HomeMy WebLinkAbout06080101.35L K E F3 167 B SYSTEM NO. W -L -1093 F- RATING - 1 AND 2 HR (SEE ITEM 1) T- RATING - 1 AND 1-1/2 HR (SEE ITEM 1) A 1 1B 2 B O O O O O 0 0 O O O 3 3B 3 A ILA SECTION AA 1. WALL ASSEMBLY - THE 1 OR 2 HR FIRE -RATED GYPSUM BOARD /STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U400 SERIES WALL OR PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. STUDS - WALL FRAMING SHALL CONSIST OF MIN 3 -5/8 IN. WIDE STEEL CHANNEL STUDS SPACED MAX 24 IN. OC. B. GYPSUM BOARD* - 5/8 IN. THICK, 4 FT WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM BOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX AREA OF OPENING IS 66 SQ IN. WITH MAX DIMENSION OF 22 IN. THE HOURLY F AND T RATINGS OF THE FIRESTOP SYSTEM ARE DEPENDENT ON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED AS SHOWN IN THE TABLE BELOW: RATING OF WALL HR F RATING HR T RATING HR 2 2 1 -1/2 1 1 1 2. THROUGH - PENETRANTS - ONE OR MORE PIPES, CONDUITS OR TUBING TO BE INSTALLED WITHIN THE OPENING. THE SPACE BETWEEN PIPES, CONDUITS OR TUBING SHALL BE A MIN OF 1/2 IN. TO A MAX OF 1 IN. THE SPACE BETWEEN PIPES, CONDUITS OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN 0 IN. (POINT CONTACT) TO MAX 1-1/4 IN. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF PIPES, CONDUITS OR TUBING MAY BE USED: A. STEEL PIPE - NOM 2 IN. DIAM (OR SMALLER) SCHEDULE 5 (OR HEAVIER) STEEL PIPE. B. IRON PIPE - NOM 2 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE. C. CONDUIT - NOM 2 IN. DIAM ( OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR GALV STEEL CONDUIT. 3. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING: A. GYPSUM BOARD* - TWO LAYERS OF 5/8 IN. THICK BOARD CUT TO FIT THE CONTOUR THE THROUGH PENETRANTS ON BOTH SURFACES OF THE WALL. THE ANNULAR SPACE BETWEEN THE THROUGH PENETRANTS AND THE CUTOUTS OF THE GYPSUM BOARD SHALL BE A MIN OF 1/4 IN. TO A MAX 3/8 IN. GYPSUM BOARD SHALL EXTEND A MIN OF 2 IN. BEYOND THE PERIPHERY OF THE OPENING ON BOTH SURFACES OF THE WALL. PRIOR TO SECURING THE GYPSUM BOARD TO BOTH SURFACES OF THE WALL, A MIN 1/2 IN. DIAM BEAD OF FILL MATERIAL (ITEM 3B) APPLIED AS A GASKET /SEALANT BETWEEN EACH LAYER OF GYPSUM BOARD. ON BOTH SURFACES OF THE WALL, EACH LAYER OF GYPSUM BOARD TO BE SECURED TO WALL BY MEANS OF MIN 1 -1/4 IN. LONG TYPE G STEEL SCREWS SPACED 6 IN. OC. SEE GYPSUM BOARD (CKNX) CATEGORY IN VOL. 1 OF THE UL FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS. B. FILL, VOID OR CAVITY MATERIAL* - SEALANT - ON BOTH SURFACES OF THE WALL, A MIN 1/2 IN. DIAM BEAD OF FILL MATERIAL APPLIED AS A GASKET /SEALANT BETWEEN EACH LAYER OF GYPSUM BOARD (ITEM 3A). AFTER INSTALLATION OF BOTH LAYERS OF GYPSUM BOARD, 1 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN ANNULAR SPACE BETWEEN THE CUTOUTS OF THE GYPSUM BOARD AND THE PENETRATING ITEMS. ADDITIONAL FILL MATERIAL TO BE INSTALLED SUCH THAT A MIN 1/4 IN. THICK CROWN OF FILL MATERIAL APPLIED AROUND THE OUTER CIRCUMFERENCE OF THE THROUGH PENETRANTS ON BOTH SURFACES OF WALL. SPECIFIED TECHNOLOGIES INC - SPECSEAL LC 150, 151, 152 OR 155 SEALANT. AS AN OPTION , SPECSEAL 100, 101, 102, 105, 120 OR 129 SEALANT OR SPECSEAL LCI SEALANT MAY BE USED IN THE THE ANNULAR SPACE AROUND THE PENETRATING ITEMS. *BEARING THE UL CLASSIFICATION MARK 1 HOUR RATING THROUGH - PENETRATION FIRESTOP SYSTEMS (WALL) CAD ID: NOT TO SCALE ELECTRICAL DETAILS SCALE: N.T.S. SYSTEM NO. W -L -1156 F RATING - 1, 2 AND 3 HR (SEE ITEM 1) T RATING - 0 HR L RATING AT AMBIENT - LESS THAN 1 CFM /SQ FT L RATING AT 400 F - LESS THAN 1 CFM /SQ FT SECTION A -A 1. WALL ASSEMBLY - THE 1, 2 OR 3 HR FIRE -RATED GYPSUM WALLBOARD /STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL 0300 OR 0400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. STUDS - WALL FRAMING SHALL CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. LUMBER SPACED 16 IN. OC. STEEL STUDS TO BE MIN 3 -5/8 IN. WIDE AND SPACED 24 IN. OC. B. GYPSUM BOARD* - 1/2 OR 5/8 IN. THICK, 4 FT WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 1 -1/2 IN. THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED. 2. THROUGH PENETRANTS - ONE METALLIC PIPE OR CONDUIT INSTALLED CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE WITHIN THE FIRESTOP SYSTEM SHALL BE MIN 1/4 IN. TO MAX 1/2 IN. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPE OR CONDUIT MAY BE USED: A. STEEL PIPE - NOM 3/4 IN. DIAM (OR SMALLER) SCHEDULE 5 (OR HEAVIER) STEEL PIPE. B. CONDUIT - NOM 3/4 IN. DIAM (OR SMALLER) RIGID STEEL CONDUIT, STEEL ELECTRICAL METALLIC TUBING (EMT) OR FLEXIBLE STEEL CONDUIT. 3. FILL, VOID OR CAVITY MATERIALS* - SEALANT - FILL MATERIAL INSTALLED TO COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND GYPSUM WALLBOARD WITH A MIN 1/4 IN. DIAM BEAD OF CAULK APPLIED TO PERIMETER OF PIPE OR CONDUIT AT ITS EGRESS FROM BOTH SIDES OF THE WALL. SPECIFIED TECHNOLOGIES INC - SPECSEAL 100, 101, 102 OR 105 SEALANT *BEARING THE UL CLASSIFICATION MARKING 1 HOUR RATING THROUGH - PENETRATION FIRESTOP SYSTEMS (WALL) CAD ID: 14EO07 NOT TO SCALE SYSTEM NO. W -L -1029 (FORMERLY SYSTEM NO. 467) F- RATING - 1 AND 2 HR (SEE ITEM 1B) T- RATING - 0 HR L RATING AT AMBIENT - LESS THAN 1 CFM /SQ FT L RATING AT 400 F - LESS THAN 1 CFM /SQ FT • Section A A 1. WALL ASSEMBLY - THE 1 OR 2 H FIRE RATED GYPSUM WALLBOARD /STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 AND U400 SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. LUMBER SPACED 16 IN. OC. STEEL STUDS TO BE MIN 2 -1/2 IN. WIDE AND SPACED MAX 24 IN. OC. B. GYPSUM BOARD* - 5/8 IN. THICK, 4 FT WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 6 IN. THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED. 2. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE CENTERED WITHIN THE FIRESTOP SYSTEM. A NOM ANNULAR SPACE OF 3/4 IN. IS REQUIRED WITHIN THE FIRESTOP SYSTEM. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED: A. STEEL PIPE - NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 5 (OR HEAVIER) STEEL PIPE. B. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR STEEL CONDUIT. C. COPPER TUBING - NOM 4 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING. D. COPPER PIPE - NOM 4 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE. 3. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING: A. PACKING MATERIAL - MIN 1 IN. THICKNESS OF MIN 3.5 PCF FIBERGLASS INSULATION SHALL BE WRAPPED AROUND THE THROUGH - PENETRANT AND SECURED TOGETHER BY MEANS OF NO. 24 AWG STEEL TIE WIRE. PACKING MATERIAL SHALL BE CENTERED AT MID -DEPTH OF OPENING AND RECESSED FROM BOTH SURFACES OF WALL ASSEMBLY REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL. B. FILL, VOID OR CAVITY MATERIAL* - CAULK OR PUTTY - IN 2 HR FIRE RATED ASSEMBLIES MIN 3/4 IN. THICKNESS FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH BOTH SURFACES OF WALL. ADDITIONAL FILL MATERIAL TO BE INSTALLED SUCH THAT A MIN 1/4 IN. CROWN IS FORMED AROUND THE PENETRATING ITEM. IN 1 H FIRE -RATED ASSEMBLIES, MIN 5/8 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN ANNULUS ON BOTH SURFACES OF WALL. ADDITIONAL FILL MATERIAL TO BE INSTALLED SUCH THAT A MIN 3/8 IN. CROWN IS FORMED AROUND THE PENETRATING ITEM AND LAPPING 1 IN. BEYOND THE PERIPHERY OF THE OPENING. SPECIFIED TECHNOLOGIES INC - SPECSEAL 100, 101 OR 105 SEALANT AND SPECSEAL PUTTY *BEARING THE UL CLASSIFICATION MARKING CAD ID: 14EO09 1 HOUR RATING THROUGH - PENETRATION FIRESTOP SYSTEMS (WALL) NOT TO SCALE a 2214 METROCENTER BLVD. SUITE 128 NASHVILLE, TN 37228 OFFICE 615.256.7038 FAX 61 5.256.7132 L 0 0 I M z LEI LU -� o ti p 00 N 00 Z C'4 Q CN (n M M U) w > N Z CO M > W 00 00 Q 00 00 ry -75; U I-- ry • LC) LO z U CV) cu�C.0 U � Z F- U- '� F z W J Q U Z � Q U (n O U) Z > z Q _ O W U W Q ry -75; U I-- ry Q z U O U W 1- u LLj tL z O U I- z O U W CL RAWN: LKK ROJECT ARCHITECT: SPP (PROJECT MANAGER: LKK 1 (REVISIONS: )B# 05098 LE: DATE: JULY 21, 2006 � e N0. PEr1�00 0 . � � =_ STATE F •' 3 Electrical Details E6.01 R