HomeMy WebLinkAbout06080101.18IL I IF IE C Ic IB IA RTU -1 AIR HANDLING UNIT CONTROL SEQUENCE THE AIR HANDLING UNIT (AHU) SUPPLY FAN SHALL BE STARTED AND STOPPED THROUGH A HAND -OFF -AUTO SWITCH. WHEN THE SWITCH IS IN THE AUTO MODE, THE UNIT SHALL START AND STOP ACCORDING TO AN ADJUSTABLE TIME SCHEDULE BY THE BUILDING AUTOMATION SYSTEM (BAS) WITH AN INTERFACE PANEL LOCATED IN THE BUILDING. UPON "START" COMMAND, THE CONTROL SYSTEM SHALL BE ACTIVATED, THE OUTSIDE AIR DAMPER WILL OPEN AND INTERLOCKED EXHAUST FANS SHALL START. WHEN CONFIRMED OPEN, THE SUPPLY AIR FAN WILL START AND RUN CONTINUOUSLY. DAMPERS THAT FAIL TO OPEN SHALL BE INDICATED BY ALARM. INTERLOCKED FANS THAT FAIL TO START SHALL BE INDICATED BY ALARM. DUCT MOUNTED REHEAT COILS SHALL BE TIED IN TO THE ON BOARD CONTROLLER. SPACE TEMPERATURE CONTROL SHALL BE WITH WALL MOUNTED THERMOSTATS. A DISCHARGE AIR TEMPERATURE SENSOR SHALL MODULATE THE AHU COMPRESSORS TO MAINTAIN SET -POINT (ADJUSTABLE) TEMPERATURE. THE DISCHARGE AIR TEMPERATURE SHALL BE RESET FOR ENERGY CONSERVATION BASED ON FEEDBACK FROM SYSTEM REHEAT COIL THERMOSTATS. HOWEVER, HUMIDITY SENSORS IN THE DISCHARGE AIR SHALL LOAD COMPRESSORS TO MAINTAIN HUMIDITY CONTROL (ADJUSTABLE). "EVAPORATOR DEFROST" OR EQUIVALENT SHALL ALLOW OPERATION AT LOW CAPACITY. FILTER PRESSURE DROP SHALL BE MEASURED AND ALARM THE CONTROL SYSTEM IF THE DROP IS EXCESSIVE (ADJUSTABLE). WHEN THE UNIT IS OFF, THE FOLLOWING SHALL OCCUR: A. OUTSIDE AIR DAMPERS SHALL CLOSE. B. THE SUPPLY FAN SHALL STOP. C. THE CONTROL SYSTEM SHALL BE DE- ENERGIZED. D. INTERLOCKED EXHAUST FANS SHALL STOP. E. ALL OUTPUTS SHALL BE EQUIPPED WITH LOCAL /REMOTE SWITCHES AND ON /OFF PUSHBUTTONS OR GRADUAL SWITCHES TO FACILITATE TROUBLESHOOTING. AIR HANDLER CONTROL SEQUENCE DX ROOF -TOP A/C UNIT SCHEDULE ELECTRIC REHEAT COIL SCHEDULE ALL LOSSES IN DUCT SYSTEM GENERAL NOTES: MAINTAIN SERVICE CLEARANCES AS SHOWN ON DRAWINGS E.P. - EMERGENCY POWER UNIT ACCESSORIES: O1 - MOTORIZED INLET VANES ON SUPPLY & 80 - ROOF CURB WITH UNIT ACCESSORIES: O1 - PROVIDE WITH SCR CONTROLLERS O2 - PROVIDE DOOR INTERLOCK DISCONNECT O3 O4 - PROVIDE SAIL SWITCH AT EACH COIL - PROVIDE 120 VOLT CONTROL CIRCUIT TRANSFORMER IDENTIFICATION RHC -1 RHC -2 O - MFG'S 100% 0/A ECONOMIZER MODULE 11 - INDIVIDUAL ELEC. CONNECTIONS FOR EACH RHC -3 O - 2 'r THROWAWAY PRE FILTERS AND FRAME 12 - EMERGENCY POWER FOR SUPPLY AND RHC -4 CFM 2415 1135 (VFD) WITH LINE REACTOR AND DISCONNECT 1170 CONTROL TRANSFORMER, AND PILOT LIGHT 745 E.A.T. /L.A.T. 55'/100' 55'/95' AREA SERVED 55'/100' 55'/100' DUCT SIZE 20x18 1 4x1 4 1604 TCD 180 12x12 NO. OF STAGES 3 2 2 UNIT ACCESSORIES 2 TOTAL KW 35 KW 14 KW CFM 17 KW 10 KW ELEC. 460 -3 460 -3 460 -3 460 -3 UNIT ACCESSORIES O2 O3 O4 O2 �3 O4 O2 O3 O4 5/460 -3 O2 O3 40 REMARKS a_ N STARTER TYPE OD DISCONNECT TYPE OA ACCESSORIES RTU -1 AIR HANDLING UNIT CONTROL SEQUENCE THE AIR HANDLING UNIT (AHU) SUPPLY FAN SHALL BE STARTED AND STOPPED THROUGH A HAND -OFF -AUTO SWITCH. WHEN THE SWITCH IS IN THE AUTO MODE, THE UNIT SHALL START AND STOP ACCORDING TO AN ADJUSTABLE TIME SCHEDULE BY THE BUILDING AUTOMATION SYSTEM (BAS) WITH AN INTERFACE PANEL LOCATED IN THE BUILDING. UPON "START" COMMAND, THE CONTROL SYSTEM SHALL BE ACTIVATED, THE OUTSIDE AIR DAMPER WILL OPEN AND INTERLOCKED EXHAUST FANS SHALL START. WHEN CONFIRMED OPEN, THE SUPPLY AIR FAN WILL START AND RUN CONTINUOUSLY. DAMPERS THAT FAIL TO OPEN SHALL BE INDICATED BY ALARM. INTERLOCKED FANS THAT FAIL TO START SHALL BE INDICATED BY ALARM. DUCT MOUNTED REHEAT COILS SHALL BE TIED IN TO THE ON BOARD CONTROLLER. SPACE TEMPERATURE CONTROL SHALL BE WITH WALL MOUNTED THERMOSTATS. A DISCHARGE AIR TEMPERATURE SENSOR SHALL MODULATE THE AHU COMPRESSORS TO MAINTAIN SET -POINT (ADJUSTABLE) TEMPERATURE. THE DISCHARGE AIR TEMPERATURE SHALL BE RESET FOR ENERGY CONSERVATION BASED ON FEEDBACK FROM SYSTEM REHEAT COIL THERMOSTATS. HOWEVER, HUMIDITY SENSORS IN THE DISCHARGE AIR SHALL LOAD COMPRESSORS TO MAINTAIN HUMIDITY CONTROL (ADJUSTABLE). "EVAPORATOR DEFROST" OR EQUIVALENT SHALL ALLOW OPERATION AT LOW CAPACITY. FILTER PRESSURE DROP SHALL BE MEASURED AND ALARM THE CONTROL SYSTEM IF THE DROP IS EXCESSIVE (ADJUSTABLE). WHEN THE UNIT IS OFF, THE FOLLOWING SHALL OCCUR: A. OUTSIDE AIR DAMPERS SHALL CLOSE. B. THE SUPPLY FAN SHALL STOP. C. THE CONTROL SYSTEM SHALL BE DE- ENERGIZED. D. INTERLOCKED EXHAUST FANS SHALL STOP. E. ALL OUTPUTS SHALL BE EQUIPPED WITH LOCAL /REMOTE SWITCHES AND ON /OFF PUSHBUTTONS OR GRADUAL SWITCHES TO FACILITATE TROUBLESHOOTING. AIR HANDLER CONTROL SEQUENCE DX ROOF -TOP A/C UNIT SCHEDULE GENERAL NOTES: (1) - EXTERNAL STATIC PRESSURE INCLUDES ALL LOSSES IN DUCT SYSTEM (2) - HIGH EFFICIENCY MOTOR UNIT ACCESSORIES: O1 - MOTORIZED INLET VANES ON SUPPLY & 80 - ROOF CURB WITH RETURN FANS 90% EFFICIENT FINAL FILTERS O2 - FACTORY INSTALLED HUMIDIFIER Og - SPRING ISOLATION RAIL (SEE SCHEDULE) O3 - MFG'S BLENDER MODULE 10 - UNIT STARTERS, CONTROLS, DAMPERS AND ACCESSORIES FACTORY INSTALLED BY O - MFG'S DISCHARGE PLENUM MODULE A/C UNIT MANUFACTURER O - MFG'S 100% 0/A ECONOMIZER MODULE 11 - INDIVIDUAL ELEC. CONNECTIONS FOR EACH FAN AND CONDENSING UNIT O - 2 'r THROWAWAY PRE FILTERS AND FRAME 12 - EMERGENCY POWER FOR SUPPLY AND RETURN FANS ONLY U7 - MFG'S FINAL FILTER MODULE • -C STARTER ACCESSORIES: OA - FACTORY MTD. COMBINATION MAG -X -LINE OC = FACTORY MTD. VARIABLE FREQUENCY DRIVE (VFD) WITH LINE REACTOR AND DISCONNECT OB - FACTORY MTD. AUTO. TRANSFORMER OD - HAND -OFF -AUTO. SWITCH, 120 VOLT CONTROL TRANSFORMER, AND PILOT LIGHT IDENTIFICATION RTU -1 AREA SERVED DIALYSIS CLINIC MANUFACTURER TRANE MODEL NO. TCD 180 OPER. WEIGHT (LBS) 2500# UNIT ACCESSORIES 5 6 10 CFM 5465 EXT. SP. (1) 3" TOTAL SP. 4" H.P. /ELEC (2) 5/460 -3 a_ N STARTER TYPE OD DISCONNECT TYPE OA ACCESSORIES o MINIMUM 1050 ja o MAXIMUM 5255 DEHUM CFM 5255 o MAX. FV 500 z E.A.T. D.B. /W.B. 79.4/66 J oL.A.T. D.B. /W.B. 55/54.6 GTH BTU /HR 173,047 NO. 2 Z N xw R.L.A. 14.6/10 CL Z 2 z ° L.R.A. 118/63 WCe N0. 2 o wN U o- o F.L.A. 1.6 U REMARKS fti 2 2214 METROCENTER BLVD. SUITE 128 NASHVILLE, TN 37228 OFFICE 615.256.7038 FAX 615.256.7132 L K ro M C • Q_ 0 Z 00 N 04 00 N N > Q Z O 00 M 00 00 CO • -C to v- Lo v- M �- CU Z O 1-- Co LL. U z_ J U Cf) V) J Q D J W ry Q U Q z Q O z W ry Q U Cn z W U O 0 z O U Cn z O U w U W ttZ U Ce z O F- U I-- V) z O U I II N_ DRAWN: LKK PROJECT ARCHITECT: SPP (PROJECT MANAGER: LKK IREVIS(ONS: 1 )B# 05098 LE: DATE: JULY 21, 2006 ` \,,`tt lt�tft �s NO. PE10000164 STATE" : '' !A!DI . A. tt,tt,� HVAC Schedules M0.01