HomeMy WebLinkAbout06110089.55CD Q Cr M ,y N N M CD GENERAL NOTES: (APPLY TO ALL ELECTRICAL SHEETS) 1. PROVIDE SUPPORT WIRES AS SHOWN IN DETAIL BELOW FOR ALL LIGHT FIXTURES. 2. ALL WORK SHALL CONFORM TO OR EXCEED THE MINIMUM REQUIREMENTS OF THE CURRENT ANSI /NFPA 70 WITH STATE OF INDIANA AMENDMENTS, ANSI /IEEE C2 AND ALL FEDERAL, STATE, LOCAL, AND MUNICIPAL CODES AND ORDINANCES. THE ELECTRICAL SUBCONTRACTOR SHALL COMPLY WITH THE DIRECTIONS OF ALL AUTHORITIES HAVING JURISDICTION. 3. INSTALL WORK USING PROCEDURES DEFINED IN NECA STANDARDS OF INSTALLATION. ALL WORK SHALL PRESENT A NEAT MECHANICAL APPEARANCE WHEN COMPLETED. 4. REFER TO THE ARCHITECTURAL DRAWINGS FOR CEILING WORK BY THE SEPARATE GENERAL CONTRACT. COORDINATE ALL ELECTRICAL WORK. 5. THE ELECTRICAL SUBCONTRACTOR SHALL PROVIDE ALL FLOOR, WALL, AND CEILING PENETRATIONS TO COMPLETE HIS WORK. PROVIDE PROPER FIRE SAFEING FOR ALL PENETRATIONS MADE. 6. COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES TO ENSURE EFFECTIVE AND EFFICIENT OVERALL INSTALLATION. 7. COORDINATE ALL ELECTRICAL SYSTEM DOWNTIME WITH THE OWNER AND OTHER TRADES. DOWNTIME OF THE SYSTEM SHALL BE MINIMIZED. WEEKEND AND AFTER HOUR WORK SHALL BE REQUIRED TO PREVENT OR MINIMIZE INTERFERENCE WITH THE OWNER'S OPERATION. 8. ALL NEW EQUIPMENT SHALL BE SUBMITTED FOR APPROVAL PRIOR TO ORDERING. 9. PHYSICAL SIZES AND LOCATIONS OF ALL MECHANICAL EQUIPMENT SHOWN ON THESE DRAWINGS ARE APPROXIMATE. COORDINATE ELECTRICAL WORK FOR THIS EQUIPMENT WITH THE OTHER TRADES. 10. PROVIDE APPROPRIATE SEALANT (I.E. FIRESAFEING) TO MAINTAIN CONSTRUCTION INTEGRITY FOR ANY PENETRATIONS THROUGH FLOORS, STRUCTURAL CEILINGS, AND FIRE WALLS. 11. ALL BRANCH CIRCUITS SHALL UTILIZE SEPARATE INDEPENDENT NEUTRAL CONDUCTORS. DO NOT COMBINE NEUTRAL CONDUCTORS. 12. ALL FEEDER NEUTRAL/GROUNDED CONDUCTORS SHALL BE CONSIDERED CURRENT CARRYING. DERATE MULTIPLE CONDUCTORS IN A RACEWAY ACCORDINGLY WITH NEC TABLES. 13. INSTALL ALL CONDUITS, RACEWAYS, AND CABLE TRAY FOR MAXIMUM HEAD CLEARENCE IN MECHANAICAL AREAS, AND ATTIC. COORDINATE CLEARANCES WITH PERFORMANCE SERVICES AND THE OWNER. 14. ALL ELECTRICAL SERVICE WORK SHALL COMPLY WITH THE LOCAL UTILITY. COORDINATE ALL REQUIREMENTS PRIOR TO BID AND INCLUDE ALL NECESSARY MATERIAL AND LABOR REQUIRED FOR THE NEW ELECTRICAL SERVICE. SPECIFICATIONS: (APPLY TO ALL ELECTRICAL SHEETS) 1. PROVIDE AND INSTALL NEW GREEN INSULATED COPPER GROUNDING CONDUCTORS AS THE EQUIPMENT GROUNDING MEANS FOR ALL ELECTRICAL DEVICES AND EQUIPMENT. 2. ALL COVERPLATES FOR WIRING DEVICES SHALL BE WHITE NYLON TYPE. DEVICES SHALL BE WHITE IN COLOR. 3. PROVIDE LABELING FOR ALL PANELBOARDS, SWITCHBOARDS, AND DISCONNECT SWITCHES TO INCLUDE AN ENGRAVED PLASTIC LABEL IDENTIFING THE EQUIPMENT AND WHERE IT IS FED FROM. ALL BRANCH DEVICES IN THE MAIN SWITCHBOARD SHALL HAVE AN ENGRAVED PLASTIC LABEL. ALL PANELBOARDS SHALL INCLUDE A TYPEWRITTEN DIRECTORY. ALL RECEPTICALS SHALL HAVE CIRCUIT NUMBERS WRITTEN ON THE INSIDE OF THE COVERPLATE. ALL JUNCTION BOX COVERS SHALL BE IDENTIFIED TO INDICATE CIRCUITS CONTAINED. WHERE MULTIPLE SWITCHES ARE GANGED TOGETHER THE SWITCHES SHALL BE IDENTIFIED. 4. ALL CONDUIT INSIDE THE BUILDING SHALL BE A ELECTRICAL METALLIC TUBING (EMT) AND SHALL BE A MINIMUM 3/4" UNLESS OTHERWISE NOTED. ALL CONDUIT INSTALLED UNDERGROUND SHALL BE SCHEDULE 40 PVC UNLESS OTHERWISE NOTED. ALL CONDUIT INSTALLED ABOVE GRADE OUTSIDE THE BUILDING SHALL BE RIGID STEEL. NO PVC CONDUIT SHALL BE USED ABOVE THE FLOOR SLAB. 5. SWITCHES SHALL BE 20 AMPERE RATED, 120/277 VOLT, HUBBELL 1121 SERIES OR APPROVED EQUIVALENT. 6. RECEPTACLES SHALL BE 20A, 120V GROUNDING TYPE LIKE HUBBELL 5342 SERIES. 7. ALL ELECTRICAL CONNECTORS, LUGS, BREAKERS, EQUIPMENT, ETC. SHALL BE RATED AT A MINIMUM OF 75 DEG. C. 8. WIRING METHODS: MC TYPE CABLING MAY BE USED FOR ALL INSTALLATIONS IN WALLS AND ABOVE CEILINGS. SUPPORT MC CABLE EVERY 6 FEET MINIMUM OR AS REQIUIRED BY CODE. MC CABLE MAY NOT BE USED FOR ANY EXPOSED WIRING OR PANELBOARD FEEDERS. ALL EXPOSED BRANCH CIRCUIT WIRING AND PANELBOARD FEEDERS SHALL BE TYPE THHN/THWN WIRING INSTALLED IN CONDUIT. ALL WIRING SHALL BE COPPER. NO ALUMINUM WIRING WILL BE ALLOWED. 9. PROVIDE (1) 1" SPARE CONDUIT FOR EACH 3 SPACES OR SPARES IN EACH FLUSH MOUNTED PANEL FROM PANEL TO ABOVE ACCESSABLE CEILING FOR FUTURE USE. 10. ALL PANELBOARDS SHALL HAVE COPPER BUS AND RATINGS AS SPECIFIED. REFERENCE STANDARDS SHALL BE SQUARE D NQOD SERIES BRANCH PANELS AND I LINE SEIRES DISTRIBUTION PANELS. 11. ALL EXTERIOR RECEPTACLES SHALL HAVE IN -USE TYPE WEATHERPROOF COVERPLATES. 12. FIRE ALARM SYSTEM SHALL BE ADDRESSABLE TYPE WITH 48 HOUR BACKUP. SYSTEM SHALL HAVE CAPACITY FOR QUANTITY OF DEVICES SHOWN PLUS CAPACITY TO ADD 50 MORE DEVICES. SYSTEM AND INSTALLATION SHALL COMPLY WITH NFPA 72. OPERATION OF ANY INIATION DEVICE SHALL AUTOMATICALLY CAUSE ALL ALARMS IN THE BUILDING TO SOUND OR FLASH, AND SIGNAL TO BE SENT VIA DACT. ALL ALARMS SHALL BE VISIBLE ON THE REMOTE ANNUNCIATOR. OPERATION OF ANY DUCT MOUNTED SMOKE DETECTOR SHALL CAUSE THE UNIT TO SHUT DOWN AND ALL ALARM DEVICES TO SOUND OR FLASH. INSTALLER SHALL BE A FACTORY AUTOHORIZED INSTALLER. ALL EQUIPMENT, DEVICES AND WIRING SHALL BE NEW. MAIN FIRE ALARM PANEL SHALL INCLUDE ALL COMPONETS NECESSARY TO MONITOR ALL DEVICES SHOWN AND SUPPORT ALL SIGNAL DEVICES SHOWN. INCLUDE ALL PROGRAMMING NECESSARY FOR SYSTEM OPERATION. SYSTEM SHALL INCLUDE BATTERY BACKUP FOR 48 HOURS AND INCLUDE SURGE PROTECTION FOR PANEL. SYSTEM SHALL HAVE LCD DISPLAY ON CONTROL PANEL AND REMOTE ANNUNCIATOR TO DISPLAY ALL ALARMS AND TROUBLES. PROVIDE DIGITAL ALARM COMMUNICATOR TRANSMITTER (DACT) WITH 2 DEDICATION TELEPHONE LINES TO THE MAIN TELEPHONE MAT. HORN TYPE SIGNAL DEVICES SHALL PROVIDE 96dBA SOUND LEVEL MEASURED AT 10 FEET AND INCLUDE VISUAL DEVICE AS SPECIFIED BELOW. SOUNDER SHALL BE FIELD PROGRAMMABLE TO CHANGE ALARM TONES. MOUNT DEVICE AT +80 ". VISUAL DEVICES SHALL COMPLY WITH ADA REQUIREMENTS PER UL 1971. MOUNT DEVICE AT +80 ". MANUAL PULL STATION SHALL BE ADDRESSABLE TYPE, SINGLE ACTION, FLUSH MOUNTED. DUCT MOUNTED DETECTORS SHALL BE PHOTOELECTRIC TYPE, ADDRESSABLE, ADJUSTABLE SENSITIVITY INSTALLED IN DUCT MOUNTED HOUSING WITH SAMPLING TUBES AS REQUIRED. HEAT DETECTORS SHALL BE ADDRESSABLE TYPE, RATE OF RISE TYPE. ADDRESSABLE RELAYS: PROVIDE ADDRESSABLE RELAYS AS REQUIRED FOR CONTROL OF HVAC EQUIPMENT AND DOOR HOLD /RELEASE DEVICES. PROVIDE MAGNETIC DOOR HOLD /RELEASE DEVICES FOR DOORS SHOWN. PROVIDE POWER FROM FIRE ALARM PANEL AND CONTROL WITH ADDRESSABLE RELAYS. LCD ALPHANUMERIC REMOTE ANNUNCIATOR SHALL BE FLUSH MOUNTED AND INCLUDE SYSTEM ACKNOWLEDGE, SILENCE AND RESET. ALL FIRE ALARM WIRING SHALL BE NEW. WIRING MAY BE INSTALLED WITHOUT CONDUIT ABOVE ACCESSABLE CEILINGS. WIRING SHALL BE INSTALLED IN CONDUIT IN WALLS AND ABOVE HARD CEILINGS AND EXPOSED CEILINGS. ALL JUNCTION BOX COVERS SHALL BE PAINTED RED. FIRE ALARM SYSTEM SHALL BE MANUFACTURED BY SIMPLEX, EDWARDS, SIEMENS (PYROTRONICS) OR NOTIFIER. REFERENCE STANDARD IS THE NOTIFIER AFP -100 SERIES SYSTEM. �A �A SYSTEM NO. WL2154 r n_i..__- r -.- n tin /O. -..-. T +.._ 1% SECTION A- A 1. Wall Assembly - The 1 or 2 hr fire rated gypsum wallboard / stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 series Walt and Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A, Studs - Wall framing may consist of either wood studs or steel channel studs, Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be rein 3 -1/2 in. wide and spaced maximum 24 in, OC, B. Wallboard, Gypsum Board, - Thickness, type, number of layers and fasteners as required in the individual Wall and partition Design. Maximum diameter of opening is 7 -3/4 in, The hourly F and T Ratings of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrants - One nonmetallic pipe or conduit to be centered within opening with a nom, 1/4 in, annular space between pipe or conduit and periphery of opening. Pipe or conduit to be rigidly supported on both sides of the wall assembly, The following types and sizes of nonmetallic pipes or conduits may be used; A. Polyvinyl Chloride (PVC) Pipe - nom. 6 in, diameter (or smaller) Schedule 40 solid core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system, B. Rigid Nonmetallic Conduit ++ - Nom. 6 in, diameter (or Smaller) Schedule 40 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA No, 70). C. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 6 in, diameter (or smaller) SDR17 CPVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. 3, Firestop system - The details of the firestop system shall be as follows: A. Steel Sleeve - Minimum 26 gauge galvanized steel cut 6 in, longer than overall width of wall with the outside diameter equal to diameter of opening in wall with a minimum 1 in, overlap along longitudinal seam. Sleeve placed in wall opening such that 3 in. extends beyond both sides of wall. Edges of sleeve to be provided with 112 in, long slits to form retaining tabs. B. Fill, Void or Cavity Materials, - Wrap Strip - Nom. 1/8 in. thick intumescent material supplied in 2 in. wide strips, minimum four continuous layers of wrap strip tightly wrapped around nonmetallic pipe on both sides of wall, and recessed within steel sleeve 2 -112 in, from the end of sleeve on both side of wall. An additional stack of four continuous layers of wrap strip tightly wrapped around nonmetallic pipe an both sides of the wall and butted tightly against sleeve. the slit edges of sleeve to be bent 90 degrees toward pipe. two minimum 112 in, wide by 0,028 in, thick stainless steel band clamps shall be tightly fastened around sleeve on both sides of wall, approximately 1/2 in. from the wall surfaces and 3/4 in. from each end of sleeve, Minnesota Mining & Mfg. Co. - Ultra GS C. Fill, Void or Cavity Materials, - Caulk - Minimum 112 in, diameter bead of caulk shall be applied to outer perimeter of sleeve on both sides of wall at sleeve / wall interface, Minnesota Mining & Mfg. Co, - CP 25WB+ Caulk , Bearing the UL Classification Marking ++ Bearing the UL Listed Mark UL_ PENETRATION DETAILS SPECIFICATIONS (CONY.): 13. PROVIDE AND INSTALL SERVICE ENTRANCE TRANSIENT VOLTAGE SURGE SUPPRESSORS (TVSS), INTEGRAL TO THE EACH PANELBOARD WHERE INDICATED WITH THE FOLLOWING REQUIREMENTS: RATED AND TESTED FOR CATEGORY C (8 BY 20 MICROSECOND WAVEFORM) AS DEFINED BY ANSI /IEEE C62.41 WITH SYSTEM VOLTAGE RATING: 208/120,3 PHASE, 4 WIRE GROUNDED, 60HZ; PROTECTION MODES: EACH LINE TO NEUTRAL, EACH LINE TO GROUND, NEUTRAL TO GROUND, MAXIMUM SURGE CURRENT CAPACITY (8 X 20 MICROSECONDS) FOR MULTIPLE OCCURRENCES: MINIMUM CAPACITY ALLOWED IS 240,000 AMPS PER PHASE; CLAMPING VOLTAGE: 472; UL -1449 VOLTAGE SUPPRESSION RATING: L -N, 500, L -G = 500 AND N -G = 500. ACCESSORIES: PROVIDE WITH INTEGRAL FUSED DISCONNECT, MODULE STATUS INDICATOR LIGHTS, UNIT STATUS INDICATOR LIGHTS, AUDIBLE ALARM AND SILENCE SWITCH, AND TRANSIENT COUNTER. ACCEPTABLE MANUFACTURES: SQUARE D. 618 East Market Street Indianapolis, Indiana 46202 ph 317/264.8162 fx 317/264.8165 a x i s a r c h. c o m Scope Drawings These drawings indicate the general scope of the project in terms ofarchitedural design concept, the dimensions of the building, the major architectural elements and the type of structural, mechanical and electrical systems. The drawings do not necessarily indicate or describe all work required for full performance and completion of the requirements of the contract On the basis of the general scope indicated or described, the trade contractors shall furnish all items required for the proper execution and completion of the work DRAWN by DGS CHECKED by DGS DATE issued 17 OCT 2006 REVISIONS THE SCHNEIDER CORP. ASHTON FRITZ 8901 OTIS AVENUE INDIANAPOLIS, IN 46216 (317) 826 -7100 (317) 826 -7200 STRUCTURAL DESIGN, INC. CHUCK SCHAEFER 337 MAIN STREET BEECH GROVE, IN 46107 (317) 822.0204 (317) 822.0206 VECTOR CONSULTING BEN DEREMIAH 212 W. 10TH ST., SUITE D -395 INDIANAPOLIS, IN 46202 (317) 632.4444 (317) 632.4960 Z Z U-11 P U > N WZ W O �C W = J o O C U i U i i i i I I � � W W - � W N w E l W v W I U 06 � � 2 i I I l r I r l I � r I I I i 1 l l I i 1 I I \\`v��llinnufffiii� � No. - e 10200105 o STATE OF :W_ I I I I ELECTRICAL SPECIFICATIONS i 1 l SCALE AS NOTED I I 1 1 E6o 3 0