HomeMy WebLinkAbout06020007.17L a 0 N °o N M 01 VI 'c cn a 0 U 3 m N 0 TYPICAL SANITARY SEWER SPECIFICATIONS TO BE USED FOR PRIVATE SEWER DEVELOPMENT WITHIN CLAY TOWNSHIP REGIONAL WASTE DISTRICT REVISED MAY, 2002 1. Standard specifications of the Clay Township Regional Waste District (District) and Indiana Department of Transportation shall apply for all work and materials. Pipe shall be installed in accordance with Section 715 of the latest edition of the Indiana Department of Transportation Standard Specifications. 2. Sanitary sewer pipe shall be PVC in accordance with ASTM D -3034 (S.D.R. 35) and ASTM 2321. PVC pipe shall have a grooved bell and gasket. The pipe shall be made of PVC plastic having a cell classification of 12454B. 3. PVC sewer fittings shall conform to the requirements of ASTM D- 3034 -89 specification. Fittings in sizes through 8" shall be molded in one piece with elastomeric joints and minimum socket depths as specified in sections 6.2 and 7.3.2. Fittings 10" and larger shall be molded or fabricated in accordance with section 7.11 with manufacturers standard pipe bells and gaskets. Wall thickness of fittings shall be SDR 26 as defined in section 7.4.1 of specifications. Gaskets for elastomeric joints shall be molded with a minimum cross - sectional area of 0.20 square inches and conform to ASTM F -477 specification. 4. All sanitary manholes shall be Aprecast concrete@ manholes in accordance with ASTM C -478 and Section 720. 0 -rings shall conform to C -443. Kent Seal or equivalent shall also be applied to all joints and between riser rings and castings. Manhole step spacing shall be no more than 16- inches. Manholes shall be air tested for leakage in accordance with ASTM C1244 -93, Standard Test Method for Concrete Sewer Manholes by the Negative Air Pressure (Vacuum) Test. A Installation and operation of vacuum equipment and indicating devices must be in accordance with manufacturer =s recommendations and performance specifications which have been provided by the manufacturer and accepted by the Engineer. The vacuum equipment must be capable of testing the entire manhole, including the casting and riser rings. B. With the vacuum tester set in place: 1. Connect the vacuum pump to the outlet port with the valve open. 2. Draw a vacuum of ten (10) inches of Hg. and close the valve. C. Accepted standards for leakage will be established from the elapsed time for a negative pressure change from ten (10) inches to nine (9) inches of mercury. The maximum allowable leakage rate for a four (4) foot diameter manhole must be in accordance with the following: Minimum Elapsed Time for a Manhole Depth Pressure Change of 1 Inch Hg 10 feet or less 60 seconds >10 feet but <15 feet 75 seconds >15 feet but <25 feet 90 seconds For manholes five (5) feet in diameter, add an additional fifteen (15) seconds and for manholes six (6) feet in diameter, add an additional thirty (30) seconds to the time requirements for four (4) foot diameter manholes. For all manholes deeper than twenty -five (25) feet. Engineer will determine the applicable minimum elapsed time. D. If the manhole fails the test, necessary repairs must be made and the vacuum test and repairs must be repeated until the manhole passes the test. E. If manhole joint sealants are pulled out during the vacuum test, the manhole must be disassembled and the joint sealants replaced. F. Manholes will be subject to visual inspection with all visual leaks being repaired. 5. Butyl rubber coating shall be applied around each manhole joint from 6- inches above to 6- inches below each joint. The appropriate primer shall be applied prior to applying the rubber coating. Inside joints to be filled with precoat plug material. 6. The manhole chimney =s including all riser rings shall be sealed using Infi - Shield AUniband@ or approved equal. Prior to placement, the top 4- inches of the manhole cone and casting frame shall be cleaned and primed. The Uniband shall extend from 3- inches below the top of the cone section to 2- inches over the flange of the manhole casting frame. 7. The casting elevations are set by plan. However, the castings are to be adjusted in the field by the Engineer =s representative, should a discrepancy occur between plan grade and existing grade. New manhole ring and cover shall be installed to establish grade. Maximum height of adjusting rings shall be 12- inches. 8. Backfill around all structures and all cuts under paved areas with granular material. Trenches opening within 5 -feet of paved roadways shall be backfilled with granular material in accordance with Section 211. Backfill under sidewalks shall be granular, unless the walks are constructed a minimum of 6 months after backfill has been in place. 9. The Contractor shall be responsible for verifying that all state highways, city, and county permits have been obtained by the developer prior to start of construction. 10. The Contractor shall be required to furnish the developer =s Engineer with a set of prints, marked in red pencil, showing actual sewer location and invert, to include lateral location, depth and length. Such Acts built© prints must be received by the Engineer before the final contract payment can be authorized. The sanitary sewer laterals and stubs termination shall be indicated on the surface with a metal fence post set immediately above the said termination point. 11. All sanitary sewer lines upon completion will be required to pass a low pressure air test. Said test shall be conducted according to ASTM 1417 -92, and shall be witnessed by an Engineer and a representative of the District. The testing shall be in accordance with Table 1. Add 0.5 psig for each foot of water above the sewer line being tested. 12. Deflection tests shall be performed on all flexible* pipe after the final backfill has been in place at least 30 days. No pipe shall exceed a vertical deflection of 5% deflection test results. ( *The following are considered non - flexible pipes: concrete pipe, ductile iron pipe, and cast iron pipe). The deflection test shall be performed with a nine -point mandrel. Proving rings shall be available. 13. All mandrel testing shall be observed by a professional engineer representative for certification and a representative of the District. 14. The ends of laterals are to be plugged tight with a braced plastic disc or cap capable of withstanding a low pressure air test without leakage. 15. Bedding for flexible pipe shall be No. 8 crushed stone from 6- inches below the pipe to 12- inches above the pipe. Bedding for rigid pipe shall be No. 8 crushed stone from 6- inches below the pipe to the spring line of the pipe and from this point to 12- inches a;ove shall be fill sand or equivalent. Manholes shall be placed on no less than 6- inches of No. 8 crushed stone bedding. 16. Water and sewer line crossings and separations shall be in accordance with 3271AC 3 -6 -9. 17. Trench shall be opened sufficiently ahead of pipe laying to reveal obstruction, and shall be Properly protected and /or barricaded when left unattended. 18. No water shall be permitted to flow into the sanitary sewer system during construction. Contractor shall utilize a pump to keep the water level below the pipe. Pump discharge shall be directed to a storm outlet in accordance with state and federal laws and regulations (327 -IAC 3- 6 -20). Any pipe entering existing sewers shall be plugged with screw type mechanical, braced plug until such time as all tests on the sewers have been completed and the lines have passed all punch lists. 19. All sewer laterals installed by the mainline Contractor shall be bedded the some as the main line sewer. 20. Forty -eight (48) hours notice shall be given to the District prior to the start of sewer construction. Also, 48 hours notice shall be given prior to doing any testing done on the sewer. 21. Manhole castings shall be stamped SANITARY SEWER, Neenah Casting R 1642A or equal and be self - sealing type. The casting flange shall be 34 inches and the clear opening shall be 24 inches. Waterproof castings shall be Neenah R- 1916 -F1 and stamped SANITARY SEWER. 22. The minimum slope for sewer acceptance by the Clay Township Regional Waste District are: Size of Pipe Minimum Constructed Slope TABLE I MINIMUM SPECIFIED TDNE REQUIRED FOR A 1.0 psig DROP FOR SIZE AND LENGTH OF PIPE INDICATED TABLE 1 Pipe Diameter In. 8 -inch 0.40% Specification Time for Length (L) Shown, mints 10 -inch R- 1916 -F1 0.28% 1045Z2 12 -inch 150 ft 0.22% 250 R 15 -inch 350 ft 0.15% 450 ft 18 -inch 3:48 0.12% 23. The Contractor shall provide measurements of the slope Registered Land Surveyor or Engineer be of the sewer for each manhole section as construction progresses. Such measurements shall be certified by a and advance of such measurements. available on -site for observation by the District =s Inspector. No more than three manhole sections can be constructed in 24. In the event the Contractor does not meet the minimum slopes, the sewer section and any other affected sewer sections shall be reconstructed to meet such minimum slopes. 0.854 L 540 5:40 25. Laterals are to be traced with a minimum size of 14 gauge wire from the Wye to the terminus. The contractor for the building or home will extend the wire from this terminus to the building cleanout adjacent to the building. 5:42 6:24 TABLE I MINIMUM SPECIFIED TDNE REQUIRED FOR A 1.0 psig DROP FOR SIZE AND LENGTH OF PIPE INDICATED TABLE 1 Pipe Diameter In. Mminn mt Time, mina Length for Minimlun Time, ft Time for Longer Length, S Specification Time for Length (L) Shown, mints R -1642A R- 1916 -F1 EAST JORDAN 1045Z2 100 Fit 150 ft 200 ft 250 R 300 ft 350 ft 400 ft 450 ft 4 3:48 597 0.360 L 3:46 3:46 3 :46 346 3:46 3:46 3:46 3:46 6 5:40 386 0.854 L 540 5:40 5:40 5:40 5:40 5:40 5:42 6:24 8 7:34 298 1.520 L 7:34 7:34 7:34 7:34 7:36 8:52 10:08 11:24 10 8:26 239 2.374 L 9:28 9:28 11:20 9:28 9:63 11:52 13:51 15:49 17:48 12 11:20 199 3.418 L 11:20 11:24 14:15 17:05 19:58 22:47 25:38 16 14:10 158 5.342 L _14:10 14:10 17:48 22:15 26:42 31:09 35:36 40:04 18 17:00 133 7.682 L 17:00 19:13 25:38 32:03 26:27 44:52 51:16 57:41 21 19:50 114 10.470 L 1 18:60 26:10 34:54 43:37 52:21 1 61:00 69:48 78:31 24 22:40 89 13.674 L 22:47 34:11 34 56:58 68:22 79:46 91:10 102:33 27 25:30 88 17.306 L 28:51 43:16 57:41 72:07 86:32 100:57 115:22 129:48 30 28:20 80 21.388L 96:37 53:26 71:13 89:02 108:50 124:38 142:25 160:15 33 31:10 72 25.852 L 49:05 64:38 88:10 107:49 129:18 150:43 172:21 193:53 38 34:00 86 30.788 L 61:17 76:55 102:12 128:12 153:80 179:29 205:07 230:46 FINISH Go " ill 104 INFI "UN BUTYL Rl _ N r M MANHOLE CASTING SCHEDULE MANUFACTURER SELF SEALING WATERTIGHT NEENAH R -1642A R- 1916 -F1 EAST JORDAN 1045Z2 1045WT CASTING SHALL BE EITHER SELF - SEALING OR WATERTIGHT, (SEE PLAN & PROFILE SHEETS FOR CASTING TYPE). LIDS SHALL BE STAMPED "SANITARY SEWER" AND HAVE CLOSED PICKHOLES. FRAME SHALL BE SET ON DOUBLE ROW OF KENT SEAL, (SEE MANHOLE CASTING SCHEDULE). PRECAST CONCRETE ADJUSTING RING DOUBLE ROW OF KENT SEAL MANHOLE STEPS PER SPECS INTERIOR JOINTS AND LIFT HOLES SHALL BE SEALED WITH NON - SHRINK GROUT PER SPECS SET BARREL JOINTS WITH RUBBER TYPE GASKET EQUAL TO ASTM C -443 AND ON DOUBLE ROW OF KENT SEAL MANHOLE REINF. PER ASTM SPECS PIPE DIA. PER PLAN & PROFILE BENCHWALL SHALL BE CLASS "B" CONC. BENCHWALL HEIGHT SHALL BE 80% OF PIPE DIA. ,MANHOLE TO PIPE CONNECTION BOOTS, NCLUDING LATERALS, SHALL BE A -LOCK, DURA SEAL OR APPROVED EQUAL. 6" MIN. CONCRETE ENCASEMENT 6" MIN. COMPACTED #8 STONE I.D. SANITARY MANHOLE - TYPE "B" NOT TO SCALE NOTE: BEDDING, HAUNCHING AND INITIAL BACKFILL MATEPIALS, PLACEMENT AND COMPACTION FOR WATER MAINS, WATER SERVICES LATERALS, SANITARY MAINS AND SANITARY SERVICE LATERALS SHALL BE IN ACCORDANCE WITH THE STANDARD PRACTICE OF THE UTILITY THAT HAS JURISDICTION OVER THE INSTALLATION. FINAL BACKFILL FOR WATER MAINS, WATER SERVICE LATERALS, SANITARY MAINS AND SANITARY LATERALS UNDER AND WITHIN 5 -FEET OF PAVEMENT SHALL BE B- BORROW FOR STRUCTURE BACKFILL MEETING THE MATERIAL REQUIREMENTS OF THE INDOT AND SHALL BE COMPACTED IN 6 -INCH MAXIMUM LIFTS TO NOT LESS THAN 95% STANDARD PROCTOR DENSITY FOR THE ENTIRE DEPTH OF THE MATERIAL PLACED. THE BACKFILL FOR THE TOP 6- INCHES OF THE EXCAVATION BELOW THE START OF THE AGGREGATE SUBBASE OF THE PAVEMENT HALL BE NO. 53 STONE MEETING THE MATERIAL REQUIREMENTS OF THE INDOT AND SHALL BE COMPACTED TO NOT LESS THAN 950/7 STANDARD PROCTOR DENSITY. IF THE STANDARD PRACTICE OF THE UTILITY THAT HAS JURISDICTION OVER THE INSTALLATION HAS A MORE STRINGENT FINAL BACKFILL REQUIREMENT, THE MOPE STRINGENT REQUIREMENT SHALL GOVERN. SANITARY MANHOLE R -1642A NOT -TO- -SCALE W \V BOTTOM OF TRENCH d D D a D D \ D D d \ D Q D D a CLAY TOWNSHIP REGIONAL WASTE DISTRICT SUMMARY OF-LATERA.I_ LVSTALLATiON REQUIREMENTS 1. All houses, buildings, etc., shall connect to the District's sanitary sewer system within 90 days of notice providing a sewer is within 300 feet for Hamilton County or 100 feet for Boone County of the property line. Only one (wilding may connect to the sewer main per lateral unless otherwise approved by the Disbid 2. No foundation or other storm Water drains shall be interconnected to the sewer lateral installed and connected to the District's sanitary sewer. 3. The existing sewer line from the building to the septic tank may only be used if it is located under a building addition, patio, porch or paved driveway. Air test is required to show, if acceptable for re -use. The property owner shag bear the cost of all testing. The District inspector must be Dnsite for the duration of the air test. 4. The owner or contractor shall notify the District prior to covering the installed lateral so that the District can make an inspection to determine compliance With the District's sower use ordinahm, Such notification shall be made 24 hours prior to the need for the inspection. B the inspection fails and a second inspection is required, or contractor is not on site for scheduled inspection, or fails to cancel inspection, an additional fee of $100.00 will be due. This must be paid prior to the time of the follow up inspection. 5. Pmperty owners are hereby advised that the County Board of Health regulates the operation and maintenance of private sewage disposal (septic) systems. The County ordinance provides in part that, upon connection to a public sewer, a septic tank ' -shall be abandoned and filled with earthen material in a safe and sanitary manner.' Please contact the appropriate County Board of Health for further information. 6 Acceptable Pipe Materials: PVC PIPE: SDR 35, ASTM D -3034, SIX INCH PIPE PVC PIPE: SDR 21, ASTM 0-241, SIX INCH PIPE GASKETS JOINTS ASTM D 3212 GASKETS ASTM F -477 FITTINGS - SDR -26 DUCTILE IRON MECHANICAL COUPLING WITH PROPER FITTINGS. CLEAN OUTS TO BE LOCATED THREE FEET WITHIN THE FOUNDATION AND NO MORE THAN 300 FEET APART. 7 Bedding: Use fill sand or Number 8, 9 or 11 stone Fill material Is to be placed from 6 inches below to 6 inches above the pipe The trench should be a minimum of 18 inches wide 8. Laterals shall be installed no closer than 20 feet from water wells unless PVC pressure grade pipe is used meeting SDR 21 and ASTM D -2241. Any proposed installation requiring pressure pipe shall be reviewed and accepted by the District and the District's engineer prior to Installation. 9. Where a transition is made between SDR 35 pipe and pressure grade SDR 21 pipe, a ductile iron gasketod mechanical coupling shall be used. 10. Laterals shall terminate within 3 feet of the building unless the conditions in item #3 above are ,net. No clued Dice shall be installed outside of building foundation walls. 11. Additional information on District standards and specifications may be obtained from the District's office 0unng business hours of 8 00a m. to 430 p m Monday through Friday All District standards can be located on our web site at hao' /hxw�a ctrwrf r Clay Township Regional Waste District 10701 North College Suite A. Indianapolis, Indiana 46280 Phone: 844 -9200 Fax: 844 -9203 12 Septic effluent shall not be pumped out into the sanitary sewer system. 13. The District shall Inspect ALL laterals. Please call the District office at 844 9200 24 hours prior to time of inspection 14. Contractors shall lair 1d oauge- stranded wire the entire length of the lateral Wire is to be placed on top of the lateral. The ussinct inspector will verify placement of the wire. After inspection, bedding is to be placed on top 15. Call before you dg. IUPPS 1.800-382-5544,48 hours prior to digging I_dtera1ray.01 -05akr 2500 psi CONCRETE TAMPED IN PLACE #8 CRUSHED STONE \ \ PERSPECTIVE VIEW - EARTH CUT AWAY \ TO BE USED WHEN CLEAR DISTANCE BETWEEN PIP ® ES IS 18" OR LESS, OR WERE NOTED ON THE DRAWINGS. CONCRETE CRADLE NOT -TO -SCALE MANHOLE CASTIN7771 MANUFACTURER SELF SE NEENAH R -1 4 EAST JORDAN 1045 CASTING SHALL BE EITHER SELF - SEALING OR WATERTIGHT, (SEE PLAN k PROFILE SHEETS FOR CASTING TYPE). LIDS SHALL BE STAMPED 'SANITARY SEWER" AND HAVE CLOSED PICKHOLES. FRAME SHALL BE SET ON DOUBLE ROW OF 1/2 KENT SEAL, OR SINGLE ROW OF 1" KENT SEAL (SEE MANHOLE CASTING SCHEDULE). FINISH GRADE Ln x 24' - PRECAST CONCRETE ADJUSTING RING - �m a W 19358 IA STATE OF DOUBLE ROW OF KENT SEAL }- O S`S,bNAL ''''''111►111111 MANHOLE STEPS PER SPECS INFlSHIELD "UNIBAND" Q INTERIOR JOINTS AND LIFT HOLES BUTYL RUBBER J SHALL BE SEALED NTH NON- SHRINK Q �� %1 V GROUT PER SPECS, NO GROUT ABOVE 1' I � TOP OF CONE SECTION CD iV) Cr W SET BARREL JOINTS WITH RUBBER TYPE GASKET j -- LLJ I _ EQUAL TO ASTM C -443 AND ON DOUBLE ROW OF O O ;y ti 00 14" KENT SEAL OR SINGLE ROW OF 1" KENT SEAL 1 ^ '- - W MANHOLE REINF. PER ASTM SPECS i-4 o to n PIPE DIA. PER PLAN do PROFILE i � J ei BENCHWALL SHALL BE CLASS "8" CONC. BENCHWALL HEIGHT SHALL BE 80% OF PIPE DIA. �. U I"� V) MANHOLE TO PIPE CONNECTION BOOTS, i INCLUDING LATERALS, SHALL BE A -LOCK, DURA r SEAL OR APPROVED EQUAL. PRESS -SEAL, KOR -N -SEAL AND OTHER FLEXIBLE BOOTS r> SHALL NOT BE USED IN MANHOLES WITH PIPE INVERT DEPTHS OF 14 FT. OR GREATER. I:,. - -4 _ r 6" MIN. COMPACTED #8 SNE TO ' SANITARY MANHOLE -- TYPE "A" NOT TQ SCALE MANHOLES SHALL BE AIR TESTED IN ACCORDANCE WITH ASTM C1244 -93, STANDARD TEST METHOD FOR CONCRETE SEWER MANHOLES BY THE NEGATIVE AIR PRESSURE (VACUUM) TEST. #8 CRUSHED STONE HAND TAMPED OR WALKED IN TO 12" ABOVE PIPE. AND 8" BELOW PIPE NOTE: ALL BEDDING & INTAIL BACKFILL SHALL BE INSTALLED IN 6" TO 12" BALANCED LIFTS DX2 (MAX) SANITARY SEWER SERVICE CONNECTION NOT -TO -SCALE MIN. WIDTH L25 (O.D.) -12" #8 CRUSHED STONE BELL HOE EXCAVATED. BEDDING DETAIL NOT -TO -SCALE CD In Z _O (n w Of `L < W F- < 0 0 M z Q = M w a LC) \ o m LLJ ^ I I oa 1 1 0 111111111111 /11j STOEpp, 1,,i�� Ln ......... P�1STEq�' • c� ° Li No. s �m a W 19358 � w STATE OF 0 }- O S`S,bNAL ''''''111►111111 Q \111 \1` Q BACKFILL WITH CLEAN GRANULAR MATERIAL PER REQUIREMENT OF INDIANA DEPARTMENT OF HIGHWAYS (MECHANICAL COMPACTED TO 95% PROCTOR DENSITY). JDISTURBED EARTH NOT -TO -SCALE SANITARY SEWER SERVICE CONNECTION NOT -TO -SCALE SURFACE % MIN. SLOPE I SHALL BE MAIN SEWER n� a 0 Ln z < Z L1J > 0-) zj- DO �m a W W �N 0 }- O Z Q Q Li Z W J Q �� %1 V I � CD iV) Cr W I UJ r- LLJ I _Z O O `^ V 00 Z W o to n Z � J w 0 �. U I"� V) V J Q �m a W W �N pZ }- O CY OI- �-•�- U F- Z W Z Q �� %1 V LLJ Q U SHEET NO. C800 Joe No 46600S2B