HomeMy WebLinkAbout0825.96.41I
24„
6.62"
N
A
MATERIALS SCHEDULE
ITEM QTY. DESCRIPTION
1 1 HOFFMAN NEMA 1 RATED ENCLOSURE, MODEL #A24N24A (24" X 24" X '-
6.62") WITH INTERIOR MOUNTING PANEL AND LOCKING HANDLE, MODEL
#A -L12B
2 1 PER SQUARE D CIRCUIT BREAKER, MODEL #QOU215, 120 1AC, 15 AMP, 2 POLE
DISPENSER
OTOKHEIM 3 SQUARE D CIRCUIT BREAKER, MODEL 40OU220, 120 VAC, 20-AMP. 2 POLE
GILBARC0 1 >
WAYNE 1
O4 1 PER SQUARE D GENERAL PURPOSE RELAY, MODEL #RS43VO2, TYPE K, CLASS
DISPENSER 8501, 10 AMP, 3 POLE, 120 VAC COIL WITH SNAP MOUNT SOCKET,
MODEL #NR43 _
5O 1 PER SQUARE D DEFINITE PURPOSE CONTACTOR, MODEL #DPA12VO2, CLASS 1
SUBM. PUMP 8910, 20 AMP, 2 POLE, 120 VAC COIL
O QUANTITY 1 2
SQUARE D DEFINITE PURPOSE CONTACTOR, MODEL #OPA62V02, CLASS
TOKHEIM :!� 5 -5 8910, 60 AMP, 2 POLE, 120 VAC COIL
GILBARCO --4 >4
WAYNE --7 -7
O7 AS REQUIRED SQUARE D TERMINAL BLOCK, MODEL #GC6, CLASS 9080, SOLDER•LESS BOX
LUG, 60OV, 65 AMP - END BARRIER: MODEL #MFEM6 ;
8O 8 SQUARE D TERMINAL BLOCK END CLAMP, MODEL #MHA10 .• '
9 AS REQUIRED SQUARE D TERMINAL BLOCK, MODEL #GMG, CLASS 9080, SOLDERLESS BOX
LUG, 60OV, 30 AMP - END BARRIER: MODEL #GM68
10 AS REQUIRED SQUARE D STANDARD CHANNEL, MODEL #MH220, CLASS 9080, 35 MM WIDTH `
11 1 SQUARE D GROUNDING BUS, MODEL #PK9GTA d INSULATOR KIT, MODEL *PKGTAB t,
12 AS REQUIRED PANDUIT
13 AS REQUIRED WIRE - COPPER, THHN OR THWN, SIZED PER NEC TABLE 310 -16 (75 C)
14 15 WIRE TIE CLAMPSy��;`'.
15 AS SHOWN LABELING
16 1 SQUARE D GENERAL PURPOSE RELAY, MODEL #RS44VO2, TYPE K, CLASS
8501, 10 AMP, 4 POLE, 120 VAC COIL WITH SNAP MOUNT SOCKET,
MODEL #NR34
CONSTRUCTION ,�
ITT;
1. THE MANUFACTURER SHALL PURCHASE ALL ITEMS LISTED IN THE MATERIAL SCHEDULE AND
INSTALL IN ACCORDANCE WITH THIS DRAWING, OEM'S INSTRUCTIONS, AND THE NATIONAL
ELECTRICAL CODE. ALL CIRCUITS SHALL BE WIRED AS NATIONAL ELECTRICAL CODE CLASS I
WIRING (ART. 725). THE DISPENSER MANAGER MUST BE "UL" LISTED AND EACH DISPENSER
MANAGER MUST BE LABELED AS SUCH.
2. INDIVIDUAL WIRES SHALL BE INSTALLED BETWEEN THE EMERGENCY STOP CONTACTOR AND EACH 4 s
CIRCUIT BREAKER AND BETWEEN EACH GROUND TERMINAL BLOCK AND THE GROUNDING BUS.
3. WIRES MAY BE JUMPERED FROM ONE LOCATION TO ANOTHER FOR THE DISPENSER LIGHTING
TERMINAL BLOCKS TO THE DISPENSER LIGHTING CIRCUIT BREAKER AND FOR WIRES M1 -CO, M2-C�,
AND M3 -CO.
4. IF THE DISPENSER MANAGER IS BEING MANUFACTURED FOR TOKHEIM DISPENSERS, THREE (3)
CIRCUIT BREAKERS ARE REQUIRED FOR DISPENSER LIGHTS. A MAXIMUM OF THREE (3)
DISPENSERS CAN BE WIRED TO EACH CIRCUIT BREAKER (FOUR (4) DISPENSERS ARE ALLOWED ON
ONE CIRCUIT BREAKER IF TWO OF THE DISPENSERS ARE DIESEL AND KEROSENE). GILBARCO AND
WAYNE ONLY REQUIRE ONE (1) CIRCUIT BREAKER FOR DISPENSER LIGHTS.
5. LABEL ALL COMPONENTS AND WIRES AS SHOWN. SUBMERSIBLE PUMP CONTACTORS (PART
#DPA12VO2) SHOULD BE LABELED WITH "P1" THROUGH "P4" ONLY. THE PRODUCT LABELS:
UNLEADED; MIDGRADE; PREMIUM; DIESEL; & KEROSENE; SHOULD ALL BE CREATED AND PLACED
WITHIN THE DISPENSER MANAGER FOR FIELD INSTALLATION. IN ADDITION, A LABEL READING':
"DISPENSER MANAGER" SHALL BE PLACED ON THE OUTSIDE OF THE ENCLOSURE DOOR, A FULL
LOAD AMPERAGE LABEL SHALL BE INCLUDED ON THE INTERIOR AS WELL AS A UL LISTING LABEL.
6. INSTALL WIRE TIE CLAMPS AS SHOWN FOR MARATHON'S USE DURING FIELD INSTALLATION.
7. ALL TERMINAL BLOCKS, CIRCUIT BREAKERS, AND GENERAL PURPOSE RELAYS SHALL BE MOUNTED
TO STANDARD 35 MM DIN -3 RAIL AS SHOWN ON THIS DRAWING. -'a
8. FOR GRAPHICAL REASONS, WIRES P1 -M1 THROUGH P4 -M2 ON THE SUBMERSIBLE PUMP
CONTACTORS HAVE NOT BEEN SHOWN. WIRES P1 -M1 THROUGH P4 -M2 SHALL BE CONNECTED TO
THEIR RESPECTIVE TERMINAL BLOCKS DIRECTLY ABOVE THE SUBMERSIBLE PUMP CONTACTORS IN xa�<
THE DISPENSER MANAGER.
9. EACH DISPENSER MANAGER SHALL BE TESTED TO VERIFY THAT IS HAS BEEN WIRED CORRECTLY.¢
10. ALL WIRING SHALL BE THWN OR THHN AND SIZED AND COLOR CODED PER THE FOLLOWING {
SCHEDULE:
DM -L1 d DM -L2: # 6 AWG - RED
DM -N1 & DM -N2: # 6 AWG - WHITE
DM -GND: # 6 AWG - GREEN r
GND - GND10: #10 AWG - GREEN >.
LT1H - LT10H: #12 AWG - BROWN y
LT1N - LT10N: -12-AWG - GREY �� r
LT01H - LT03H: #12 AWG - BROWN
LT01N - LT03N: #12 AWG - GREY . ,'•::'
L1 - L11: #12 AWG - RED
N1 - Nll: #12 AWG - GREY
P1-L1 - P4 -L1: 912 AWG - BLACK
P1 -L2 - P4 -L2: #12 AWG - BLACK `M r
P1-M1 - P4 -M1: #12 AWG - BLACK `
P1 -M2 - P4 -M2: #12 AWG - BLACK
ES -CO: #14 AWG - PURPLE
N -CO: #14 AWG - WHITE
R1H - R9H: #14 AWG - ORANGE
R1N - R9N: #14 AWG - GREY
M1 -CO A P1 -CO: #14 AWG - BLACK
M2 -CO & P2 -CO: #14 AWG - BLUE
M3 -CO & P3 -00: #14 AWG - RED
M4 -CO $ P4 -CO: #14 AWG - YELLOW
MARATHON'S PRODUCT COLOR CODE:
REGULAR UNLEADED BLACK
MIDGRADE BLUE
PREMIUM RED
DIESEL YELLOW
KEROSENE BROWN „�ti��u�niu„pi
A.
,a
Q 1995 MARATHON OIL COMPANY ? P GNSTE -i
. Q,E. NQ q� •, y , „
• 17486 :. ? /. d/49977 7-18d.3d * e.
)TE #3 %o . STATE ,. �[
Marathon Av.
) :*=Y
)RIGIN ,,,, )R MARATHON OilCompany " Fr&y. Otio 45M `
r.
NO. REVISIONS -WTR CHKR QGNR RVWR L�p
DATE DATE DATE 1 5 c ,t ,� D_I SPENSER M-ANAGER�.Y,
j ADDED ITEM #16 ETM M
MANUFACTURER DRAW I IG
x�
} - -: t
9
- SCALE HALF SIZE DATE F IL
DRFTR R.A. MOREHART
CHKR,
BUD..
DGNR K.M. MCDANIEL 5 -1 -95 YR.,. y
RVWR D. W. FOWLER' 5 -1 -95 DWO fi
F ILIuD