Loading...
HomeMy WebLinkAboutT601CONDUCTOR SIZING Recommended Sizing of the Telecommunications Bonding Backbone Conductor(TBBC) and Grounding Equalizer (GE) per J- STD -607 -A The TBBC, BC, and BCT shall be copper conductors. The TBBC shall be sized at 2 kcmil per linear foot of conductor length up to a maximum size of a3 /0 AWG. The TBBC may be insulated. The Bonding conductor for Telecommunications (BCT) and Bonding Conductor (BC) shall be, as a minimum, the same size as the largest TBBC used.(1) TBBC LENGTH LINEAR M (FT) LESS THAN 4 (13') 4 -6 (14 -20') 6 -8 (21 -26') 8 -10 (27 -33') 10 -13 (34 -41') 13 -16 (42 -52') 16 -20 (53 -66') GREATER THAN 20 (66') The TEBC minimum conductor size shall be a No. 6 AWG. TBBC SIZE (AWG) 6 3 1 1/0 2/0 3/0* *3/0 may not always be available. 4/0 is a more common size that may be substituted (1). Telecommunications Industry Association, Commercial Building Grounding (Earthing) and Bonding Requirements For Telecommunications, J- STD - 607 -A, October 2002. ABBREVIATIONS TR = TELECOMMUNICATIONS ROOM BC = BONDING CONDUCTOR TBBC = TELECOMMUNICATIONS BONDING BACKBONE CONDUCTOR TEBC = TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR TMGB = TELECOMMUNICATIONS MAIN GROUNDING BUSBAR TGB = TELECOMMUNICATIONS GROUNDING BUSBAR R/C = RACK AND /OR CABINET GROUNDING BUSBAR ER = EQUIPMENT ROOM BCT = BONDING CONDUCTOR FOR TELECOMMUNICATIONS EF = ENTRANCE FACILITY GROUNDING SYSTEM NOTES: (THIS DETAIL 11 TBBC, TEBC, AND BC GROUNDING CONDUCTORS MUST BE INSTALLED IN COMPLIANCE WITH LOCAL CODES; THIS MAY REQUIRE INSTALLATION IN METALLIC CONDUIT IF RUN THROUGH PLENUM CEILING CAVITIES. 21 GROUNDING CONDUCTORS RUN THROUGH A CONDUIT SHALL BE BONDED TO THE CONDUIT AT EACH END. 31 ALL GROUND CONDUCTORS SHALL BE INSTALLED IN THE SHORTEST AND MOST DIRECT PATH PRACTICAL. 41 WHERE THE ENTRANCE FACILITY IS LOCATED IN THE ER, THE TMGB SHALL ALSO SERVE AS A TGB FOR THE ROOM; THE TBBCS REQUIRED FROM THE ER TO EACH TR ALONG THE BACKBONE CABLE PATH WILL ALSO BE USED TO CONNECT THE TGBS TO THE TMGB. 51 REMOTE CABINETS SHALL SUBSTITUTE A R/C BUSBAR IN PLACE OF THE TGB. TELECOMMUNICATIONS GROUNDING DIAGRAM Scale = NONE TELECOMMUNICATIONS SERVICE ENTRANCE FACILITY 4'x8' PLYWOOD BACKBOARD MOUNTED BEHIND ENTRANCE CONDUITS LOCATED AS INDICATED ON THE FLOORPLAN BC BONDING CONDUCTOR TO ELECTRICAL GROUNDING ELECTRODE SYSTEM IF NOT CO- LOCATED WITH BUILDING ELECTRICAL SERVICE ENTRANCE TMGB 10 0 0 SPACE RESERVED FOR ; CABLE TV SERVICE ENTRANCE - GROUND : • • CONNECTION BY UTILITY ; ........... SPACE RESERVED FOR TELEPHONE SERVICE ENTRANCE (PROTECTORS) - GROUND CONNECTION BY UTILITY 9 - BCT TO BUILDING SERVICE INTERSYSTEM BONDING CONNECTION POINT BC (SHORT AS PRACTICAL) FROM TBBC TO TGB TBBC (TYPICAL) TBBC FROM TMGB CONTINIOUS TO FARTHEST ER/TR AND BONDED TO LAST BUSBAR; INTERIM ER/TR BUSBARS ATTACH TO TBBC WITH A SHORT BC UTILIZE A SEPARATE TBBC IN EACH DIRECTION REQUIRED BY BUILDING LAYOUT TBBC(S) SHALL BE INSTALLED ALONG THE THE SHORTEST AND MOST DIRECT PATH TBBC (TYPICAL) TBBC FROM THE ER TO EACH TR - BONDED TO THE TGB AT EACH END TBBC MUST FOLLOW THE PATH OF THE BACKBONE CABLES BUILDING ELECTRICAL SERVICE ENTRANCE (LOCATED AS INDICATED ON THE FLOORPLAN) BY DIVISION 26 INTER - SYSTEM BONDING CONNECTION POINT (PER NEC 250- 92(B)) _ BY DIVISION 16 MAIN COMMON BUILDING GROUND BY DIVISION 16 TGB (TYPICAL) WORK BY DIVISION 26 LECTRICAL CONTRACTOR ELECTRICAL GROUNDING ELECTRODE SYSTEM BY DIVISION 26 ATTACHMENT TO THE ELECTRICAL GROUNDING ELECTRODE SYSTEM (BY DIVISION 26) CONNECTION (WITH APPROVED BONDING METHOD) TO NEAREST APPROVED BUILDING GROUND: 11 GROUNDED ELECTRICAL PANEL SERVING LOCAL AREA 2] GROUNDED CONDUIT SYSTEM ATTACHMENT 31 BUILDING STRUCTURAL STEEL 4] ANY COMBINATION OF THESE THAT IS ACCESSIBLE (AS DIRECTED BY DIVISION 26 TO LIMIT POTENTIAL DIFFERENCES BETWEEN TELECOMMUNICATIONS AND ELECTRICAL GROUNDING SYSTEMS) BC TO ELECTRICAL GROUNDING ELECTRODE SYSTEM =BC(S) (TYPICAL - ONE PER ROW) WORK INSIDE BY DIVISION 26 WORK OUTSIDE BY DIVISION 27 TELECOMMUNICATIONS ROOMS, EQUIPMENT ROOMS, AND REMOTE CABINETS (TYPICAL) (LOCATED AS INDICATED ON THE FLOORPLAN) TEBC(S) (TYPICAL AS REQUIRED) RACK /CABINET BUSBAR (MOUNTED ON REAR RAILS) CONTINUE TO EACH ADJACENT CABINET/ RACK BOND TO ALL RACEWAYS, OR OTHER METALLIC ITEMS IN THIS ROOM INSTALLED BELOW CEILING LINE WORK BY DIVISION 27 TELECOMM CONTRACTOR 4V4 CARMEL PEDCOR DESIGN GROUP E11�( —I i uF;�l Ss h' D Y N 1�VJ � i-A j! Q;[.5 FaSt 56th,':V +t SU T 2150 !I`D!A,`ir`S.Pn_L!S IN 462':6 17.`•i24. 63.'9 FAX P E D C O R ?ip antex DEVELOPMENT CO. P; tct `.0 =i 1 Z O GROUNDING DIAGRAM T6() I d y _ 44 x P; tct `.0 =i 1 Z O GROUNDING DIAGRAM T6() I