L I fE 5Ar-ETY 0017E NOTES
APPLICABLE CODE:
2003 INDIANA BUILDING CODE (IBC)
OCCUPANCY CLASSIFICATIONS:
REPAIR GARAGE
- 5-1 OCCUPANCY [311.1]
OFFICE
- B OCCUPANCY [304.1]
CONSTRUCTION TYPE:
TYPE VB (COMBUSTIBLE, UNPROTECTED) CONSTRUCTION,
BASED UPON ALLOWABLE AREA FOR 5-1 OCCUPANCY [302.3.2, 503.11
LOWABLE AREA FOR S -1/13 OCCUPANCY BUILDING AREA:
TABULAR AREA:
Q,0005F TABLE 503
SPRINKLER INCREASE:
+ 21,000 5F SEC. 5063
FRONTAGE INCREASE:
+ 63505F 5EC. 506.2
ALLOWABLE AREA 15T FLOOR:
42,150 5F
ACTUAL AREA:
11,320 5F
BUILDING ELEMENTS - FIRE RESISTIVE REQUIREMENTS:
BUILDING ELEMENTS, INCLUDING STRUCTURAL FRAME, FLOORS,
AND ROOF ARE PERMITTED TO BE OF COMBUSTIBLE, UNPROTECTED
CONSTRUCTION. [TABLE 6011
EXTERIOR NONBEARING WAL.5 ARE PERMITTED TO BE OF NONRATED,
COMBUSTIBLE CONSTRUCTION, SINCE HAVING MORE THAN 10 FEET OF
FIRE SEPARATION DISTANCE [TABLE 6021
OCCUPANCY SEPARATIONS:
2 -HOUR FIRE BARRIER REQUIRED TO SEPARATE THE REPAIR
GARAGE FROM THE REST OF THE BUILDING [406.6]
INCIDENTAL USE SEPARATIONS:
STORAGE ROOMS OVER 100 SQUARE FEET ARE REQUIRED TO BE
PROVIDED WITH WALL5 TO DECK AND SELF- CLOSING DOOR5
[TABLE 302.1.11
AUTOMATIC SPRINKLERS:
AUTOMATIC SPRINKLERS ARE REQUIRED, BASED UPON 5 -1
OCCUPANCY REPAIR GARAGE FIRE AREA EXCEEDING 12,000
SQUARE FEET [x032.10.1]
FIRE ALARM SYSTEM:
FIRE ALARM 5Y5TEM NOT REQUIRED FOR 5-1 OCCUPANCY
OR FOR B OCCUPANCIES WITH AN OCCUPANT LOAD OF LESS
THAN 500 [9012]
SMOKE DETECTORS.
SMOKE DETECTORS ARE REQUIRED FOR HVAC SHUTDOWN
FOR 5Y5TEM5 DELIVERING IN EXCESS OF 2,000 CFM
[606.1, IMC]
LIFE SAFETY PLAN NOTES
L.I ML. MOUNTED FIRE EXTINW15HER.