TYPICAL SANITARY SEWER SPECIFICATIONS TO BE USED FOR PRIVATE SEWER DEVELOPMENT WITHIN CLAY TOWNSHIP REGIONAL WASTE DISTRICT REVISED NOVEMBER, 2001 1. Standard specifications of the Clay Township Regional Waste District ( "District ") and Indiana Department of Transportation shall apply for all work and materials. Pipe shall be installed in accordance with Section 715 of the latest edition of the Indiana Department of Transportation Standard Specifications. 2. Sanitary sewer pipe shall be PVC in accordance with ASTM D -3034 (S.D.R. 35) and ASTM 2321. PVC pipe shall have grooved bell and gasket. The pipe shall be made of PVC plastic having a cell classification of 124546. 3. PVC sewer fittings shall conform to the requirements of ASTM D- 3034 -89 specification. Fittings in sizes through 8" shall be molded in one piece with elastomeric joints and minimum socket depths as specified in sections 6.2 and 7.3.2. Fittings 10" and larger shall be molded or fabricated in accordance with section 7.11 with manufacturers standard pipe bells and gaskets. Wall thickness of fittings shall be SDR 26 as defined in section 7.4.1 of specifications. Gaskets for elastomeric joints shall be molded with a minimum cross - sectional area of 0.20 square inches and conform to ASTM F -477 specification. 4. All sanitary manholes shall be precast concrete manholes in accordance with ASTM C -478 and Section 720. 0 -rings shall conform to C -443. Kent Seal or equivalent shall also be applied to all joints and between riser rings and castings. Manhole step spacing shall be no more than 16- inches. Manholes shall be air tested for leakage in accordance with ASTM C1244 -93, Standard Test Method for Concrete Sewer Manholes by the Negative Air Pressure (Vacuum) Test. A Installation and operation of vacuum equipment and indicating devices must be In accordance with manufacturer =s recommendations and performance specifications which have been provided by the manufacturer and accepted by the Engineer. B. With the vacuum tester set in place: 1. Inflate the compression bond to forty (40) psi to effect a seal between the vacuum base and the structure. 2. Connect the vacuum pump to the outlet port with the valve open. 3. Draw a vacuum of ten (10) inches of Hg. and close the valve. C. Accepted standards for leakage will be established from the elapsed time for a negative pressure change from ten (10) inches to nine (9) inches of mercury. The maximum allowable leakage rate for a four (4) foot diameter manhole must be in accordance with the following: Minimum Elapsed Time for a Manhole Depth Pressure Change of 1 Inch Hg 10 feet or less 60 seconds >10 feet but <15 feet 75 seconds >15 feet but <25 feet 90 seconds For manholes five (5) feet in diameter, add an additional fifteen (15) seconds and for manholes six (6) feet in diameter, odd an additional thirty (30) seconds to the time requirements for four (4) foot diameter manholes. For all manholes deeper than twenty -five (25) feet, the Engineer will determine the applicable minimum elapsed time. D. If the manhole fails the test, necessary repairs must be made and the vacuum test and repairs must be repeated until the manhole posses the test. E. If manhole joint sealants are pulled out during the vacuum test, the manhole must be disassembled and the joint sealants replaced. F. Manholes will be subject to visual inspection with all visual leaks being repaired. 5. Butyl rubber coating shall be applied around each manhole joint from 6- inches above to 6- inches below each joint. The appropriate primer shall be applied prior to applying the rubber coating. Inside joints to be filled with precoat plug material. 6. The manhole chimney =s including all riser rings shall be sealed using infi- Shield Uniband or approved equal. Prior to placement, the top 4- inches of the manhole cone and costing frome shall be cleaned and primed. The Uniband shall extend from 3- inches below the top of the cone section to 2- inches over the flange of the manhole costing frame. 7. The costing elevations are set by plan. However, the castings are to be adjusted in the field by the Engineer =s representative should a discrepancy occur between plan grade and existing grade. New manhole ring and cover shall be installed to establish grade. Maximum height of adjusting rings shall be 12- inches. 8. Backfill around all structures and all cuts under paved areas with granular material. Trenches opening within 5 -feet of paved roadways shall be backfilled with granular material in accordance with Section 211. Backfill under sidewalks shall be granular, unless the walks are constructed a minimum of 6 months after backfill has been in place. _ 9. The Contractor shall be responsible for verifying that all state highways, city, and county permits have been obtained by the developer prior to start of construction. 10. The Contractor shall be required to furnish the developer =s Engineer with a set of prints, marked in red pencil, showing actual sewer location and invert, to include lateral location, depth and length. Such as -built prints must be received by the Engineer before the final contract payment can be authorized. The sanitary sewer laterals and stubs termination shall be indicated on the surface with a metal fence post set immediately above the said termination point. 11. All sanitary sewer lines upon completion will be required to pass a low pressure air test. Said test shall be conducted according to ASTM 1417 -92, and shall be witnessed by an Engineer and a representative of the District. The testing shall be in accordance with Table 1. Add 0.5 psig for each foot of water above the sewer line being tested. 12. Deflection tests shall be performed on all flexible* pipe after the final backfill has been in place at least 30 days. No pipe shall exceed a vertical deflection of 5% deflection test results. ( *The following are considered non - flexible pipes: concrete pipe, ductile iron pipe, and cast iron pipe). The deflection test shall be performed with a nine -point mandrel. Proving rings shall be available. 13. All mandrel testing shall be observed by a professional engineer representative for certification and a representative of the District. 14. The ends of laterals are to be plugged tight with a braced plastic disc or cap capable of withstanding a low pressure air test without leakage. 15. Bedding for flexible pipe shall be No. 8 crushed stone from 6- inches below the pipe to 12- inches above the pipe. Bedding for rigid pipe shall be No. 8 crushed stone from 6- inches below the pipe to the spring line of the pipe and from this point to 12- inches above shall be fill sand or equivalent. Manholes shall be placed on no less than 6- inches of No. 8 crushed stone bedding. 16. Water and sewer line crossings and separations shall be in accordance with 327 IAC 3 -6 -9. 17. Trench shall be opened sufficiently ahead of pipe laying to reveal obstruction, and shall be properly protected and /or barricaded when left unattended. 18. No water shall be permitted to flow into the sanitary sewer system during construction. Contractor shall utilize a pump to keep the water level below the pipe. Pump discharge shall be directed to a storm outlet in accordance with state and federal laws and regulations (327 IAC 3- 6 -20). Any pipe entering existing sewers shall be plugged with screw type mechanical, braced plug until such time as all tests on the sewers have been completed and the lines have passed all punch lists. ng 19. All sewer laterals installed by the mainline Contractor shall be bedded the some as the main line sewer. 20. Forty -eight (48) hours notice shall be given to the District prior to the start of sewer construction. Also, 48 hours notice shall be given prior to doing any testing on the sewer. 21. Manhole castings shall be stamped SANITARY SEWER (Neenah Casting R 1642 or equal) and be self - sealing type. Waterproof castings shall be Neenah R- 1916 -F1 and stamped SANITARY SEWER. 22. The minimum slopes for sewer acceptance by the District are: Size of Pipe Minimum Constructed Slope TYPICAL UTILITY CROSSING 5 NO SCALE C$04 NEENAH R -1642 W /SELF /SEALING LID (OR EQUAL) FINISH GRADES STAMPED "SANITARY SEWER' N a ' -" DIA. EAST CONC. > RINGS TAPERED CONE INFI- SHIELD 'UNIBAND' SECTION OR APPROVED EQUAL SEAL o PER SPECIFICATIONS til .' L ° PRECAST CONCI z `,e b x SECTIONS :r (16" MAX.) C'4 v: o BUM RUBBER COATING MANHOLE STEPS AS PER SPECIFICATION 4• -0" DIA. FiLL WITH CONCRETE PLAN PRECAST BASE : •'•D'•'•'•' o.. a .a'.'...'.'.' #4 0 12" EA. WAY o•o O•o o•o o'., 0.0 0.0 .O•o o.o. o•o •0 °0.0 °O•o °O.0.0•0.O.0 °0.00 °o•o °o•o °o.o °o.o °0.0.0.0'0.0 °o•o °O•o 6" MIN. N0. 8 CRUSHED STONE 0.00.0.0 °0.0 °0.00 °0.00 °o.o °O.o °00.00 °o REQUIRED UNDER MANHOLE BASE FOR LEVELING AND SUPPORT 4'-0' MIN. MANHOLE BASE FOR PRECAST SECTION A -A SANITARY MANHOLE DETAIL CARMEL C804 NOTE MANHOLE CONFORMS TO ASTM C -478 JOINT CONFORMS TO ASTM C -443 1 NORMAL 4' PER GFOAOT J MIN. -1/8" PER FOOT SEE I CAP USE 6' UNLESS SPECIFIEI APPRO> ISOMETRIC PLAN PLAN VIEW 8 -inch 0.40% Time, min:8 Lech fOr Minimum Time $ Time for LOW Leagtb, S 10 -inch 0.28% 12 -inch 0.22% CONNECTION TO MAiN SEWER 2 15 -inch 0.15% 100 150ft C804 18 -inch 0.12% 300 ft 350 & 400 8 23. The Contractor shall provide measurements of the slope of 4 148 597 the sewer for each manhole section as construction 3.46 3:46 3 :46 progresses. Such measurements shall be certified by a COVER &SEAL 3:46 NOTE: CONTRACTOR SHALL PLACE A 2X4 POST ABOVE PROPOSED GRADE Registered Land Surveyor or Engineer and be available on -site 6 L ®END OF EACH LATERAL. POST for observation by the District =s Inspector. No more than 5:40 5.40 SHALL BE PAINTED GREEN. three manhole sections can be constructed in advance of such 5:40 5:40 5:42 measurements. * BELL HOLES SHALL BE PROVIDED 7:34 298 1.520 L AND THE TRENCH PREPARED SO THAT THE BOTTOM IS PROPERLY USE 6" SEWER PIPE UNLESS 24. In the event the Contractor does not meet the minimum SUPPORTED THROUGHOUT ITS 7:36 OTHERWISE SPECIFIED slopes, the sewer section and any other affected sewer LENGTH. 10 8 :26 sections shall be reconstructed to meet such minimum slopes. 2.374 L 9:28 9Z8 25. Laterals are to be traced with a minimum size of 14 9:63 11:52 13:51 gauge wire from the Wye to the terminus. The contractor for APPROX 90'-� 12 11:20 the building or home will extend the wire from this terminus 3.418 L 11:20 11:20 to the building cleanout adjacent to the building. 14 :15 17:05 19:58 22 :47 2538 16 LONG RADIUS CURVE TABLE 1 MINIMUM SPECIFIED TIME REQUIRED FOR A 1.0 prig DROP FOR SIZE AND LENGTH OF PIPE INDICATED p�Min== 11L Time, min:8 Lech fOr Minimum Time $ Time for LOW Leagtb, S SpeeiSostion Time for IA%* (L) Shawn, mica CHECKED BY: CIND DAS SHEET TITLE: 100 150ft 200 ft 250 ft 300 ft 350 & 400 8 450 ft 4 148 597 0.360 L 3.46 3:46 3 :46 3.46 3:46 3:46 3 :46 3 :46 6 5:40 386 0.834 L 5:40 5.40 5:40 5:40 5:40 5:40 5:42 6:24 8 7:34 298 1.520 L 7:34 7:34 7:34 7:34 7:36 8:52 10:08 11:24 10 8 :26 239 2.374 L 9:28 9Z8 9:28 9:63 11:52 13:51 15.49 17:48 12 11:20 199 3.418 L 11:20 11:20 11:24 14 :15 17:05 19:58 22 :47 2538 16 14:10 158 5.342 L 14:10 14.10 17:48 22:15 26:42 31:09 35:36 40:04 18 17:00 133 7.682 L 17:00 19:13 25:38 32:03 38:27 44:52 31:16 57.41 21 19:50 114 10.470 L 18:60 26:10 34:54 43:37 521 6100 69:48 78:31 24 22 :40 89 13.674 L 22:47 34:11 45:34 56 :58 68:22 79:46 91:10 10233 27 25:30 88 17.306 L 28:51 43:16 57:41 72:07 86.32 100:57 115:22 129:48 30 28:20 80 21.388 L 35:37 53:26 71:13 89:02 108:50 124:38 14225 160:15 33 31:10 72 25.852 L 49:05 64:38 88:10 107:49 129:18 150:43 1721 193:33 38 34:00 86 30.788 L 61:17 76:55 102:12 128:12 153:80 179:29 205:07 230:46 DIAMETER AS SPECIFIED ON PLANS * SEAL MUST BE ABLE TO PASS AIR PRESSURE TESTS REQUIRED FOR SEWER MAIN WYE & LATERAL CAPPING DETAIL 3 C804 2500 psi CONCRETE BOTTOM OF TRENCH Perspective View -earth cut away \\ � To be used when clear distance between pipes is 18" or less, or where noted on the drawings. CONCRETE CRADLE 4 C804 i.n M M 0 w W n. V) 0 I 0 O o wlz o' 00` n S O\\`\ EIS \ GA ©. No. �= 890'258 STATE OF �Dt ANQ: U�-0- THIS DRAWING AND THE IDEAS. DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF THE SCHNEIDER CORPORATION, AND ARE NOT TO BE USED OR REPRODUCED. IN,WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF THE SCHNEIDER CORPORATION. © COPYRIGHTED BY THE SCHNEIDER CORP. (2002 f4lbI Schneider THE SCHNEIDER CORPORATION Historic Fort Harrison 8901 Otis Avenue Indianapolis, IN 46216 -1037 Telephone: 317.826.7100 Fax: 317.826.7200 www.schneidercorp.com Architecture Civil Engineering Environmental Engineering Geotechnical Services GIS * LIS Home Builder Services Interior Design Land Surveying Landscape Architecture Transportation Engineering DATE: PROJECT NO.: 09/03/02 3357.003 0112 -.t CHECKED BY: CIND DAS SHEET TITLE: GENERAL DETAILS & SPECIFICATIONS DRAWING FILES: S: \3k \3357 \003 \dwgs \C804.dwg XREF: S: \3k \3357 \003 \dw9s \Title1.dwg CD �L,o(04 co Wz C\2 H Z � 0 c o c co U x x co C" x b Q) 0 DATE: PROJECT NO.: 09/03/02 3357.003 DRAWN BY: CHECKED BY: CIND DAS SHEET TITLE: GENERAL DETAILS & SPECIFICATIONS DRAWING FILES: S: \3k \3357 \003 \dwgs \C804.dwg XREF: S: \3k \3357 \003 \dw9s \Title1.dwg SHEET NO.: �L,o(04