HomeMy WebLinkAbout05050050.47APPLICABLE CODES AND ORDINANCES: A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE. B. ENTIRE INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH APPLICABLE CODES AND ORDINANCES. C. SECURE AND PAY FOR ALL REQUIRED PERMITS. D. PROVIDE A MINIMUM OF 10' -0" BETWEEN EXHAUST OUTLETS, PLUMBING VENTS AND ALL OUTSIDE AIR INTAKES. E. CONTRACTOR SHALL NOT LOCATE ANY DUCT OR PIPING DIRECTLY OVER ANY ELECTRICAL PANEL, SWITCHGEAR, TRANSFORMER, ETC. COORDINATE LOCATIONS OF DUCTS AND PIPING WITH THE ELECTRICAL CONTRACTOR TO AVOID THESE CONFLICTS. ARCHITECT: A. CONTRACTOR SHALL BE GUIDED BY THE ARCHITECT'S REFLECTED CEILING PLAN FOR EXACT LOCATION OF DIFFUSERS, REGISTERS AND GRILLES UNLESS OTHERWISE NOTED. B. COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS, LIGHTING, AND OTHER CEILING ITEMS AND MAKE MINOR DUCT MODIFICATIONS TO SUIT. C. EXTERIOR LOUVERS ARE INDICATED FOR INFORMATION ONLY. DETAILED DESCRIPTIONS ARE PROVIDED IN THE ARCHITECTURAL SPECIFICATIONS. D. FURNISH ALL MATERIAL AND EQUIPMENT AS SPECIFIED, EXCEPT WHERE SPECIFIC APPROVAL FOR SUBSTITUTION IS GIVEN BY THE ARCHITECT /ENGINEER. GENERAL: A. THESE DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF TERMINATION FOR PIPING, DUCTWORK, CONDUIT, ETC. THE EQUIPMENT SHOWN ILLUSTRATES SUGGESTED ROUTING, BUT ALL NECESSARY OFFSETS AND FITTINGS MAY NOT BE SHOWN. CONTRACTOR SHALL INSTALL HIS WORK IN A MANNER THAT WILL CONFORM WITH THE STRUCTURE. CONTRACTOR SHALL AVOID OBSTRUCTIONS, PRESERVE HEAD ROOM AND MAINTAIN MAXIMUM CLEARANCE WITHOUT ADDITIONAL COST TO THE OWNER. B. ALL DIMENSIONS SHOWN ON THESE PLANS ARE IN FEET AND /OR INCHES UNLESS OTHERWISE NOTED. C. MECHANICAL WORK SHALL BE COMPLETE IN EVERY DETAIL AND ALL MISCELLANEOUS ITEMS OF MATERIAL AND LABOR NECESSARY TO COMPLETE THE WORK DESCRIBED, SHOWN OR REASONABLY IMPLIED ON DRAWINGS OR SPECIFICATIONS, SHALL BE INCLUDED IN THE CONTRACT. D. PROPOSAL SHALL BE BASED ON SPECIFIED MATERIAL AND EQUIPMENT. IN ORDER TO PROMOTE COMPETITION, HOWEVER, BIDDERS MAY SUBMIT ALTERNATE PROPOSALS ON ANY ALTERNATE MATERIALS AND /OR EQUIPMENT THEY WISH TO PROPOSE, INCLUDING ANY PRICE CHANGES AFFECTED BY ACCEPTANCE OF ALTERNATIVES. THESE MUST BE PROVIDED IN ADDITION TO THE BASE BID, NOT IN PLACE OF THE BASE BID. E. CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. F. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS. G. PROVIDE VIBRATION ISOLATION AS SPECIFIED FOR ALL MECHANICAL EQUIPMENT TO PREVENT TRANSMISSION OF VIBRATION TO BUILDING STRUCTURE. H. PROVIDE VIBRATION ISOLATORS FOR ALL PIPING SUPPORTS CONNECTED TO AND WITHIN 50 FEET OF ISOLATED EQUIPMENT (EXCEPT AT BASE ELBOW SUPPORTS AND ANCHOR POINTS) THROUGHOUT MECHANICAL EQUIPMENT ROOMS. I. THE LOCATION OF EXISTING UNDERGROUND UTILITIES IS SHOWN IN AN APPROXIMATE WAY ONLY. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. THE CONTRACTOR SHALL PAY FOR AND REPAIR ALL DAMAGES CAUSED BY FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UNDERGROUND UTILITIES UNLESS OTHERWISE INDICATED. J. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL, STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ON OTHER CONTRACT DOCUMENT DRAWINGS. K. EACH RESPECTIVE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE INSTALLATION OF HIS WORK WITH THE WORK OF OTHER CONTRACTORS AND TRADES PRIOR TO THE INSTALLATION. L. MAINTAIN A MINIMUM OF 6' -8" CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS, SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL ROOMS. M. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING INSULATION IS APPLIED. N. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND DOWNSTREAM AS RECOMMENDED BY THE MANUFACTURER FOR APPROPRIATE ACCURACY. 0. WORK SHALL INCLUDE STARTUP OF ALL SYSTEMS, FURNISHING OF OPERATING AND MAINTENANCE INSTRUCTIONS AND ONE (1) YEAR GUARANTEE, COMMENCING ON DATE OF ACCEPTANCE BY THE OWNER OR AS OTHERWISE SPECIFIED. P. TESTING, ADJUSTING, AND BALANCING AGENCY SHALL BE BY A MEMBER OF THE ASSOCIATED AIR BALANCE COUNCIL (AABC) OR THE NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB). TESTING, ADJUSTING, AND BALANCING SHALL BE PERFORMED IN ACCORDANCE WITH THE AABC STANDARDS. Q. WHERE TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED, THE PRODUCT OF ONE MANUFACTURER SHALL BE USED UNLESS OTHERWISE NOTED. HVAC GENERAL NOTES R. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS' CERTIFIED DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DUCT AND PIPING DIMENSIONS BEFORE FABRICATION. S. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST CONDITIONS AND RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND SHALL HAVE THE APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO NOT SCALE DRAWINGS. T. ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND /OR AS SHOWN IN DETAILS FOR PIPING, DUCTWORK, AND EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR. U. PROVIDE ACCESS PANELS FOR INSTALLATION IN WALLS AND CEILINGS, WHERE REQUIRED, TO SERVICE DAMPERS, VALVES, SMOKE DETECTORS, AND OTHER CONCEALED MECHANICAL EQUIPMENT. ACCESS PANELS SHALL BE TURNED OVER TO GENERAL CONTRACTOR FOR INSTALLATION. V. ALL EQUIPMENT, PIPING, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED, SPECIFIED, AND /OR REQUIRED TO PROVIDE A VIBRATION FREE INSTALLATION. W. ALL DUCTWORK, PIPING, AND EQUIPMENT SUPPORTED FROM STRUCTURAL STEEL SHALL BE COORDINATED WITH THE GENERAL CONTRACTOR. ALL ATTACHMENTS TO STEEL BAR JOISTS, TRUSSES, OR JOIST GIRDERS SHALL BE AT PANEL POINTS. PROVIDE BEAM CLAMPS MEETING MSS STANDARDS. WELDING TO STRUCTURAL MEMBERS SHALL NOT BE PERMITTED. THE USE OF C- CLAMPS SHALL NOT BE PERMITTED. X. MECHANICAL EQUIPMENT, DUCTWORK, AND PIPING SHALL NOT BE SUPPORTED FROM METAL DECK. Y. ALL ROOF MOUNTED EQUIPMENT CURBS FOR EQUIPMENT PROVIDED BY THE MECHANICAL CONTRACTOR SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR AND INSTALLED BY THE GENERAL CONTRACTOR. Z. LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE COORDINATED WITH ALL OTHER TRADES. AA. ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE FIRE STOPPED WITH A PRODUCT SIMILAR TO 3M OR EQUAL. PRODUCT SHALL BE LISTED BY UL OR FM AND MEET THE REQUIREMENTS OF LOCAL AND STATE CODES. BB. ALL AIR CONDITIONING CONDENSATE DRAIN LINES FROM EACH AIR HANDLING UNIT OR ROOFTOP UNIT SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, WITH "P" TRAP, AND PIPED TO THE NEAREST DRAIN OR ROOF DECK. SEE DETAILS SHOWN ON THE DRAWINGS OR THE CONTRACT SPECIFICATIONS FOR DEPTH OF AIR CONDITIONING CONDENSATE TRAPS. CC. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION. DD. ALL VALVES, COILS, DAMPERS, ETC. SHALL BE INSTALLED ALLOWING EASY ACCESS TO THEM. AREAS ADJACENT TO THE ACCESS PANELS SHALL BE CLEAR OF OBSTRUCTION. EE. FURNISH AND INSTALL ALL EQUIPMENT AND MATERIAL REQUIRED TO COMPLETE THE INSTALLATION AS SHOWN ON THE DRAWINGS. FF. EQUIPMENT SIZES AND SERVICE SPACE REQUIREMENTS MAY VARY BETWEEN DIFFERENT MANUFACTURERS. CONSULT APPROVED MANUFACTURER DRAWINGS AS SUBMITTED AND COORDINATE WITH THESE DRAWINGS. GG. REFER TO MECHANICAL DETAILS FOR ADDITIONAL EQUIPMENT REQUIREMENTS. HVAC /SHEETMETAL: A. CERTAIN ITEMS SUCH AS RISES AND DROPS IN DUCTWORK, ACCESS DOORS, VOLUME DAMPERS, ETC., ARE INDICATED ON THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY FOR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR THESE ITEMS. B. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR DIMENSIONS. C. ALL AIR HANDLING UNITS SHALL OPERATE WITHOUT MOISTURE CARRYOVER. D. LOCATE ALL MECHANICAL EQUIPMENT (SINGLE DUCT, VARIABLE VOLUME BOXES, CEILING HEATERS, WALL HEATERS, ETC.) FOR UNOBSTRUCTED ACCESS TO UNIT ACCESS PANELS, CONTROLS, AND VALVING E. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS (SUPPLY, RETURN, AND EXHAUST) CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE POINT OF CONNECTION TO THE EQUIPMENT UNLESS OTHERWISE NOTED. F. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO THE UNDERSIDE OF THE STRUCTURE, WITH SPACE FOR INSULATION AND BELOW ANY REQUIRED PIPING. G. RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 5' -0 ". FLEXIBLE DUCT SHALL NOT BE USED AS AN ELBOW. PROVIDE SHEET METAL ELBOW AT DIFFUSER NECK WHERE TAP IS NOT OUT OF THE BOTTOM OF THE SUPPLY MAIN. H. ALL DUCTWORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN DUCTS, INCLUDING DIVIDED DUCTS AND TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER. I. SMOKE DETECTORS SHALL BE FURNISHED AND INSTALLED BY UNIT MANUFACTURER. J. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION AND COSTS ASSOCIATED TO OTHER TRADE WITH THE USE OF EQUIPMENT OTHER THAN THAT LISTED AS BASIS OF DESIGN. K. SEE SPECIFICATIONS FOR DUCTWORK GAUGES, BRACING, HANGERS, AND OTHER REQUIREMENTS. L. CONTRACTOR SHALL NOT LOCATE ANY DUCT OR PIPING DIRECTLY OVER ANY ELECTRICAL PANELS, SWITCHGEAR, TRANSFORMER, ETC. COORDINATE LOCATIONS OF DUCTS AND PIPING WITH THE ELECTRICAL CONTRACTOR TO AVOID THESE CONFLICTS. M. ALL DUCTS PENETRATING SHAFT WALLS SHALL BE SEALED AIRTIGHT WITH FIRESTOP. N. PROVIDE VOLUME DAMPERS UPSTREAM OF ALL AIR INLETS /OUTLETS UNLESS OTHERWISE NOTED. 0. ALL ROOFTOP UNITS SHALL BE ACCESSED FROM THE ROOF. P. POWER FOR ALL ROOFTOP UNITS SHALL BE WIRED BY THE ELECTRICAL CONTRACTOR AND SHALL BE PLACED ON A DEDICATED CIRCUIT. Q. LOCATE ROOFTOP UNITS ON ROOF. COORDINATE WITH STRUCTURAL PLANS. SET UNITS AS REQUIRED TO ALLOW SUPPLY AND RETURN OPENINGS TO CLEAR ROOF STRUCTURE. R. UNLESS OTHERWISE NOTED ALL DUCTWORK ABOVE CEILINGS SHALL BE INSULATED WITH 14" DUCTWRAP. DUCTWRAP SHALL BE .75 LB. DENSITY. S. MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL A 3 "x3 "xJ" STEEL ANGLE FRAME AROUND EACH ROOFTOP UNIT ROOF OPENING. FIELD WELD FRAMES TO TOP OF JOISTS. LOCATE ROOFTOP UNITS ON ROOF SO THAT THE DUCT DROPS WILL CLEAR THE ROOF STRUCTURE. RELATED CONTROLS: A. MECHANICAL CONTRACTOR SHALL PROVIDE A DDC T -STAT FOR EACH VAV BOX. PROVIDE 50' SLACK CABLE FOR RELOCATION OF T -STAT DURING TENNANT BUILDOUT. RELATED ELECTRICAL AND PLUMBING: A. UNLESS OTHERWISE NOTED ALL LOW VOLTAGE WIRING (24 VOLTS) SHALL BE PROVIDED AND INSTALLED BY THE MECHANICAL CONTRACTOR. THIS INCLUDES FANS, RADIANT HEATERS, ROOFTOP UNITS, ETC. B. UNLESS OTHERWISE NOTED LINE VOLTAGE WIRING (120 VOLTS OR GREATER) SHALL BE PROVIDED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. C. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE AND DIVISION 16 OF THE SPECIFICATIONS. D. CONDENSATE DRAIN PIPE RUN OUT SIZE SHALL BE A MINIMUM OF 1" TO NEAREST DRAIN. E. FURNISH AND INSTALL GAS PIPING FOR ROOFTOP UNITS. EXTEND PIPING FROM METER LOCATION TO UNITS ACROSS ROOF UNLESS OTHERWISE NOTED ON PLUMBING PLANS. F. FURNISH AND INSTALL A GAS COCK AT EACH UNIT CONNECTION. G. REFER TO ELECTRICAL AND PLUMBING DRAWINGS FOR ADDITIONAL COORDINATION WITH THESE DRAWINGS. H. ANY UNIT SUPPLIED WITH NATURAL OR LP GAS SHALL BE FURNISHED WITH PRESSURE REGULATORS BY UNIT MANUFACTURER. RELATED GENERAL CONSTRUCTION: A. UNLESS OTHERWISE NOTED FLASHING OF ROOF OPENINGS WILL BE DONE BY THE GENERAL CONTRACTOR. DELIVER ROOFTOP UNIT AND EXHAUST FAN CURBS TO GENERAL CONTRACTOR FOR INSTALLATION. CONTACT GENERAL CONTRACTOR TO COORDINATE THIS PORTION OF THE WORK. SUBSTITUTIONS: A. COST OF ANY CHANGES REQUIRED BY OTHER TRADES DUE TO SUBSTITUTION OF ALTERNATE EQUIPMENT SHALL BE INCLUDED IN THE MECHANICAL CONTRACTOR'S ALTERNATE PROPOSAL. UTILITIES: A. UNLESS OTHERWISE NOTED THE LOCAL GAS COMPANY SHALL PROVIDE GAS TO THE BUILDING AND FURNISH AND INSTALL THE METER. CONNECTION TO THE METER AND EXTENSION OF THE PIPING SHALL BE MADE IN ACCORDANCE WITH THE UTILITY COMPANY REQUIREMENTS. B. CONTACT LOCAL UTILITY COMPANY TO ARRANGE FOR GAS METER INSTALLATION. FURNISH AND INSTALL PIPING AND SPECIALTIES AS REQUIRED TO RECEIVE METER. C. VERIFY LOCAL CONDITIONS AT THE SITE. 17 PEDCOR DESIGN GROUP Architecture / Project Managment: 335 Ridgepoint Drive Carmel, Indiana 46032 317.705.7979 (phone) 317.705.7980 (fax) © Copyright 2004 ��� • •• �('1$TE�'•, S �jii �0�. �"' •.�� S -o No. 13968 i 0 STATE ' ijjz OF S/ ONA 1 E�-0 Consulting Engineer: JOHN OBERLIES C INC. Mechanical • Electrical • C­1 • Sanitary Developer: P E D C O R ?ip awAw DEVELOPMENT CO. (n Project: W U O� m WO06� �Z a Q �o � C z � w £ N m d O U D W d Issue Date Drawn By Checked By 02/28/2005 Jtl 51h Revisions: Project Number: 0401.00 MEI 24187 Sheet Title: Building #4 & #5 HVAC Symbols and General Notes Sheet Number lil 1()() HVAC SYMBOLS AND ABBREVIATIONS ABBREVIATIONS PIPING SYMBOLS ACC AIR COOLED CONDENSER FT FOOT TWP TOWER WATER PUMP DROP —10 ACCU AIR COOLED CONDENSING UNIT F &T TRAP FLOAT AND THERMOSTATIC TRAP UH UNIT HEATER (GAS) HOT WATER SUPPLY ACHP AIR COOLED HEAT PUMP FTR FIN TUBE RADIATION UV UNIT VENTILATOR (CLASSROOM) HOT WATER RETURN - - - - - -- AFF ABOVE FINISH FLOOR G GAS VAV VARIABLE AIR VOLUME BOX PITCH DOWN IN DIRECTION OF ARROW AHU AIR HANDLING UNIT GC GENERAL CONTRACTOR VD VOLUME DAMPER RUN OUT —__40 AP ACCESS PANEL GPM GALLONS PER MINUTE WB WET BULB RUN OUT OFF BOTTOM OF MAIN —�- AS AIR SEPARATOR H HUMIDIFIER WT WEIGHT RUN OUT OFF TOP OF MAIN B BOILER (HOT WATER OR STEAM) HC REHEAT COIL (HOT WATER) TEE OFF SIDE OF MAIN BDD BACKDRAFT DAMPER HDR HEAVY DUTY REGISTER OR GRILLE BOD BOTTOM OF DUCT HPS HIGH PRESSURE STEAM (101 -200 PSIG) C CHILLER HT -X SHELL AND TUBE HEAT EXCHANGER CAL COMBUSTION AIR LOUVER HYD HYDRONIC CC CABINET CONVECTOR HX PLATE AND FRAME HEAT EXCHANGER CD CEILING DIFFUSER (SUPPLY AIR) HWP HOT WATER PUMP CEF CEILING EXHAUST FAN HWR HOT WATER RETURN CFM CUBIC FEET PER MINUTE HWS HOT WATER SUPPLY CH CABINET UNIT HEATER (ELECTRIC OR HW) IN INCH CHWP CHILLED WATER PUMP IRH INFRA -RED SPACE HEATER (GAS FIRED) CHWR CHILLED WATER RETURN KEC KITCHEN EQUIPMENT CONTRACTOR CHWS CHILLED WATER SUPPLY LAT LEAVING AIR TEMPERATURE CT COOLING TOWER LPS LOW PRESSURE STEAM (0 -15 PSIG) SHEET METAL SYMBOLS CP CONDENSATE PUMP (STEAM) LS LINEAR SLOT DIFFUSER FIRE DAMPER 1 CW COLD WATER MAN MANUAL DB DRY BULB MFR MANUFACTURER COMBINATION SMOKE /FIRE DAMPER lso DG DOOR GRILLE MBH 1000 BTUH VOLUME DAMPER OR - F DL DRUM LOUVER MC MECHANICAL CONTRACTOR SUPPLY DIFFUSER 0 DIAMETER MCC MOTOR CONTROL CENTER SUPPLY DUCT RISER EADB ENTERING AIR DRY BULB MPS MEDIUM PRESSURE STEAM (16 -100 PSIG) RETURN DUCT RISER 0 EAWB ENTERING AIR WET BULB OA OUTSIDE AIR SUPPLY REGISTER CEO EBR ELECTRIC BASEBOARD RADIATION OAL OUTSIDE AIR LOUVER LINEAR DIFFUSER EC ELECTRICAL CONTRACTOR PD PRESSURE DROP FLEXIBLE CONNECTION ECH ELECTRIC CABINET HEATER PDU POOL DEHUMIDIFICATION UNIT RETURN AIR GRILLE ECR EGGCRATE GRILLE PRV PRESSURE RELEIF VALVE EXHAUST GRILLE EDH ELECTRIC DUCT HEATER PSI POUNDS PER SQUARE INCH EXHAUST FAN COoR D EF EXHAUST FAN PTAC PACKAGE TERMINAL AIR CONDITIONER TEMPERATURE CONTROL SYMBOLS EG EXHAUST GRILLE RA RETURN AIR ROOM THERMOSTAT OR SENSOR OR 0 OR OR a oR Q. EH EXHAUST HOOD RAC ROOM AIR CONDITIONER (THRU WALL) DRAWING SYMBOLS EHC ELECTRIC HEATING COIL RAF RETURN AIR FAN MOTOR ❑M DENOTES SECTION SECTION NUMBER EOM END OF MAIN DRIP RAL RETURN AIR LOUVER MOTORIZED DAMPER �— ER EXHAUST REGISTER RD ROUND DIFFUSER f ERC ELECTRIC REHEAT COIL RG RETURN AIR GRILLE S 1 ARROW INDICATES M1 —SHEET NUMBER ESP EXTERNAL STATIC PRESSURE RHP RADIANT HEATING PIPING DIRECTION IN WHICH WHERE SECTION SECTION IS CUT IS LOCATED ET EXPANSION TANK RL RELIEF LOUVER EVC EVAPORATIVE COOLER RPM REVOLUTIONS PER MINUTE EWH ELECTRIC WALL HEATER RTU ROOF TOP UNIT DENOTES DETAIL DETAIL NUMBER NOTE DESIGNATION F FURNACE SA SUPPLY AIR D 1 PLAN NOTES: SPECIFIC INFORMATION AS INDICATED ON A FA FACE AREA SAF SUPPLY AIR FAN M1 SHEET NUMBER WHERE DETAIL DRAWING FCRC FAN AND COIL ROOM CONDITIONER SAT SOUND ATTENUATOR IS LOCATED FCV FLOW CONTROL VALVE SD SPUTTER DAMPER LETTER DESIGNATING-,,,, ELEVATION LEADER LINE OF PLAN NOTE REFERENCED �^ DIRECTED TO ITEM OF PLAN NOTE FD FLOOR DRAIN SP STATIC PRESSURE REFERENCED FD FIRE DAMPER SPA -D SPA DEHUMIDIFICATION UNIT A 1 CIRCLE WITH NUMBER INDICATES A PLAN M1 —SHEET NUMBER NOTE REFERENCED, WITH THE NUMBER FD /SD FIRE AND SMOKE DAMPER SR SUPPLY REGISTER WHERE ELEVATION INDICATING THE ITEM NUMBER OF THE PLAN IS LOCATED NOTE REFERENCED FLA FULL LOAD AMPS ST STORAGE TANK GENERAL PLAN NOTES: GENERAL INFORMATION AS IT PERTAINS FPHB FREEZE PROOF HOSE BIBB TCC TEMPERATURE CONTROL CONTRACTOR ONLY TO THE DRAWING IT IS ON FPM FEET PER MINUTE TD THERMAL DIFFUSER GENERAL NOTES: GENERAL INFORMATION PERTAINING TO ALL THE DRAWINGS OF THE FPVAV FAN POWERED VARIABLE AIR VOLUME BOX TSP TOTAL STATIC PRESSURE DISCIPLINE IT IS ON APPLICABLE CODES AND ORDINANCES: A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE. B. ENTIRE INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH APPLICABLE CODES AND ORDINANCES. C. SECURE AND PAY FOR ALL REQUIRED PERMITS. D. PROVIDE A MINIMUM OF 10' -0" BETWEEN EXHAUST OUTLETS, PLUMBING VENTS AND ALL OUTSIDE AIR INTAKES. E. CONTRACTOR SHALL NOT LOCATE ANY DUCT OR PIPING DIRECTLY OVER ANY ELECTRICAL PANEL, SWITCHGEAR, TRANSFORMER, ETC. COORDINATE LOCATIONS OF DUCTS AND PIPING WITH THE ELECTRICAL CONTRACTOR TO AVOID THESE CONFLICTS. ARCHITECT: A. CONTRACTOR SHALL BE GUIDED BY THE ARCHITECT'S REFLECTED CEILING PLAN FOR EXACT LOCATION OF DIFFUSERS, REGISTERS AND GRILLES UNLESS OTHERWISE NOTED. B. COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS, LIGHTING, AND OTHER CEILING ITEMS AND MAKE MINOR DUCT MODIFICATIONS TO SUIT. C. EXTERIOR LOUVERS ARE INDICATED FOR INFORMATION ONLY. DETAILED DESCRIPTIONS ARE PROVIDED IN THE ARCHITECTURAL SPECIFICATIONS. D. FURNISH ALL MATERIAL AND EQUIPMENT AS SPECIFIED, EXCEPT WHERE SPECIFIC APPROVAL FOR SUBSTITUTION IS GIVEN BY THE ARCHITECT /ENGINEER. GENERAL: A. THESE DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF TERMINATION FOR PIPING, DUCTWORK, CONDUIT, ETC. THE EQUIPMENT SHOWN ILLUSTRATES SUGGESTED ROUTING, BUT ALL NECESSARY OFFSETS AND FITTINGS MAY NOT BE SHOWN. CONTRACTOR SHALL INSTALL HIS WORK IN A MANNER THAT WILL CONFORM WITH THE STRUCTURE. CONTRACTOR SHALL AVOID OBSTRUCTIONS, PRESERVE HEAD ROOM AND MAINTAIN MAXIMUM CLEARANCE WITHOUT ADDITIONAL COST TO THE OWNER. B. ALL DIMENSIONS SHOWN ON THESE PLANS ARE IN FEET AND /OR INCHES UNLESS OTHERWISE NOTED. C. MECHANICAL WORK SHALL BE COMPLETE IN EVERY DETAIL AND ALL MISCELLANEOUS ITEMS OF MATERIAL AND LABOR NECESSARY TO COMPLETE THE WORK DESCRIBED, SHOWN OR REASONABLY IMPLIED ON DRAWINGS OR SPECIFICATIONS, SHALL BE INCLUDED IN THE CONTRACT. D. PROPOSAL SHALL BE BASED ON SPECIFIED MATERIAL AND EQUIPMENT. IN ORDER TO PROMOTE COMPETITION, HOWEVER, BIDDERS MAY SUBMIT ALTERNATE PROPOSALS ON ANY ALTERNATE MATERIALS AND /OR EQUIPMENT THEY WISH TO PROPOSE, INCLUDING ANY PRICE CHANGES AFFECTED BY ACCEPTANCE OF ALTERNATIVES. THESE MUST BE PROVIDED IN ADDITION TO THE BASE BID, NOT IN PLACE OF THE BASE BID. E. CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. F. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS. G. PROVIDE VIBRATION ISOLATION AS SPECIFIED FOR ALL MECHANICAL EQUIPMENT TO PREVENT TRANSMISSION OF VIBRATION TO BUILDING STRUCTURE. H. PROVIDE VIBRATION ISOLATORS FOR ALL PIPING SUPPORTS CONNECTED TO AND WITHIN 50 FEET OF ISOLATED EQUIPMENT (EXCEPT AT BASE ELBOW SUPPORTS AND ANCHOR POINTS) THROUGHOUT MECHANICAL EQUIPMENT ROOMS. I. THE LOCATION OF EXISTING UNDERGROUND UTILITIES IS SHOWN IN AN APPROXIMATE WAY ONLY. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. THE CONTRACTOR SHALL PAY FOR AND REPAIR ALL DAMAGES CAUSED BY FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UNDERGROUND UTILITIES UNLESS OTHERWISE INDICATED. J. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL, STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ON OTHER CONTRACT DOCUMENT DRAWINGS. K. EACH RESPECTIVE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE INSTALLATION OF HIS WORK WITH THE WORK OF OTHER CONTRACTORS AND TRADES PRIOR TO THE INSTALLATION. L. MAINTAIN A MINIMUM OF 6' -8" CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS, SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL ROOMS. M. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING INSULATION IS APPLIED. N. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND DOWNSTREAM AS RECOMMENDED BY THE MANUFACTURER FOR APPROPRIATE ACCURACY. 0. WORK SHALL INCLUDE STARTUP OF ALL SYSTEMS, FURNISHING OF OPERATING AND MAINTENANCE INSTRUCTIONS AND ONE (1) YEAR GUARANTEE, COMMENCING ON DATE OF ACCEPTANCE BY THE OWNER OR AS OTHERWISE SPECIFIED. P. TESTING, ADJUSTING, AND BALANCING AGENCY SHALL BE BY A MEMBER OF THE ASSOCIATED AIR BALANCE COUNCIL (AABC) OR THE NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB). TESTING, ADJUSTING, AND BALANCING SHALL BE PERFORMED IN ACCORDANCE WITH THE AABC STANDARDS. Q. WHERE TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED, THE PRODUCT OF ONE MANUFACTURER SHALL BE USED UNLESS OTHERWISE NOTED. HVAC GENERAL NOTES R. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS' CERTIFIED DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DUCT AND PIPING DIMENSIONS BEFORE FABRICATION. S. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST CONDITIONS AND RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND SHALL HAVE THE APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO NOT SCALE DRAWINGS. T. ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND /OR AS SHOWN IN DETAILS FOR PIPING, DUCTWORK, AND EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR. U. PROVIDE ACCESS PANELS FOR INSTALLATION IN WALLS AND CEILINGS, WHERE REQUIRED, TO SERVICE DAMPERS, VALVES, SMOKE DETECTORS, AND OTHER CONCEALED MECHANICAL EQUIPMENT. ACCESS PANELS SHALL BE TURNED OVER TO GENERAL CONTRACTOR FOR INSTALLATION. V. ALL EQUIPMENT, PIPING, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED, SPECIFIED, AND /OR REQUIRED TO PROVIDE A VIBRATION FREE INSTALLATION. W. ALL DUCTWORK, PIPING, AND EQUIPMENT SUPPORTED FROM STRUCTURAL STEEL SHALL BE COORDINATED WITH THE GENERAL CONTRACTOR. ALL ATTACHMENTS TO STEEL BAR JOISTS, TRUSSES, OR JOIST GIRDERS SHALL BE AT PANEL POINTS. PROVIDE BEAM CLAMPS MEETING MSS STANDARDS. WELDING TO STRUCTURAL MEMBERS SHALL NOT BE PERMITTED. THE USE OF C- CLAMPS SHALL NOT BE PERMITTED. X. MECHANICAL EQUIPMENT, DUCTWORK, AND PIPING SHALL NOT BE SUPPORTED FROM METAL DECK. Y. ALL ROOF MOUNTED EQUIPMENT CURBS FOR EQUIPMENT PROVIDED BY THE MECHANICAL CONTRACTOR SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR AND INSTALLED BY THE GENERAL CONTRACTOR. Z. LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE COORDINATED WITH ALL OTHER TRADES. AA. ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE FIRE STOPPED WITH A PRODUCT SIMILAR TO 3M OR EQUAL. PRODUCT SHALL BE LISTED BY UL OR FM AND MEET THE REQUIREMENTS OF LOCAL AND STATE CODES. BB. ALL AIR CONDITIONING CONDENSATE DRAIN LINES FROM EACH AIR HANDLING UNIT OR ROOFTOP UNIT SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, WITH "P" TRAP, AND PIPED TO THE NEAREST DRAIN OR ROOF DECK. SEE DETAILS SHOWN ON THE DRAWINGS OR THE CONTRACT SPECIFICATIONS FOR DEPTH OF AIR CONDITIONING CONDENSATE TRAPS. CC. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION. DD. ALL VALVES, COILS, DAMPERS, ETC. SHALL BE INSTALLED ALLOWING EASY ACCESS TO THEM. AREAS ADJACENT TO THE ACCESS PANELS SHALL BE CLEAR OF OBSTRUCTION. EE. FURNISH AND INSTALL ALL EQUIPMENT AND MATERIAL REQUIRED TO COMPLETE THE INSTALLATION AS SHOWN ON THE DRAWINGS. FF. EQUIPMENT SIZES AND SERVICE SPACE REQUIREMENTS MAY VARY BETWEEN DIFFERENT MANUFACTURERS. CONSULT APPROVED MANUFACTURER DRAWINGS AS SUBMITTED AND COORDINATE WITH THESE DRAWINGS. GG. REFER TO MECHANICAL DETAILS FOR ADDITIONAL EQUIPMENT REQUIREMENTS. HVAC /SHEETMETAL: A. CERTAIN ITEMS SUCH AS RISES AND DROPS IN DUCTWORK, ACCESS DOORS, VOLUME DAMPERS, ETC., ARE INDICATED ON THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY FOR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR THESE ITEMS. B. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR DIMENSIONS. C. ALL AIR HANDLING UNITS SHALL OPERATE WITHOUT MOISTURE CARRYOVER. D. LOCATE ALL MECHANICAL EQUIPMENT (SINGLE DUCT, VARIABLE VOLUME BOXES, CEILING HEATERS, WALL HEATERS, ETC.) FOR UNOBSTRUCTED ACCESS TO UNIT ACCESS PANELS, CONTROLS, AND VALVING E. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS (SUPPLY, RETURN, AND EXHAUST) CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE POINT OF CONNECTION TO THE EQUIPMENT UNLESS OTHERWISE NOTED. F. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO THE UNDERSIDE OF THE STRUCTURE, WITH SPACE FOR INSULATION AND BELOW ANY REQUIRED PIPING. G. RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 5' -0 ". FLEXIBLE DUCT SHALL NOT BE USED AS AN ELBOW. PROVIDE SHEET METAL ELBOW AT DIFFUSER NECK WHERE TAP IS NOT OUT OF THE BOTTOM OF THE SUPPLY MAIN. H. ALL DUCTWORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN DUCTS, INCLUDING DIVIDED DUCTS AND TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER. I. SMOKE DETECTORS SHALL BE FURNISHED AND INSTALLED BY UNIT MANUFACTURER. J. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION AND COSTS ASSOCIATED TO OTHER TRADE WITH THE USE OF EQUIPMENT OTHER THAN THAT LISTED AS BASIS OF DESIGN. K. SEE SPECIFICATIONS FOR DUCTWORK GAUGES, BRACING, HANGERS, AND OTHER REQUIREMENTS. L. CONTRACTOR SHALL NOT LOCATE ANY DUCT OR PIPING DIRECTLY OVER ANY ELECTRICAL PANELS, SWITCHGEAR, TRANSFORMER, ETC. COORDINATE LOCATIONS OF DUCTS AND PIPING WITH THE ELECTRICAL CONTRACTOR TO AVOID THESE CONFLICTS. M. ALL DUCTS PENETRATING SHAFT WALLS SHALL BE SEALED AIRTIGHT WITH FIRESTOP. N. PROVIDE VOLUME DAMPERS UPSTREAM OF ALL AIR INLETS /OUTLETS UNLESS OTHERWISE NOTED. 0. ALL ROOFTOP UNITS SHALL BE ACCESSED FROM THE ROOF. P. POWER FOR ALL ROOFTOP UNITS SHALL BE WIRED BY THE ELECTRICAL CONTRACTOR AND SHALL BE PLACED ON A DEDICATED CIRCUIT. Q. LOCATE ROOFTOP UNITS ON ROOF. COORDINATE WITH STRUCTURAL PLANS. SET UNITS AS REQUIRED TO ALLOW SUPPLY AND RETURN OPENINGS TO CLEAR ROOF STRUCTURE. R. UNLESS OTHERWISE NOTED ALL DUCTWORK ABOVE CEILINGS SHALL BE INSULATED WITH 14" DUCTWRAP. DUCTWRAP SHALL BE .75 LB. DENSITY. S. MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL A 3 "x3 "xJ" STEEL ANGLE FRAME AROUND EACH ROOFTOP UNIT ROOF OPENING. FIELD WELD FRAMES TO TOP OF JOISTS. LOCATE ROOFTOP UNITS ON ROOF SO THAT THE DUCT DROPS WILL CLEAR THE ROOF STRUCTURE. RELATED CONTROLS: A. MECHANICAL CONTRACTOR SHALL PROVIDE A DDC T -STAT FOR EACH VAV BOX. PROVIDE 50' SLACK CABLE FOR RELOCATION OF T -STAT DURING TENNANT BUILDOUT. RELATED ELECTRICAL AND PLUMBING: A. UNLESS OTHERWISE NOTED ALL LOW VOLTAGE WIRING (24 VOLTS) SHALL BE PROVIDED AND INSTALLED BY THE MECHANICAL CONTRACTOR. THIS INCLUDES FANS, RADIANT HEATERS, ROOFTOP UNITS, ETC. B. UNLESS OTHERWISE NOTED LINE VOLTAGE WIRING (120 VOLTS OR GREATER) SHALL BE PROVIDED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. C. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE AND DIVISION 16 OF THE SPECIFICATIONS. D. CONDENSATE DRAIN PIPE RUN OUT SIZE SHALL BE A MINIMUM OF 1" TO NEAREST DRAIN. E. FURNISH AND INSTALL GAS PIPING FOR ROOFTOP UNITS. EXTEND PIPING FROM METER LOCATION TO UNITS ACROSS ROOF UNLESS OTHERWISE NOTED ON PLUMBING PLANS. F. FURNISH AND INSTALL A GAS COCK AT EACH UNIT CONNECTION. G. REFER TO ELECTRICAL AND PLUMBING DRAWINGS FOR ADDITIONAL COORDINATION WITH THESE DRAWINGS. H. ANY UNIT SUPPLIED WITH NATURAL OR LP GAS SHALL BE FURNISHED WITH PRESSURE REGULATORS BY UNIT MANUFACTURER. RELATED GENERAL CONSTRUCTION: A. UNLESS OTHERWISE NOTED FLASHING OF ROOF OPENINGS WILL BE DONE BY THE GENERAL CONTRACTOR. DELIVER ROOFTOP UNIT AND EXHAUST FAN CURBS TO GENERAL CONTRACTOR FOR INSTALLATION. CONTACT GENERAL CONTRACTOR TO COORDINATE THIS PORTION OF THE WORK. SUBSTITUTIONS: A. COST OF ANY CHANGES REQUIRED BY OTHER TRADES DUE TO SUBSTITUTION OF ALTERNATE EQUIPMENT SHALL BE INCLUDED IN THE MECHANICAL CONTRACTOR'S ALTERNATE PROPOSAL. UTILITIES: A. UNLESS OTHERWISE NOTED THE LOCAL GAS COMPANY SHALL PROVIDE GAS TO THE BUILDING AND FURNISH AND INSTALL THE METER. CONNECTION TO THE METER AND EXTENSION OF THE PIPING SHALL BE MADE IN ACCORDANCE WITH THE UTILITY COMPANY REQUIREMENTS. B. CONTACT LOCAL UTILITY COMPANY TO ARRANGE FOR GAS METER INSTALLATION. FURNISH AND INSTALL PIPING AND SPECIALTIES AS REQUIRED TO RECEIVE METER. C. VERIFY LOCAL CONDITIONS AT THE SITE. 17 PEDCOR DESIGN GROUP Architecture / Project Managment: 335 Ridgepoint Drive Carmel, Indiana 46032 317.705.7979 (phone) 317.705.7980 (fax) © Copyright 2004 ��� • •• �('1$TE�'•, S �jii �0�. �"' •.�� S -o No. 13968 i 0 STATE ' ijjz OF S/ ONA 1 E�-0 Consulting Engineer: JOHN OBERLIES C INC. Mechanical • Electrical • C­1 • Sanitary Developer: P E D C O R ?ip awAw DEVELOPMENT CO. (n Project: W U O� m WO06� �Z a Q �o � C z � w £ N m d O U D W d Issue Date Drawn By Checked By 02/28/2005 Jtl 51h Revisions: Project Number: 0401.00 MEI 24187 Sheet Title: Building #4 & #5 HVAC Symbols and General Notes Sheet Number lil 1()()