Loading...
HomeMy WebLinkAbout06080101.21a L J a F E B 18x6 SIDEWALL SUPPLY REGI BALANCE AT 300 CFM 18x10 SIDEWALL RETURN GRILLE, BALANCE AT 300 CFM 1 2 HVAC PLAN SCALE: 1/8" = 1' -0" 0 2' 4' 8' 16' q0 TRUE NORTH •EF -1 ON MFG'S ROOF CURB ON ROOF ABOVE 8x6 SIDEWALL SUPPLY REGISTER, BALANCE AT 115 CFM EACH (TYP 3) 8x6 SIDEWALL SUPPLY REGISTER, BALANCE AT 140 CFM EACH (TYP 2) GENERAL NOTES 1. DUCTWORK DIMENSIONS ARE INSIDE CLEAR. 2. TO INDICATES THERMOSTAT. 3. INDICATES THERMOSTAT WITH LOCKING COVER. 4. REFER TO SCHEDULE SHEET MO.00 FOR DIFFUSER AND GRILLE SCHEDULE. 5. SPACES WITH DRYWALL CEILINGS SHALL HAVE FLANGE TYPE CEILING OUTLETS. 6. ALL DIFFUSERS IN SAME SPACE SHALL HAVE THE SAME FACE SIZE USING LARGEST SIZE REQUIRED FROM DIFFUSER AND GRILLE SCHEDULE. 7. IF NO SIZE IS SHOWN FOR DUCT SERVING DIFFUSER OR GRILLE, USE SIZE SHOWN ON DIFFUSER AND GRILLE SCHEDULE. 8. AIR INTAKES THRU ROOF SHALL BE A MINIMUM 25 FEET FROM EXHAUST FAN OUTLETS AND PLUMBING VENTS. 9. PROVIDE ACCESS PANELS IN AREAS WITH DRYWALL CEILING FOR ACCESS TO VALVES, BALANCING DAMPERS, FIRE, SMOKE AND /OR COMBINATION DAMPERS, REHEAT COILS, ETC.. 10. REFER TO OTHER DISCIPLINES DRAWINGS FOR COORDINATION WITH THIS DRAWING. 11. SEAL ALL WALL, ROOF AND FLOOR PENETRATIONS AIR TIGHT AT PIPE, DUCTWORK AND CONDUIT PENETRATIONS. 12. REFER TO HVAC DETAILS FOR ADDITIONAL REQUIREMENTS ON EQUIPMENT. 13. EQUIPMENT SIZES AND SERVICE SPACE REQUIREMENTS MAY VARY BETWEEN DIFFERENT MANUFACTURERS. CONSULT THE MANUFACTURER SUBMITTED AND APPROVED, AND COORDINATE WITH THESE DOCUMENTS. 14. REFER TO EQUIPMENT SCHEDULES FOR BRANCH PIPE SIZES TO INDIVIDUAL EQUIPMENT. 15. PROVIDE MANUAL BALANCING DAMPERS IN EACH BRANCH RUN OUT TO SUPPLY DIFFUSERS, RETURN AND EXHAUST GRILLES. 16. CONTRACTOR SHALL VERIFY CLEARANCE REQUIREMENTS AND INDICATE ROUTING OF NEW DUCTWORK BEFORE FABRICATION BEGINS AS RISES AND DROPS MAY BE NECESSARY DUE TO FIELD CONDITIONS. LEGEND I EXISTING TO REMAIN NEW CONSTRUCTION I EXISTING CONDITIONS NOTE FIELD VERIFY EXISTING CONDITIONS. NEW A /C -1 TO BE AT LOCATED TO MAINTAIN 25' -0" FROM ANY EXISTING EXHAUST OR VENT. NEW EXHAUST FANS TO BE LOCATED TO MAINTAIN 25' -0" FROM ANY NEW OR EXISTING AIR INTAKE. FIELD VERIFY EXISTING DUCTWORK LOCATIONS AT NEW RATED WALL PENETRATIONS. PROVIDE FIRE DAMPERS IN EXISTING DUCTWORK AS NECESSARY. I KEYED NOTES I O1 NEW A /C -1 ON MFG'S ROOF CURB ON ROOF ABOVE. TRANSITION CONNECTION SIZE SUPPLY AND RETURN DUCT TO SIZES SHOWN. PROVIDE SMOKE DETECTORS IN SUPPLY AND RETURN VERTICAL RISERS. PROVIDE 1" SOUNDLINER IN RETURN DUCT FOR A RUN OF 15' -0" IN ALL DIRECTIONS. 02 PROVIDE 1" SOUND LINER FROM FAN TO THIS POINT IN EXHAUST DUCT. DUCT DIMENSIONS GIVEN ARE INSIDE CLEAR DIMENSIONS. O 4"0 COMBUSTION AIR & 4"0 VENT UP THRU ROOF PROVIDE MFG'S CONCENTRIC ROOF TERMINATION KIT. CONTROL SEQUENCE THE A/C UNIT FAN WILL RUN CONTINUOUS AS DETERMINED BY A 24/7 PROGRAMMABLE THERMOSTAT TO MAINTAIN AIR CHANGE AND OUTSIDE AIR REQUIREMENTS DURING FACILITY OPERATING HOURS TO BE DETERMINED BY FACILITY STAFF. THE COMPRESSOR /COOLING CYCLE OR HEATING CYCLE SHALL ACTIVATE IN RESPONSE TO THE PROGRAMMABLE THERMOSTAT TO SATISFY THE SPACE TEMPERATURE SETTING. EXHAUST FANS ASSOCIATED WITH EACH A/C UNIT WILL DE- ENERGIZE DURING CORRESPONDING A/C UNIT SHUT DOWN. SEE THE EXHAUST FAN INTERLOCK SCHEDULE SHEET MO.00. THE NEW AIR HANDLER SHALL BE PROVIDED WITH A HUMIDITY SENSOR IN THE SUPPLY DUCT. THE COMPRESSOR(S) SHALL CONTINUE TO OPERATE TO MAINTAIN HUMIDITY SET POINT. THE UNIT WILL INITIATE THE HOT GAS REHEAT TO MAINTAIN SPACE TEMPERATURE SET POINT. a 2214 METROCENTER BLVD. SUITE 128 NASHVILLE, TN 37228 OFFICE 615.256.7038 FAX 61 5.256.7132 L J H w O CL z CL to -c- o 00 0 o I I� N Z Z M 00 0 M Q 0 00 0 00 •> L LO L Lo M c cu ( (.0 C CO 1 Ci U W ON r V) z U z O Q U U z > Q U ry 0 V) cf) z z z O Q J O W � U J ry : F-- U F � ry Q z III III U OU DRAWN: LKK PROJECT ARCHITECT. SPP PROJECT MANAGER: LKK REVISIONS: 1 -02-06j ADD #2 05098 FILE: DATE: JULY 21, 2006 PEl 0 STATEro �r ' !a!D ��''•�SS�oaa�L HVAC Plan M2.01 DRAWN: LKK PROJECT ARCHITECT. SPP PROJECT MANAGER: LKK REVISIONS: 1 -02-06j ADD #2 05098 FILE: DATE: JULY 21, 2006 PEl 0 STATEro �r ' !a!D ��''•�SS�oaa�L HVAC Plan M2.01