HomeMy WebLinkAbout1059.95.40ROOFTOP UNIT CABINET
GASKET BY —`
ROOFTOP UNIT MFR.
CANT STRIP BY , G.C.
WOOD NAILER BY
ROOFTOP UNIT MFR. / BUILT —UP ROOF BY G.C.
/ ROOF INSULATION BY G.C.
ROOF CURB BY
ROOFTOP UNIT MFR.
1 -1/2" RIGID / /i / / /i /
INSULATION BY G.C. //
`— METAL DECK BY G.C.
METAL CHANNEL FILLERS BY M.C.
TYPICAL ROOF CURB DETAIL 1
NO SCALE M2.1
f�lPf�A ►l ►If nT IM.IMTA1 f
INSL
PREI
CUR
ROO
AIN. 16"
EXHAUST FAN DETAIL
NO SCALE M2 �
AIR COOLED
CONDENSING
1. ALL PIPING AND PIPING COMPONENTS UNIT
ARE BY M.C.
2. PITCH ALL HORIZONTAL LINES A
MINIMUM OF 1/t IN 10 FEET IN CHARGING VALVE
DIRECTION OF REFRIGERANT FLOW
3. INSULATE ALL SUCTION LINES.
4. UNIT MANUFACTURER SHALL PROVIDE
REFRIGERANT PIPING SCHEMATIC INCLUDING
ALL LINES do VALVE SIZES AND EXACT LINES THRU ROOF
LINE ROUTING. THIS MUST BE SUBMITTED USE PIPE ENTRY
BY M.C. BEFORE CONSTRUCTION BEGINS. CURB. SEE SPEC.
5. ONLY ONE REFRIGERANT CIRCUIT SHOWN
SECOND CIRCUIT SHALL BE SIMILAR.
PIPING & VALVING
ARRANGEMENT FOR
B TONS AND GREATER
EVAPORATOR COILl
THERMAL
EXPANSION
VALVE
LIQUID LINE
SOLENOID VALVE
SIGHT GLASS —`
nLrzn oarm'�
REFRIGERANT PIP
No scnLc
SUCTION LINE
PRE — CHARGED LINES
FURNISHED BY EQUIPMENT MFR.
OIL TRAP USE SHORT RADIUS ELBOWS,
TOP OF TRAP SHALL BE A MIN.
OF 1-1/2" BELOW LOWEST
POINT OF EVAPORATOR COIL
MAGRAM r5
M2.1
DISCONNECT
BY FAN MF1
iPUN ALUMINUM ROOF
:XHAUST FAN
PROVIDE BIRD SCREEN
INSULATED
PREFABRICATED
CURB MIN. 12"
PITCHED ROOF
BACKDRAFT DAMPER
SHEETMETAL DUCT
ROOF EXHAUST FAN DETAILri�
NO SCALE M2.1
0
RAIN CAP
(BIRD PROOF)
REQUIRED BY NON -• ^\D-ING
CODE MASTIC OR
PLASTIC SEALER
AM
SUPPORT FUZE FROM
ROOF STRUCTURE
AS REQUIRED.
STORM COLLAR
ROOF FLASHING
�— ROOFING
TYPE 'B' FLUE
0
GAS FLUE DETAIL 4
NO SCALE M2
{I
I
1 ,
CURB CAP PTCHED TO DRAIN W/
ANTI— CONDENSATE COATING
NEOPRENE GASKET
WOOD NAILER
(W/CUR8) ,-ePVC
W ALUMINUM VENT CAP
BACK-
DRAFT—DAMPER
I
CPVC VENT PIPE
(
FOR R S ZE) TO PLAN!
1" RIGID INSULATION
(3 PCF DENSITY)
It HIGH PREFABRICATED
CURB
�C ROOF ,
k" OPENING �mPJI L i
DRYER VENT HIGH HAT DETAIL
NO SCALE MZ �
10"* I.D. FLUE
CLUB
ROOF PLAN - HVAC
PLAN NOTES:
�1 DUCTWORK EXPOSED TO WEATHER. PROVIDE ONE (1) LAYER OF INSULATION BOARD AND APPLY
PROTECTIVE COVERING PER SPECIFICATION.
O2 M.C. SHALL PENETRATE SLOPED ROOF WITH THE USE OF A INSULATED ROOF CURB. COORDINATE
PENETRATION WITH STRUCTURE AND G.C. FIELD VERIFY EXACT PENETRATION LOCATION AND
COORDINATE WITH G.C.
1
r,
0
fl
i
Browning Day Mullins Dtardorf Inc
334 North Senate Avenue
Indianapolis, Indiana 46204
317.635.5030
FAX 317.634.5409
ROTZ ENGINEERS INC.
oe� Ibd�aior aw o.cwod FiipUwt7
000 APOLIS. INIM" 46224
\101 1111 1Utfl / ///
15885 .�
`s STATE
0
OF
AIL 111111�� `
PRAIRIE
VIEW
GOLF
CLUB
Clubhouse
Roof Plan
N12.1
Project No.
5M
Drawn
SOL
Checked
GAMC
Scale
AS NOITED
Date
9-8 -95
Revision
=
Clubhouse
Roof Plan
N12.1