HomeMy WebLinkAbout0267.98.35cD L0 N O L0 • -. NOTES 1. ELECTRICAL SERVICE SHALL BE 600 AMP, 120/208V, 30, 4W. 2. CONTRACTOR SHALL CONTACT UTILITY CO. FOR UNDERGROUND SERVICE AND TRANSFORMER REQUIREMENTS AND SHALL INCLUDE ALL WORK IN BID. 3. CONTRACTOR SHALL VERIFY FAULT CURRENT WITH UTILITY CO. AND PROVIDE PROTECTION OF PANELS AS REQUIRED. 4. CONTRACTOR SHALL VERIFY THE SERVICE VOLTAGE W/ UTILITY CO. AND REVISE AND BALANCE PANELS AS REQUIRED. 5. STARTERS & RELATED WIRING SHALL BE SUPPLIED AND INSTALLED BY CONTRACTOR. OVERLOAD UNITS SHALL BE INSTALLED AS PER GIVEN NAMEPLATE DATA AND EQUIPMENT. STARTERS SHALL BE INSTAI LED AS PER MECHANICAL REQUIREMENTS. 6. REFER TO SHT M1 FOR ELECTRICAL REQUIREMENTS FOR H.V.A.C. 7. ALL DISCONNECT SWITCHES SHALL BE SUPPLIED AND INSTALLED BY CONTRACTOR. LOAD SUMMARY SPEED - D EQUIPMENT DESIGNATION LIGHTING W/ LCL WATTS MISC POWER WATTS AIR COND W/ LCL WATTS TOTAL WATTS PANEL A - 39,765 - 39,765 PANEL B 30,163 14,360 - 44,523 PANEL C l - 24,004 - 24,004 PANEL C2 - 24,004 - 24,004 RTU -1 ** - - 32,850 32,850 RTU -2 ** - - 32,850 32,850 TOTAL CONNECTED LOAD = 197,996 W 197,996W = 550 AMPS @ 120/208V, 3P, 4W THE EQUIPMENT RATED FULL LOAD AMPS AS STATED ABOVE IS FOR THE WORST SCENARIO OF THE EQUIPMENT TO BE INSTALLED ON THESE PROJECTS. * * THIS LOAD IS CALCULATED ON A UNIT TO BE RATED AT 51.2 FLA, 208V, 30. THIS LOAD FACTOR COULD CHANGE BASED ON EQUIPMENT USED. LOAD SUMMARY - LINE IGNATION LIGHTING W/ i LCL WATTS MISC POWER WATTS AIR COND W/ LCL WATTS TOTAL WATTS NEL A - 39,765 - 39,765 kEQUIPMENT NEL B 31,500 14,360 - 45,860 NEL Cl - 24,004 - 24,004 NEL C2 - 24,004 - 24,004 U -1 ** - - 32,850 32,850 RTU -2 ** - - 32,850 32,850 TOTAL CONNECTED LOAD = 199,333 W 193,256W = 537 AMPS © 120/208V, 3P, 4W THE EQUIPMENT RATED FULL LOAD AMPS AS STATED ABOVE IS FOR THE WORST SCENARIO OF THE EQUIPMENT TO BE INSTALLED ON THESE PROJECTS. * * THIS LOAD IS CALCULATED ON A UNIT TO BE RATED AT 51.2 FLA, 208V, 30. THIS LOAD FACTOR COULD CHANGE BASED ON EQUIPMENT USED. KEY NOTES � 1 REFER TO SINGLE -LINE DIAGRAM ON SHT. #E5 FOR FEEDER INFORMATION. 1/2" CONDUIT FOR EMS, SEE SHEET E6. (: PROVIDE 1/2" C.O. TO MECHANICAL CONTROL PER WIRING SCHEMATIC ON SHEET M2. PROVIDE CONNECTION FROM SUPPLY & RETURN AIR DUCT SMOKE DETECTORS TO FIRE ALARM SYSTEM & MECHANICAL CONTROL PANEL PER WIRING SCHEMATIC ON SHEET M2. NOT USED. VERIFY DISCONNECT SWITCH, STARTER SIZE AND FUSE SIZES WITH SELECTED EQUIPMENT MANUFACTURER PRIOR TO PLACING ORDER. ALL DEVICES SHALL HAVE WEATHERPROOF ENCLOSURE AND SHALL BE MOUNTED ON A 2 112" UNISTRUT FRAME ASSEMBLY WERE CONSTRUCTION OF DEVICES ARE NOT ALLOWED TO BE MOUNTED IN THE UNITS. VERIFY EXACT LOCATION. POWER & CONTROL ENTRY FROM BOTTOM OF UNII. D CONNECT TO RESTROOM LIGHTING. SEE SHEET E4 FOR EXACT LOCATION. 10 TO KITCHEN LIGHTING CIRCUIT. SEE SHEET E4. 1 1 1/2" C, WITH REQUIRED CONDUCTORS TO J -BOX IN CEILING ABOVE ICE MACHINE. 2 PIPE HOOD FOR GAS & CONDENSATE LINE THROUGH ROOF -3/A6. 13 PIPE HOOD FOR ELECTRIC,GAS & CONDENSATE LINE THROUGH ROOF -3/A6. 14 LOW VOLTAGE SMOKE DETECTOR WIRING SHALL BE RUN THROUGH BOTTOM ON RTU -2. 5 POWER CONNECTION SHALL BE RUN THROUGH BACK OF DISCONNECT INTO PARAPET UNDER ROOF AND THROUGH ADJACENT PIPE HOOD TO CONDENSORS. Ln 0 U Li I SHORT CIRCUIT PROTECTION NOTE: 1 THERE SHALL BE U.L. LISTED SERIES RATING BETWEEN CKT. BREAKERS LOCATED AT THE DISTRIBUTION PANEL AND THE DOWNSTREAM 10k A.I.C. RATED CIRCUIT BREAKERS AT PANELS "A ", "B ", "C2 ", & "Cl" BASED ON THE MAXIMUM FAULT CURRENT AS DETERMINED AT THE SERVICE ENTRANCE. GENERAL NOTES 1. ANY FEES ASSOCIATED W/ CONSTRUCTION & INSPECTION SHALL BE BY CONTRACTOR IN ORDER TO DELIVER TO THE OWNER A FINISHED BUILDING, READY FOR OCCUPANCY TO 100% OPERATION. 2. THE SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS FAMILIARIZED HIMSELF W/ THE PLANS & BUILDING SITE. CLAIMS MADE SUBSEQUENT TO THE PROPOSAL FOR THE MATERIALS AND LABOR BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED IF THEY COULD HAVE BEEN FORESEEN, HAD PROPER EXAMINATION BEEN MADE. 3. ANY COST INCURRED DUE TO LACK OF COOPERATION AMONG TRADES SHALL BE BORNE BY THE CONTRACTOR. 4. ANY DEVIATION FROM PLANS WITHOUT PRIOR APPROVAL OF THE ARCHITECT SHALL BE CAUSE FOR REJECTION OF MATERIALS AND /OR METHODS AND ANY COST INCURRED TO CORRECT SUCH DEVIATION TO THE SATISFACTION OF THE CONSTRUCTION MANAGER, SHALL BE BORNE BY THE CONTRACTOR. 5. TRADE NAMES ARE GIVEN TO CLARIFY TYPE OF PRODUCT & QUALITY DESIRED, SUBSTITUTIONS MAY BE MADE, PENDING APPROVAL OF THE TACO BELL RESTAURANT PLANNING & DESIGN DEPARTMENT BEFORE CONTRACTS ARE AWARDED. 6. INSULATE ALL CONDUIT PASSING THROUGH WALK -IN COOLER /FREEZER, FILL AROUND CONDUIT W/ DUCT /SEAL WHERE IT PASSES THROUGH COOLER /FREEZER WALL OR CEILING, AND INSTALL CONDUIT SEAL. 7. ALL EXTERIOR CONDUIT FOR WIRING SHOULD BE MINIMIZED BY ROUTING IN CEILING SPACE. NO EXTERIOR CONDUIT WILL BE ACCEPTED. 8. REFER TO MECHANICAL DWGS, FOR THE LOCATION OF EXHAUST FANS, AND OTHER SPECIAL EQUIPMENT. CONTRACTOR IS RESPONSIBLE FOR THE INSTALLATION OF ALL CONDUITS, J- BOXES, WIRING AND DISCONNECT SWITCHES AND THERMOSTAT J -BOX. SEE WIRING DIAGRAMS OF MECHANICAL SHEETS. 9. CONTRACTOR IS TO FURNISH AND INSTALL CONDUIT FOR LIFE SAFETY & LOW VOLTAGE WIRING. INSTALL & CONNECT LINE VOLTAGE WIRING. LOW VOLTAGE WIRING CONNECTIONS ON H.V.A.C. SYSTEM BY CONTRACTOR. 10. THE EQUIPMENT ROUGH -INS AS SHOWN ARE ACCURATE TO THE BEST OF OUR KNOWLEDGE. HOWEVER, IN SOME INSTANCES THE OWNER AND SUPPLIER MAY SUBSTITUTE OR THE EQUIPMENT MAY VARY FROM WHAT IS SHOWN. THEREFORE, THE CONTRACTOR SHALL VERIFY ALL CRITICAL DIMENSIONS WITH THE OWNER PRIOR TO CONSTRUCTION. P-411-URE OF THE CONTRACTOR TO VERIFY THESE DIMENSIONS SHALL PLACE THE RESPONSIBILITY FOR ANY SUBSEQUENT RELOCATION DIRECTLY UPON THE CONTRACTOR. 11. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE LATEST EDITION OF THE N.E.C. AND STATE AND LOCAL CODES AS THEY APPLY. 12. ALL FLEXIBLE METALLIC AND PVC CONDUIT WHERE ALLOWED BY LOCAL CODE IS TO BE PROVIDED WITH SEPARATE GROUND WIRE. 13. ALL EQUIPMENT SHOWN ON ROOF TO BE CONFIRMED EXCEPT RTU -1 & RTU -2. EQUIPMENT ARE AS FOLLOWS: a.) EF -1, EF -2 & EF -3 b.) ICE MACHINE CONDENSING UNIT c.) FREEZER /COOLER CONDENSING UNIT COMBINATION UGPS C.T. CAB'T & METER SOCKET (VERIFY DIMENSIONS W/ SERVING UTILITY COMPANY) 3' -6" DISTRIBUTION PANEL NATIoNA� ACCT'`_ NT SWITCH GEAR ,Ef13 .PFS '.� CONTACT: PFS SALES REP. G.C. SCOPE: INSTALL STANDARD PACKAGE, SUPPLY & %STALL NON STANDARD COMPONENTS NOTE: PAINT SERVICE ENTRANCE EQUIPMENT TO MATCH STUCCO COLORS. SEE EXTERIOR ELEVATIONS. ;_t /- FINISHED SLAB INCOMING SERVICE LATERAL _/ iI I I I \ \_ UNDERGROUND FEEDERS TO I I - AIR - CONDITIONING UNITS RTU -1 I I I & RTU -2 TO RISE AT NEAREST UNDERGROUND FEEDERS FULL HEIGHT PARTITION WALL cD TO PANELS "Cl" & "C2" & EXTEND OVERHEAD TO 0 RESPECTIVE AC -UNIT. co UNDERGROUND FEEDERS ~ TO PANELS "A" & "B" SERVICE ENTRANCE EQUIPMENT ELEVATION -" -L NE" (2) PARALLEL SETS OF 4 #350 KcMiL -3 "EA. M INSTALL 120/208V/30/4W/600A, �- COMBINATION U.G.P.S., CURRENT TRANSFORMER (CT) CAN AND METER SOCKET PER SERVING UTILITY COMPANY SPECIFICATIONS. NOTE: ALL WIRING SHOWN SHALL BE COPPER TYPE 'THHN /THWN EXCEPT FEEDERS FROM UTILITY TRANSFORMER TO SWITCHBOARD MAY BE ALUMINUM SINGLE LINE DISTRIBUTION DIAGRAM INSTALL UNDERGROUND SERVICE- LATERAL TO UTILITY TRANSFORMER PER SERVING UTILITY COMPANY SPECIFICATIONS. N.T.S. 1 3 DISTRIBUTION PANEL 'MS' 1 #3/0 CU EQUIPMENT 120/208V/30/4W/600A, BOND PER N.E.C. (SQUARE -D "I- LINE" PANELBOARD ARTICLE #250 -79c -d RATED FOR USE AS SERVICE ENTRANCE EQUIP.) CIRCUIT BREAKER MAIN T ,,�60OA /3P 1 2 3 4 5 6 200AT ) 200AT fl 3P5AT ) 3P 3P 3P 5AT } 70AT AT 3P 3P / l c o 0 o z z PER N.E.C. ARTICLE #250 -81 c -d 3/4 "C -1 #310 CU BOND TO COLD WATER PIPE PER N.E.C. ARTICLE PANEL #250 -80o 'A' PANEL PANEL PANEL RTU -1 RTU -2 'B' 'C1' 'C2' N.T.S.) 4 1 ELECTRICAL ROOF- PLAN GENERAL NOTES 1. REFERENCE SHEET E1 FOR "ELECTRICAL EQUIPMENT SCHEDULE ".O 2. - - - - BELOW ROOF - IN WALL /CONCEALED 3. ABOVE ROOF /EXPOSED 1 cp-- "A " -24 J "A" -1,3,5 3/4 "C, 4 #10 "A "- 32,34,36 3/4 "C, 4 #10 rv� W E., z E- w r\ Z V U O W d v1 nqn V Li mss o q is Q� I Q U U W W C) Q 0 Q Wz zQ_ J r) W z � W rr Q U T_ DRAWN BY: TTP CHECKM BY: TH BUILDING TYPE K -50 FRAME JOB NUMBER 97125 PROTOTYPE ISSUE DATE 2/l/97.1 SHEET NUMBER ES Z° O Z° - 0 Z .- 0 z 0 O m o m O m U p m U m m _ /3/4'C-1 r j CD v v U d U N N O M O co tD co (D co UD #3/0 CU GND PER N.E.C. ARTICLE #250 -81 c -d 3/4 "C -1 #310 CU BOND TO COLD WATER PIPE PER N.E.C. ARTICLE PANEL #250 -80o 'A' PANEL PANEL PANEL RTU -1 RTU -2 'B' 'C1' 'C2' N.T.S.) 4 1 ELECTRICAL ROOF- PLAN GENERAL NOTES 1. REFERENCE SHEET E1 FOR "ELECTRICAL EQUIPMENT SCHEDULE ".O 2. - - - - BELOW ROOF - IN WALL /CONCEALED 3. ABOVE ROOF /EXPOSED 1 cp-- "A " -24 J "A" -1,3,5 3/4 "C, 4 #10 "A "- 32,34,36 3/4 "C, 4 #10 rv� W E., z E- w r\ Z V U O W d v1 nqn V Li mss o q is Q� I Q U U W W C) Q 0 Q Wz zQ_ J r) W z � W rr Q U T_ DRAWN BY: TTP CHECKM BY: TH BUILDING TYPE K -50 FRAME JOB NUMBER 97125 PROTOTYPE ISSUE DATE 2/l/97.1 SHEET NUMBER ES