Loading...
HomeMy WebLinkAboutLS000FIRE PROTECTION PROGRAM SUMMARY: FPROJECT purpose of this report is to document the Fire Protection Program for Phase 1 of the Parking Garage of the Carmel City Center an fire protection requirements of the 2003 Indiana Building Code. project will consist of a new parking structure one story high. The facility will be fully sprinklered with 30 feet of yard space on al s. The major occupancy of the building will be classified as S -2. The parking garage will be Type I -A construction. APPLICABLE CODES: GOVERNING BUILDING CODES And variance Indiana Building Code -2003 (2000 International Building Code & State Amendments) Required, floor level > 30 ft. above fire department access, Class I allowed (Sec. 905.3.1, Exc. 1) Indiana Fire Code -2003 (2003 International Fire Code & State Amendments) Every required stairway ISec. 905.4(1)] Indiana Electrical Code -2005 (2005 National Electrical Code & State Amendments) Hose connection located at an intermediate landing between floors [Sec. 905.4(1)] Indiana Mechanical Code -2003 (2000 International Mechanical Code & State Amendments) - Roof connection when slope is < 4/12 or the highest landing with stair access to roof [Sec. 905.4 Indiana Plumbing Code -1999 (1997 Uniform Plumbing Code & State Amendments) (5)] Indiana Accessibility Code -2003 (Chapter I 1 of the Indiana Building Code -2003) - Additional hose connections when the most remote portion of the building is more than 200 ft. Indiana Elevator Code -2001 (ASME A -17.2 with State Amendments) from a hose connection [Sec. 905.4(6)] Indiana Energy Conservation Code (IECC) - (CABO 1992 Edition with State Amendments) CIO STANDARDS Not required NFPA 10 -1994 Portable Fire Extinguishers Required in elevator machine room (Elevator Code Sec. 8.6.1.6.5) NFPA 13 -1999 Installation of Sprinkler Systems Required (Sec. 907) NFPA 14 - 2000 Edition, Installation of Standpipes Not required (Sec. 907) NFPA 20 -1999 Edition, Installation and Use of Centrifugal Fire Pumps NFPA 37 -1990 Edition, Installation and Use of Stationary Combustion Engines and Gas Not Required NFPA 72 - 1996 National Fire Alarm Code - In air handling units over 2000 CFM to shut down the air distribution system (IMC Sec. 606) NFPA 82 -1983 Edition, Waste and Linen Handling Systems and Equipment Interior Finish OTHER LAWS AND REGULATIONS Occupancy General Administrative Rules (675 IAC 12) Sections 3- 8.14.3 and 3- 8.14.4) Americans with Disabilities Act (Federal Law) July 26, 1992 0 Fair Housing Act (Title VIII of Civil Rights Act of 1988) OCCUPANCY CLASSIFICATIONS: Parking Garage_ Group S, Division 2, Enclosed Parking Garage Class A NOTE: Although there are not A -2 or A -3 occupancies identified in the building at this time, the Class B potential for small assembly occupancies exists. General code requirements for A -2 and A -3 Class C occupancies have been included in this summary for information purposes to be used by the Interior floor finish: Architect in developing general parameters for these tenant spaces. CONSTRUCTION TYPE: Parking Garage: Type IA ALLOWABLE HEIGHT: Actual: Maximum Allowed By Code: Rooms or enclosed spaces 1 Story Unlimited Height (Table 503) ALLOWABLE AREA: Area of lower level (parking garage) 106,845 sq.ft. Unlimited (Sec. 503) Exposed Total floor area 106,845 sq.ft. Unlimited (Sec. 503) STRUCTURAL REQUIREMENTS CATEGORY PARIQNNG GARAGE 25 flame spread (IMC 604.3), 50 smoke developed (Minimum resistance) Interior bearing walls, columns and beams EXIT REQUIREMENTS Supporting roof only 2 hour (Table 601) Supporting Floors 3 hour (Table 601) Interior non - bearing walls (partitions) Non - combustible walls (Table 601) Sec. 602.2 Exterior parapet walls Not required (Sec. 704.11, Exc. 1 and 6) Exit access corridors 0 hour (B, M, S and S -2) (Table 1004.3.2.1) Vertical exit stair enclosures 2 hour (connecting garage levels and building above) Exit passageways Not less than 2 hour (Sec. 1005.3.3.2) Fire walls between maximum areas allowed 2 hour (structurally stable) by code (Table 705.4, Footnote a.) Horizontal exit fire walls 2 hour (Sec. 1005.3.5) Fire barriers As required for its individual use as vertical enclosure, incidental use areas, exit passageways, etc. 7" (Sec. 1003.3.3.3) (Sec. 706) Floors No Requirements Minimum fire resistance 2 hour 12' vertically (Sec. 1003.3.3.6) 3 hour (where separating garage from building above) (Sec. 508.2) Mezzanine floors 2 hour (Sec. 505.1) Stairways and escalators Unenclosed stairways and escalator openings shall be provided with an 18" draft curtain with Same as number of exits close- spaced sprinklers. (Sec. 707.2, Exc. 2, and NFPA 13 -5 -13.4) Shafts 2 hour (when penetrating 3 -hour separation between garage and building above) - reduction of landing width by door Supporting construction of shafts shall afford the same fire resistance rating as the shaft requirement 7" (Sec. 1003.3.3.4) (Sec.707.5) Elevator shafts 1 12" (Sec. 1003.3.3.11.6) Enclosure 2 hour (when penetrating 3 hour separation between garage and building above) Venting Required when penetrating more than three stories (3004) Drainage Required sump pump or drain required in hoistway pit (Indiana Elevator Safety Code2002, 403.3) Sec. 2.2.2.5) Elevator lobby vestibules Not required (B, M, A and S -2) (Sec. 707.14. 1) width; 1 12" gap to wall (Sec. 1003.3.3.11.3) Not required (R -2) (See Variance) Use Qmup Sgparations Required when required stair width is > 30" Furnace and boiler rooms over Smoke resistant with automatic fire suppression system (Sec. 302.1.1.1) 400,000 BTU/hour input Fire Department communications systems Refrigerant machinery rooms 1 hour or provide automatic fire suppression system (Table 302.1.1) (per IMC, Chapter 11) - width Storage rooms > 100 sq. ft. Smoke resistant with automatic fire extinguishing system (Sec. 302.1.1.1) er S aration 7' -0" (Sec. 1003.2.4) Elevator equipment rooms and 2 hour fire resistive construction (Sec. 903.3.1.1.1) hoistways (to avoid shunt strip 7" reduction of corridor width; doors cannot devices) Connected Facilities Vertical exit enclosures 2 hour fire resistive construction (Sec. 1005.2) Electrical "Rooms" swing. Electrical vaults > 600 volts 3 hour rating [IEC, Sec. 110.31 (A)] Transformers Stairways Dry Type <112 1 /2kVA Not required [IEC 450.21 (A)] > 112 12 kVA 1 hour [IEC 4502.1 (B)]; See exceptions Vaults See Section IEC 450.41 for exceptions Switch Gear - unenclosed In a vault following IEC 450.41 through 450.48; See IEC 230.212 switchgear over 35,000 volts Stairway communication system Generator rooms 1 hour fire rated enclosure (NFPA 37 -1990 Edition, Section 2- 1.1.2.2) Fire pump 1 hour fire rated enclosure with sprinklers (NFPA 20 -1999 Edition, Section 2- 7.1.1) R R f 0.2 (Sec. 1008.5. 1) Roof deck fire resistance 1 -1/2 hour (Table 601, Footnote c.3., allows fire- retardant treated wood in Type I and Storage /mechanical Type II buildings) Supporting members and joists 1 hour (Table 601) Roof surfacing class Class A or B can be used (Table 1505.1) Stairways to roofs Not required < 4 stories (Sec. 1003.3.3.12.1) 1 50 Occupants (Table 1005.2.2), 75' Common Path of Travel B, S Special fire resistance requirements below oude 3 hour separation required parking garage and first floor (Sec. 508.2 and code variance) Protection of wall in : Multiple exits: Openings in exterior walls 0 hour unlimited (Table 704.8) greater than 30 feet 1 Service Sink Openings in interior bearing walls 0 hour (Table 714.2) Openings in interior non - bearing 0 hour (Table 714.2) walls (partitions) Multiple means of egress Openings in occupancy walls 324 in 1 hour fire barriers (Table 714.2) than 50% of the required capacity (Sec. 1003.2.3) 1 12 hour in 2 hour fire barriers (Table 714.2) Openings in exit corridors 0 hour (B, M, A and S -2) (Table 714.2) Required (Sec. 1005.3.2.3) 20 minute (R -2) (Table 714.2) Openings in exit passageways 1 12 hour (Table 714.2) Openings in stair enclosures 1 12 hour (Table 714.2) Openings in vertical shafts 1 12 hour (Table 714.2) Vertical Openings: FAutom,ticklers Protection of vertical openings Penetrations by steel, ferrous or copper conduits, pipes, tubes, vents, concrete or masonry through a for fire resistive rated floors single fire - resistive floor assembly must have the annular space (between the floor and the High Rise building (Sec. 403.2) penetrating item) filled with non - combustible material to prevent the passage of flame and hot gases And variance (Sec. 711.4.1) Required, floor level > 30 ft. above fire department access, Class I allowed (Sec. 905.3.1, Exc. 1) Penetrations through a single concrete floor by steel, ferrous or copper conduits, pipes, tubes and Every required stairway ISec. 905.4(1)] vents with a maximum 6 inches nominal diameter are allowed without a shaft provided concrete, Hose connection located at an intermediate landing between floors [Sec. 905.4(1)] grout or mortar is installed the full thickness of the floor to maintain the fire - resistive rating (Sec. - Roof connection when slope is < 4/12 or the highest landing with stair access to roof [Sec. 905.4 711.4.1) (5)] Duct penetrations of more than one (1) fire -rated floor /ceiling assembly shall be located within a - Additional hose connections when the most remote portion of the building is more than 200 ft. shaft per Section 707. from a hose connection [Sec. 905.4(6)] Duct penetrations of fire -rated floor /ceiling assembly that connects not more than two (2) stories are CIO permitted without a shaft provided a fire damper is installed at the floor line. (Sec. 715.6. 1) Not required Through penetrations of only one (1) fire -rated floor /ceiling assemblies or three (3) stories or more Required in elevator machine room (Elevator Code Sec. 8.6.1.6.5) by other items shall be located within a shaft or comply with Exception 1, 2 or 3 of Section 711.4.1. Required (Sec. 907) Electrical outlet boxes of any material are permitted provided such boxes are tested for use in fire - Not required (Sec. 907) resistive rated assemblies. Penetrating items that connect not more than two (2) stories are permitted provided that the annular Not Required space (between the floor and the penetrating item) is filled with an approved material to resist the - In air handling units over 2000 CFM to shut down the air distribution system (IMC Sec. 606) assa a of flame and hot stases Sec. 711.4.3.2 Interior Finish Maximum Flame S read & Smoke Develo ed Occupancy Sprinklered (Sec. 803.4) Sections 3- 8.14.3 and 3- 8.14.4) Vertical Exits & Exit Access Corridors Rooms and Enclosed Spaces 0 Passageways & Other Exitways S C C C Class A Flame Spread of 0 -25, Smoke Development limits of 450 (Sec. 803.1) Class B Flame Spread of 26 -75, Smoke Development limits of 450 (Sec. 803.1) Class C Flame Spread of 76 -200, Smoke Development limits of 450 (Sec. 803.1) Interior floor finish: Part of elevator recall Required vertical exits and passageways Class H or DOC FF -I "Pill Test" (Sec. 804.5.1, Exc.) Corridors providing exit access Class H or DOC FF -1 "Pill Test" (Sec. 804.5.1, Exc.) Rooms or enclosed spaces Class H or DOC FF -1 "Pill Test" (Sec. 804.5. 1) Insulation considerations: Explosion relief venting Exposed 25 flame spread (Sec. 718.3), 450 smoke developed Concealed 25 flame spread (Sec. 718.2), 450 smoke developed Within plenums /ducts 25 flame spread (IMC 604.3), 50 smoke developed Piping 25 flame spread (IMC 1204.1), 50 smoke developed EXIT REQUIREMENTS Exit Sizes Exit size measured in units of feet. Minimum Maximum Unisex bathing and toilet rooms Doors Apartments/Condominiums Required to be adaptable (IBC, Shapter 11 Accessibility, Part 2) (Fair Housing Act Title VIII of Civil - width 32" minimum width (Sec. 1003.3.1.1) 4' -0" (Sec. 1003.3.1.1) - height 6' -8" (Sec. 1003.3.1.1) No Requirements Stairs accessible locations. - risers 4" (Sec. 1003.3.3.3) 7" (Sec. 1003.3.3.3) - treads 11" (Sec. 1003.3.3.3) No Requirements - maximum height between landings No Requirements 12' vertically (Sec. 1003.3.3.6) - width 44" (Sec. 1003.3.3.1) - headroom 6' -8" (Sec. 1003.3.3.2) Same as number of exits - landing width equal to stair (Sec. 1003.3.4) - reduction of landing width by door Horn/strobe units 7" (Sec. 1003.3.3.4) - trim projection 1 12" (Sec. 1003.3.3.11.6) - handrail projection Reduction in fire resistance 4 12" (Sec. 1003.3.3.11.7) - handrails 34 ", two required 38" (Sec. 1003.3.3.11.1) 403.3) Handrail within 30" of required stair Fire resistance raring may be reduced to one -hour where automatic sprinklers are installed within the width; 1 12" gap to wall (Sec. 1003.3.3.11.3) Automatic smoke detection - intermediate handrails Required when required stair width is > 30" Required, complying with Section 907.2.12.3 systems from handrail (Sec. 1003.3.3.11.2) Fire Department communications systems Corridors Fire Command Center Required, complying with Section 911 - width 44" (Sec. 1004.3.2.2) No limitations - height 7' -0" (Sec. 1003.2.4) No limitations - projections 2 -hour full demand (on- premises) 7" reduction of corridor width; doors cannot Simultaneous operation of all connected electrical equipment Connected Facilities reduce corridor width by more than W during automatically transferable to the standby source (Sec. 403.10.1.2) swing. Egress width per occupant served SSprinklered 0.2 (Table 1003.2.3) Stairways 403.10.2) Other egress components (doors, corridors, Exit signs, exit illumination and elevator car lighting shall operate within 10 seconds of failure of 0.15 (Table 1003.2.3) horizontal exits) Stairway door operation Permitted to be locked from stairway side when capable of being unlocked simultaneously without Assembly without smoke protected seating: unlatching upon signal from the fire command center (Sec. 403.11) Stairway communication system Stairways 0.3 (Sec. 1008.5.1) Other egress components 7" risers or less and 11" treads or greater 0.2 (Sec. 1008.5. 1) OcciWancy Load Factors Square Feet/Person 300 Gross Table 1003.2.2.2 Storage /mechanical Parking garage 200 Gross Table 1 003.2.2.2 Number of exits Where one exit is allowed: Occupancy Max. Ht. Story above Grade Max. Allowances B, M, A 1 50 Occupants (Table 1005.2.2), 75' Common Path of Travel B, S 2 30 Occupants (Table 1005.2.2), 75' Common Path of Travel S 1 30 Occupants (Table 1005.2.2), 100' Common Path of Travel Multiple exits: Occupant Load Min. Number of Exits 1 -500 2 (Table 1005.2.1) 1 Service Sink 501 -1000 3 (Table 1005.2.1) Distance to Restrooms: more than 1000 4 (Table 1005.2.1) Egress Width Maintained Public Facilities Multiple means of egress Shall be sized that loss of any one means of egress shall not reduce the available capacity to less ELEVATOR than 50% of the required capacity (Sec. 1003.2.3) S Gal E ess Situation Basement stair interruption Required (Sec. 1005.3.2.3) Stair access to roof Required at 4 connected stories including basements (Sec. 1003.3.3.12) Winding stairways Not permitted (Sec. 1003.3.3.8) Circular stairways Permitted (Sec. 1003.3.3.7) Spiral stairways Limited use (Sec. 1003.3.3.9) Alternating tread stair Limited use (Sec. 1003.3.3.10) Changes in elevation By ramp when less than 12" (Sec. 1003.2.7) Guard rails Required on open sides of stairs, ramps, landings > 30" above surface below (See Sec. 1003.2.12) Boiler and fuel equipment rooms over 2 exits required (Sec. 1007.1) 400,000 BTU's and 500 square feet Refrigeration machinery rooms over 2 exit required (Sec. 1007.2) 1,000 square feet Electrical rooms See IEC Sec. 110.26 (C) for situations General Panic hardware required Each door in a means of egress from an occupancy of Group A having an occupant load of 100 or more from rooms, corridors or the building (Sec. 1003.3.1.9) Door swing in direction of travel Occupant load of 50 or more (Sec. 1003.3.1.2) Separate atmosphere egress systems No requirement Maximum travel distance to exits R, M, A 250' with sprinklers (Table 1004.2.4) B 300' with sprinklers (Table 1004.2.4) S -2 400' with sprinklers (Table 1004.2.4) Common path of travel Use Groups: R -2, M, A 75' (Sec. 1004.2.5) Use Groups: B, S 100' with sprinklers (Sec. 1004.2.5, Exc. 1) Maximum dead end corridor 20' (Sec. 1004.3.2.3) 50'B Occupancies with sprinklers (Sec. 1004.3.2.3, Exc. 2) Length of dead end is less than 2.5 times the width (Sec. 1004.3.2.3, Exc. 3) Basement stair interruption Required; (Sec. 1005.3.2.3) Grade level stair discharge Enclosed until exiting the building (Sec. 1006.1) Excl;Rtion: 1. Maximum 50% of number and capacity of enclosures is permitted a. Clear path to exterior from exit enclosure (Sec. 1006. 1, Exc. 1, 1.1) b. Area of exit discharge is separated from area below with the same rating as the exit enclosure (Sec.1006.1, Exc. 1, 1.2) c. Protected by sprinklers (Sec. 1006.1, Exc. 1, 1.3) 2. Maximum 50% of number and capacity of the enclosures is permitted to egress through a vestibule. a. Area of exit discharge is separated from area below with the same rating as the exit enclosure (Sec.1006.1, Exc. 1, 1.2) b. Depth from exterior or building is not greater than 10 feet and the length is not greater than 30 ft. (Sec. 1006. 1, Exc. 2, 2.2) c. Area is separated from the remainder of the level by at least wired glass and steel frame. (Sec. 1006. 1, Exc. 2, 2.4) d. The area is only used for exit discharge (Sec. 1006. 1, Exc. 2, 2.4) Exit Lighting Required all times the building is occupied (Sec. 1003.2.11); exception for dwelling units and sleeping rooms in R -2 occupancy. Exit Signs Required if rooms requires two or more means of aggress (Sec. 1003.2.10.1); exception for dwelling units in R -2 occupancy. Emergency Lighting Required for not less than 90 minutes. (Sec. 1003.2.11.2) FIRE PROTECTION SYSTEMS FAutom,ticklers Provided for allowable area (Sec. 504.2 and 506) Allowable height (Sec. 504) UJ High Rise building (Sec. 403.2) And variance Standpipes and hoses Required, floor level > 30 ft. above fire department access, Class I allowed (Sec. 905.3.1, Exc. 1) Every required stairway ISec. 905.4(1)] Hose connection located at an intermediate landing between floors [Sec. 905.4(1)] Z - Roof connection when slope is < 4/12 or the highest landing with stair access to roof [Sec. 905.4 (5)] - Additional hose connections when the most remote portion of the building is more than 200 ft. from a hose connection [Sec. 905.4(6)] Portable Fire extinguishers CIO Parking garage Not required Elevator machine room Required in elevator machine room (Elevator Code Sec. 8.6.1.6.5) Fire Alarm Systems Required (Sec. 907) S -2 Occupancy Not required (Sec. 907) Emergency Operations Voice /alarm communication Not Required Smoke detection - In air handling units over 2000 CFM to shut down the air distribution system (IMC Sec. 606) - Elevator automatic recall by smoke or heat detection in the hoistway and smoke detection in the elevator lobbies and machine room (ANSI/ASME A17.1, Sec. 2.27.3.2.1 and NFPA 72 U- C Sections 3- 8.14.3 and 3- 8.14.4) Annunciation: 0 Water flow of sprinklers - General building alarm ^♦ W E - Signal to a constantly attended location capable of contacting the local fire department Trouble alarm - Constantly attended location; no fire department notification Tamper switch - Constantly attended location; no fire department notification Smoke detectors: Part of elevator recall - Recall elevators U - Constantly attended location; no fire department notification (NFPA 72, Sec. 3- 18.14.15) Part of HVAC units - Shut down HVAC unit - Constantly attended location; no fire department notification (Sec. 907.11) Explosion relief venting Not applicable Smoke and heat venting Not applicable ACCESSIBILITY All public and common areas in building and ADA site are required to be accessible (except IBC, Chapter 11, Accessibility Code mechanical rooms, janitor closets, tunnels etc.) Elevator Required ADA Title III, Section 36.401 IBC Chapter 11, Sec. 4.1.3 Unisex bathing and toilet rooms Required in Group A and M occupancies (IBC, Sec. 2912.1) Apartments/Condominiums Required to be adaptable (IBC, Shapter 11 Accessibility, Part 2) (Fair Housing Act Title VIII of Civil Rights Act of 1988) - Accessible route into and through the unit. -Light switches, electrical outlets, thermostats and other invironmental controls in accessible locations. - Reinforcements in bathroom walls to allow later installation of grab bars around toilet, tub, shower stall and shower seat. - Kitchens and bathrooms such that an individual in a wheelchair can maneuver about the space. Exits: First floor Required from each room/area equal to the number of exits required by the building code (Sec. 4.1.3 (9)) Above and below the first floor Same as number of exits Areas of Rescue Assistance (Sec. 4.1.3 (9)) (Exception: supervised automatic fire suppression system throughout) (Sec. 4.1.3(9)) Horn/strobe units Required - common use areas including all classrooms, restrooms, meeting rooms, etc. High Rise Building Provisions Automatic sprinkler system Required throughout (Sec. 403.2) Reduction in fire resistance Type IB construction allowed to be reduced to Type IIA in buildings with sprinkler control valves equipped with supervisory initiating devices and water flow initiating devices for each floor (Sec. 403.3) Shaft enclosures Fire resistance raring may be reduced to one -hour where automatic sprinklers are installed within the shafts at the top and at alternate floor levels (Sec. 403.3.2) Automatic smoke detection Required, complying with Section 907.2.12 Emergency voice/alarm communications Required, complying with Section 907.2.12.3 systems Fire Department communications systems Required, complying with Section 907.2.12.2 Fire Command Center Required, complying with Section 911 Elevators Operation complying with Chapter 30 Standby power, light and emergency systems Generator 2 -hour enclosure (if within building) (Sec. 403.10.1) Fuel Supply 2 -hour full demand (on- premises) Capacity Simultaneous operation of all connected electrical equipment Connected Facilities Power and lighting facilities for the fire command center, elevators and fire pump shall be automatically transferable to the standby source (Sec. 403.10.1.2) Separated circuits and fixtures Separate lighting circuits and fixtures providing not less than 1 footcandle light intensity at the floor are required for egress corridors, stairways, smoke proof enclosures, elevator cars and lobbies (Sec. 403.10.2) Emergency systems Exit signs, exit illumination and elevator car lighting shall operate within 10 seconds of failure of normal power (sec.403.10.3) Stairway door operation Permitted to be locked from stairway side when capable of being unlocked simultaneously without unlatching upon signal from the fire command center (Sec. 403.11) Stairway communication system Telephone or two -way communication system provided at not less than every fifth floor connected to an approved constantly attended station. (Sec. 403.11.1) Seismic considerations Required, complying with Chapter 16 (Sec. 403.12) PLUMBING FIXTURES Section 2902 of the 2003 Indiana Building Code allows the number of required plumbing fixtures to be based on the actual or anticipated occupant loads of the building. Factors for determining the minimum number of fixtures required per Table 29 are as follows: Storage: Water closets 1 per dwelling unit Lavatories 1 per dwelling unit Bath tubs/showers See Section 411 of International Plumbing Code Drinking fountains 1 per 1,000 Service sink 1 Service Sink Distance to Restrooms: Public Facilities 500 feet maximum (Sec. 2906) ELEVATOR Size 80" x 51" or 68" x 54" Less than four stories refer to Indiana Elevator Code Indiana Accessibility Code and ADA for minimum dimensions (Sec. 3002.4. 1) Firefighter Emergency Operations Phase I- Emergency Recall Required (Sec. 3003.2) Phase H- Emergency In -Car Operation Required (Sec. 3003.2) Stand By Power Required (Sec. 1003.2.13.3) Hoistway Venting Required (Sec. 3004.1) Fire Extinguisher Class `ABC' Required (Elevator Code Sec. 8.6.1.6.5) Hoistway Pit Drainage Sump pump or drain required (no oil separator required) (Elevator Code Sec. 2.2.2.5) (See variance) Developer: Carmel Redevelopment Commission 111 West Main Street Carmel, Indiana 46032 317.571 -2787 (ARTS) Architect: 11,��ti'R't'S1T itl / /f /1�� �G1STE�F sl d 00033126 - STATE OF lA1`i"' 1141 air By: KEY PLAN PARKING INFILL SCALE: NTS gP F PEDCOR DESIGN GROUP Architecture / Project Management: 335 Ridgepoint Drive Carmel, Indiana 46032 317.705.7979 (phone) 317.705.7980 (fax) 0� Project: UJ Z W CIO U 4... C ICU O U � W � U- C U� 0 ^♦ W E O CU i J 0' U 06 U COPYRIGHT & OWNERSHIP OF DOCUMENTS THIS DOCUMENT IS AN INSTRUMENT OF SERVICES AND IS THE SOLE PROPERTY OF THE ARCHITECT AND PEDCOR DESIGN GROUP. ALL INFORMATION CONTAINED HEREIN IS CONFIDENTIAL. ITS REMISSION AND DISTRIBUTION TO OTHER PARTIES IS NOT TO BE CONSTRUED AS PUBLICATION N DEROGATION OF COMMON LAW COPYRIGHT, INTELLECTUAL PROPERTY RIGHTS OR OTHER RESERVED RIGHTS. ALL INFORMATION CONTAINED HEREIN CONSTITUTES THE ORIGINAL AND UNPUBLISHED WORK OF THE ARCHTECr, JAMES R. STURMAN, AND PEOCOR DESIGN GROUP. NO PMT OR WHOLE OF THIS DESIGN, THESE DRAWINGS, OR THE RESULTING BURRING OR MALORNGS, OR PORTDNS OF THE RESULTING MADNG OR BUILDINGS MAY BE DUPLICATED, COPED, EXHIINTED, PHOTOGRAPHED, PUBLISHED, MODIFED OR OTHERWISE DISTRIBUTED N ANY WAY WITHOUT THE SPECFIC AND PRIOR WRITTEN CONSENT OF THE ARCHITECT, JAMES R. STUTDMN AND PEDCOR DESIGN GROUP. c COPYRIGHT 2DO7 JAMES R. STUT MAN, AIA, INDINAPOUS, BID SET P.1 00t BID SET P102 BID SET P,103, BID SET P,104 Set Issue Date Sheet Issue Date 12.04.06 12.04.06 n Uate: 11.21.07 QADDENDUM #001, 01 -08-07 ADDENDUM #003,02/09/07 ASI #003,05/16/07 O Motor Court Public Bid Sat, 05/18/07 2L ASI #004, 05128/07 ADD #2 MOTOR COURT /ASI.005, 08/19/07 7' ASI 0008, 9/17/07 0, 8" , Bid Sat P.102, P.103 and P.104 Issue, 11/21/07 Project Number: 0502.00 Sheet Title: Code Summary Sheet Number: LSOOO