESTED WITH DRY NITROGEN
TO 150 PSI FOR 24 HOURS BY PLUMBER.
NOTE: ABOVE FIXTURES AND MODEL NUMBERS ARE FOR REFERENCE ONLY,
SIMILAR MODELS AND MANUFACTURES MAY BE USED ONLY WITH APPROVAL
OF TENANT - ALL FIXTURES SHALL BE APPROVED BY TENANT & LANDLORD.
SHUT OFF VALVE.
LOCATE ABOVE CEILING
�
WC -1 2..
ONE
L -1
3/4"
ob
WATER RISER DIAGRAM
`p
Scale: N.T.S.
3" VTR
N
2"
N C
2..
C/O
I FD -1
L
0
WC -1
U) °'
SEWER
L 1 RISER
C.O.
05
WASTE VENT RISER DIAGRAM
�•2
Scale: N.T.S.
MAXIMUM OF 7 FT. OF
FLEXIBLE DUCT UPSTREAM
01 a
OF DIFFUSER
3
vpLUME
DAF�PER� F��T LE
AIFLOW' I
D�CT N T C
I IgD,
RA�ED DE
0
CEILING
DIFFUSER DESIGN 4ASEQ
ON TITUS MODEL MSA
PATTERN CONTROLLER VANE
f:64�-
TYP. DUCT CONNECTION TO We
A2.2
Scale: N.T.S.
CONFIRM OPENING
SIZE WITH HVAC
VARIES UNIT SUPPLIER VARIES
3 1/2• X 3 1/2• X 1/4•
ANGLE FRAME
3 1/2• X 3 1/2' X 1/4•
ANGLES WELD TO JOISTS
PLAN VIEW
03
ROOFTOP UNIT SUPPORT FRAME
kA2.2
Scale: N.T.S.
COORDINATE FLASHING REQUIREMENTS
WITH HVAC UNIT SUPPLIER
PRE - FORMED ROOF CURB MEMBRANE FLASHING
BY HVAC CONTR.
PRE - FORMED
ROOF MEMBRANE CANT STRIP
ROOF INSUL.
METAL DECK
3 1/2• X 3 1/2• X 1/4•
ANGLE FRAME
3 1/2" X 3 1/2' X 1/4-
ANGLES WELD TO JOISTS
JL FIELD VERIFY -
JOIST LOCATIONS
SECTION VIEW
ro=2
ROOFTOP UNIT SUPPORT FRAME
A
Scale: N.T.S.
MECHANICAL NOTES:
1. THIS WORK SHALL INCLUDE ALL HEATING, VENTILATING AND AIR
CONDITIONS SYSTEMS REQUIRED AS INDICATED ON THE DRAWINGS,
AND INCLUDES BUT IS NOT LIMITED TO HEATERS, FANS, FILTERS.
CONTROLS, DUCTS, DAMPERS, GRILLES, REGISTERS, DIFFUSERS,
DUCT INSULATION, AND ALL ITEMS REQUIRED FOR COMPLETE
AND OPERABLE SYSTEMS..
2. EQUIPMENT SUPPLIED AND INSTALLED TO THE PROJECT SHALL BE
OF THE MANUFACTURER AND CAPACITY AS NOTED ON THE PLANS
(OR EQUAL SUBSTITUTIONS WITH PRIOR WRITTEN APPROVAL ONLY).
THE MECHANICAL SYSTEMS HAS BEEN DESIGNED AS A COMPLETE
PACKAGE; MECHANICAL CONTRACTOR SHALL VERIFY THAT ALL
EQUIPMENT, CONTROLS, AND MISC. ITEMS BE SUPPLIED TO
PROVIDE A COMPLETE AND OPERABLE SYSTEM.
3. SUPPLY DUCTWORK TRUCKS:
SHALL BE SHEET METAL OF THE PROPER GAGE FOR THE DUCT
SIZE AND AIR VOLUME HANDLED. BRACE AS REQUIRED FOR
THE DUCT SIZE AND AIR VOLUME HANDLED.
SECONDARY SUPPLY DUCTWORK:
SHALL BE SHEET METAL, EXTERNALLY INSULATED, EXCEPT FOR
THE LAST T; EACH DIFFUSER CONNECTION TO BE INSULATED
FLEXDUCT. ALL ROUND SECONDARY DUCTS TO BE SECURELY
SUPPORTED WITHOUT SAGS OR KINKS, AND TO HAVE LOCKING
QUADRANT DAMPERS AT MAIN TRUNK CONNECTION.
4. RETURN AIR DUCTWORK
TRUNKS SHALL BE SHEET METAL OF THE PROPER GAGE FOR THE
DUCT SIZE AND AIR VOLUME HANDLED. BRACE AS REQUIRED FOR
THE DUCT SIZE AND AIR VOLUME HANDLED. RETURN AIR TRUNK
TO EXTEND MINIMUM OF 10' FROM UNIT CURB CONNECTION
AS INDICATED.
NOTE: ALL SYSTEMS ABOVE 2000 CFM SHALL HAVE RETURN AIR
FIRESTATS AS REQUIRED PER STATE AND LOCAL CODES
COMPLETELY INSTALLED AS A PART OF THIS WORK. ALL SYSTEMS
SHALL BE COMPLETE WITH ALL FIRE DAMPERS AS REQUIRED PER
STATE AND LOCAL CODES.
5. ALL DUCTWORK SHALL BE SECURELY HUNG AND FASTENED TO
PRIMARY OR SECONDARY STRUCTURAL MEMBERS ONLY.
6. PROVIDE ALL NECESSARY ISOLATORS, CONNECTORS, DAMPERS AND
VOLUME CONTROLS FOR A COMPLETE AND CONTROLLABLE
MECHANICAL SYSTEM.
7. GRILLES AND DIFFUSERS SHALL BE AS NOTED ON THE PLANS (OR
EQUAL SUBSTITUTIONS WITH PRIOR WRITTEN APPROVAL ONLY).
PROVIDE ALL NECESSARY SPIN -INS, TAKE -OFFS, DAMPERS
SUPPORTS, CONNECTORS AND MISC. ITEMS FOR A COMPLETE
INSULATION.
8. EXHAUST FANS SHALL BE AS NOTED ON THE PLANS (OR EQUAL
SUBSTITUTIONS WITH PRIOR WRITTEN APPROVAL ONLY). PROVIDE
ALL NECESSARY HOODS, FLASHING, DAMPERS, CONTROLS,
DUCTING, SUPPORTS, AND MISC. ITEMS FOR A COMPLETE
INSTALLATION.
9. MECHANICAL CONTRACTOR SHALL BE FAMILIAR WITH THE WORK OF
ALL TRADES AND VERIFY /COORDINATE HIS WORK WITH OTHER
TRADES PRIOR TO THE BEGINNING OF WORK.
10. START -UP AND BALANCING SHALL BE COMPLETED IMMEDIATELY
BEFORE OCCUPANCY OF THE FACILITY BY THE OWNER. A SIGNED
COPY OF THE BALANCING REPORT SHALL BE DELIVERED TO THE
OWNER UPON OCCUPANCY.
11. ALL ROOF TOP UNITS SHALL HAVE ECONOMIZERS SET TO 15%
MINIMUM FRESH AIR INTAKE.
12. MECHANICAL CONTRACTOR SHALL INCLUDE ALL CONTROLS, CONDUIT
AND CONTROL WIRING FOR ALL HVAC CONTROL SYSTEMS.
13. ALL REQUIRED PERMITS, LICENSES, INSPECTION AND TEST CODES
SHALL BE A PART OF THIS WORK.
14. ALL HEATING Ft COOLING SYSTEMS TO HAVE PROGRAMMABLE
MICROELECTRONIC THERMOSTATS WITH ACCESS CODE AND
FAN CONTROL FEATURE.
15. MECHANICAL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH
ITS UNDERWRITERS LABORATORY LABEL, THE MANUFACTURERS'
RECOMMENDATIONS, SPECIFICATIONS, AND GOOD ENGINEERING
PRACTICES.
16. ALL MECHANICAL EQUIPMENT SHALL BE OF AN APPROVED TYPE
AND SHALL BE LABELED FOR USE IN THE AREAS PROPOSED FOR
INSTALLATION.
PLUMBING EQUIPMENT SCHEDULE
1. PROVIDE FLOOR DRAINS OF THE FOLLOWING TYPE:
FD - CAST IRON DRAIN WITH INTRGAL TRAP, CLEANOUT, & FLASHING
COLLAR, NICKEL BRONZE ADJ. ROUND STRAINER HEAD.
2. PROVIDE CLEANOUTS OF THE FOLLOWING TYPES:
C.O. - FLOOR C.O.: EXPOSED FLUSH TYPE, STANDARD NON -SLIP SCORED
FINISH, SMITH #4043. AND SIM. w/ CARPET MARKER #4023Y.
W.C.O. - WALL C.O.: CAST IRON BODY ADAPTABLE TO PIPE w /CAST
CLEANOUT BRONZE OR BRASS PLUG; STAINLESS STEEL COVER INCL.
SCREWS, SMITH #4710.
MEA 3. PROVIDE WATER HAMMER ARRESTORS - SIZED AND INSTALLED BY P.C.
PLUMBING FIXTURE SCHEDULE
P -1 TANK TYPE WATER CLOSET - AMERICAN STANDARD MODEL #2124, 336: OR
APPROVED EQUAL 14" ROUGH, 18" RIM HEIGHT AND GRAB BARS, COMPLETE
WITH CHURCH SEAT AND ALL FITTINGS FOR USE AND WHITE COLOR (U.N.O.)
P -2 HDCP. WALL MNTD. SINK - AMERICAN STANDARD WHITMAN MODEL:
19" x 17" W.H. TYPE WITH BACKSPLASH AND 4" CENTERS: WHITE COLOR
(U.N.O.): HORITAGE TYPE FAUCETS AND FITTINGS COMPLETE FOR USE.
MOUNTING HEIGHT TO MEET A.D.A. AND CODE COMPLIANCES: ALSO
"P" TRAP AND SUPPLIES TO BE INSULATED PER CODE. (REINFORCE
WALL FOR PROPER MOUNTING.)
P -3 WATER HEATER - 20 GALLON ELECTRIC WATER HEATER WITH ALL, PIPING, FITTINGS,
P.& T. VALVE, LIMIT TO 105- WATER, INSULATE ALL PIPES, AND OVERFLOW PAN TO
DRAIN, COMPLETE FOR IMMEDIATE USE. AMERICAN STD. OR APPROVED EQUAL.
P -4 HDCP. COUNTER MNTD. SINK - STAINLESS STEEL COUNTER MOUNTED:
17" x 17"
MOUNTING HEIGHT TO MEET A.D.A. AND CODE COMPLIANCES: ALSO
"P" TRAP AND SUPPLIES TO BE INSULATED PER CODE. (REINFORCE
WALL FOR PROPER MOUNTING.)
P -J NITROUS OXIDE & OXYGEN MANIFOLD SYSTEM -
REQUIRES LPORSK COPPER LIINES USILVER SOLDERLDNTOATRUNK LINES MBER
RUNNING TO EACH TREATMENT ROOM. PRESSURE TESTED WITH DRY NITROGEN
TO 150 PSI FOR 24 HOURS BY PLUMBER.
NOTE: ABOVE FIXTURES AND MODEL NUMBERS ARE FOR REFERENCE ONLY,
SIMILAR MODELS AND MANUFACTURES MAY BE USED ONLY WITH APPROVAL
OF TENANT - ALL FIXTURES SHALL BE APPROVED BY TENANT & LANDLORD.
MECHANICAL/ PLUMBING PLAN
Scale: 1/4" = 1' -0"
PLUMBING GENERAL NOTES
1. ALL PLUMBING WORK SHALL BE IN ACCORDANCE WITH ALL CURRENT
LOCAL, STATE, AND FEDERAL CODES AND ORDINANCES.
2. P.C. SHALL COORDINATE WITH OWNER ON ALL INTERIOR AND EXTERIOR HOSE
BIBBS NEEDED. INSTALL VACUUM BREAKERS AND SHUT -OFF VALVES AS READ.
3. PLUMBING CONTRACTOR (P.C.) SHALL PROVIDE ALL READ. VALVING,
PIPING, MISC. ITEMS, AND WATER HAMMER ARRESTORS, PER CODE
AND WHERE APPLICABLE TO COMPLETE THIS PROJECT FOR USE.
4. PROVIDE WOOD BLOCKING BEHIND FIXTURES AND GRAB BARS PER
ADA RECOMENDATIONS.
5. SLOPE ALL DRAINS PER CODE AND CONNECTIONS SHALL ALSO BE
PER CODE. - WASTE
6. ALL SUPPLY PIPING SHALL BE INSULATED AGAINST FREEZING.
WHERE LOCATED ABOVE INSULATION. IT SHALL BE THE PLUMBING
CONTRACTORS RESPONSIBILITY TO INDICATE SUPPLY PIPING
FROM METER TO FIXTURES WITH OWNER AND G.C.
7. ALL WORK SHALL CONFORM TO STATE AND LOCAL PLUMBING AND BACKFLOW
PREVENTION CODES AND THE SPECIFICATIONS OF THE FORT WAYNE WATER UTILITY.
8. ALL WATER LINES 3" AND LARGER MUST BE DISINFECTED, SAMPLES FROM TWO CONSEC-
UATIVE DAYS MUST BE TAKEN TO AN APPROVED TESTING LAB, AND THE LAB ANALYSIS
REPORTS MUST BE SUBMITTED TO THE DEVEL. SERVICES DEPT. SHOWING THAT THE
SAMPLES HAVE PASSED THE TESTS PER ANSI /AWWA C651 -92, THE AWWA STD. FOR
DISINFECTING WATER MAINS.
9. VACUUM BREAKERS MUST BE INSTALLED ON ALL EXISTING OR PROPOSED HOSE BIBBS, MOP/
SERVICE SINKS, WALL /YARD HYDRANTS.
10. BACKFLOW DEVICES ARE TO BE TESTED UPON INSTALLATION AND THEN PERIODICALLY THERE-
AFTER PER STATE CODE. SUBMIT COPIES OF TESTS TO THE DEVELOPEMENT SERVICES DEPT.
11. INCOMING WATER SUPPLY LINE IS SIZED WITHOUT CONSIDERATION OF EATING ES-
TABLISHMENTS OR TENANTS REQUIRING ADDITIONAL WATER SUPPLY, LARGER INCOMING SERVICE
MAY BE REQUIRED OTHERWISE. IT SHALL BE DETERMINED BETWEEN P.C. AND LANDLORD PRIOR
TO CONSTRUCTION ON WATER SERVICE SIZE TO BUILDING. IT ALSO SHALL BE THE RESPONSIBILITY
BETWEEN THE LANDLORD AND THE P.C. (PLUMBING CONTRACTOR) ON PROVIDING /INSTALLING
SEPERATE TENANT METERING.
CV I- o
+'
O �
�
ONE
0
of
`p
MECHANICAL/ PLUMBING PLAN
Scale: 1/4" = 1' -0"
PLUMBING GENERAL NOTES
1. ALL PLUMBING WORK SHALL BE IN ACCORDANCE WITH ALL CURRENT
LOCAL, STATE, AND FEDERAL CODES AND ORDINANCES.
2. P.C. SHALL COORDINATE WITH OWNER ON ALL INTERIOR AND EXTERIOR HOSE
BIBBS NEEDED. INSTALL VACUUM BREAKERS AND SHUT -OFF VALVES AS READ.
3. PLUMBING CONTRACTOR (P.C.) SHALL PROVIDE ALL READ. VALVING,
PIPING, MISC. ITEMS, AND WATER HAMMER ARRESTORS, PER CODE
AND WHERE APPLICABLE TO COMPLETE THIS PROJECT FOR USE.
4. PROVIDE WOOD BLOCKING BEHIND FIXTURES AND GRAB BARS PER
ADA RECOMENDATIONS.
5. SLOPE ALL DRAINS PER CODE AND CONNECTIONS SHALL ALSO BE
PER CODE. - WASTE
6. ALL SUPPLY PIPING SHALL BE INSULATED AGAINST FREEZING.
WHERE LOCATED ABOVE INSULATION. IT SHALL BE THE PLUMBING
CONTRACTORS RESPONSIBILITY TO INDICATE SUPPLY PIPING
FROM METER TO FIXTURES WITH OWNER AND G.C.
7. ALL WORK SHALL CONFORM TO STATE AND LOCAL PLUMBING AND BACKFLOW
PREVENTION CODES AND THE SPECIFICATIONS OF THE FORT WAYNE WATER UTILITY.
8. ALL WATER LINES 3" AND LARGER MUST BE DISINFECTED, SAMPLES FROM TWO CONSEC-
UATIVE DAYS MUST BE TAKEN TO AN APPROVED TESTING LAB, AND THE LAB ANALYSIS
REPORTS MUST BE SUBMITTED TO THE DEVEL. SERVICES DEPT. SHOWING THAT THE
SAMPLES HAVE PASSED THE TESTS PER ANSI /AWWA C651 -92, THE AWWA STD. FOR
DISINFECTING WATER MAINS.
9. VACUUM BREAKERS MUST BE INSTALLED ON ALL EXISTING OR PROPOSED HOSE BIBBS, MOP/
SERVICE SINKS, WALL /YARD HYDRANTS.
10. BACKFLOW DEVICES ARE TO BE TESTED UPON INSTALLATION AND THEN PERIODICALLY THERE-
AFTER PER STATE CODE. SUBMIT COPIES OF TESTS TO THE DEVELOPEMENT SERVICES DEPT.
11. INCOMING WATER SUPPLY LINE IS SIZED WITHOUT CONSIDERATION OF EATING ES-
TABLISHMENTS OR TENANTS REQUIRING ADDITIONAL WATER SUPPLY, LARGER INCOMING SERVICE
MAY BE REQUIRED OTHERWISE. IT SHALL BE DETERMINED BETWEEN P.C. AND LANDLORD PRIOR
TO CONSTRUCTION ON WATER SERVICE SIZE TO BUILDING. IT ALSO SHALL BE THE RESPONSIBILITY
BETWEEN THE LANDLORD AND THE P.C. (PLUMBING CONTRACTOR) ON PROVIDING /INSTALLING
SEPERATE TENANT METERING.