HomeMy WebLinkAbout08060046.3612 GAUGE HANGER WIRE OR CHAIN FOR FIXTURE
SUPPORT CONNECTED TO STRUCTURE ABOVE
JUNCTION BOX
,-'C) CD FLEXIBLE CONDUIT / \ 1���LAY-IN .CEILING
O O FLEXIBLE
WIRE (6' MAX.)
LAY -IN CEILING.
SEISMIC
CLIP
LAY -IN CEILING .
LAY -IN CEILING
LAY IN LIGHT FIXTURE DETAIL
NOT TO SCALE
GENERAL NOTES:
1. SUPPORTS FOR CABLE SHALL BE INDEPENDANTLY SUPPORTED. CABLE SHALL NOT LAY OVER
CONDUIT, DUCTWORK, PIPING, STRUCTURAL SUPPORT MEMBERS, ETC. CABLE SHALL BE
NEATLY INSTALLED AT RIGHT ANGLES TO THE BUILDING LINES. ENGINEER WILL REQUIRE CABLE
TO BE REMOVED AND REINSTALLED IF IT IS NOT INSTALLED IN AN ACCEPTABLE MANNER.
2. REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITY
3. WIRING INSTALLATION:
a• WIRING INSTALLED IN WALLS, ABOVE INACCESSABLE CEILINGS, OR AREAS WITH EXPOSED CEILINGS
SHALL BE INSTALLED IN CONDUIT COMPLETE.
b. WIRING INSTALLED ABOVE ACCESSABLE CEILINGS MAYBE EXPOSED PLENUM RATED CABLE
EXISTING NURSE
CALL SYSTEM
CABINET. PROVIDE
ALL MODIFICATION
NECESSARY TO
EXPAND EXISTING
SYSTEM
PROVIDE NEW DESKTOP
MASTER STATION SIMILAR TO
AIPHONE AX -8M. PROVIDE 16
BUTTON ADD ON AS REQUIRED.
SIMILAR TO AIPHONE AX -16SW.
1 I r- llka L. IVI%1�7 I Lf\ 1 l L 111 V IYIV 1 --
STATION, STAFF ANNUNCIATOR FOR THE EXISTING
STATION AND DUTY NURSE CALL SYSTEM.
STATIONS ANNUNCIATOR SHALL BE FOR THE
NEW AND EXISTING AREAS.
I
PATIENT
BED
TYPICAL PATIENT ROOM
TYPICAL NURSE CALL SYSTEM SCHEMATIC
GENERAL NOTES:
1. SUPPORTS FOR CABLE SHALL BE INDEPENDANTLY SUPPORTED. CABLE SHALL NOT LAY OVER
CONDUIT, DUCTWORK, PIPING, STRUCTURAL SUPPORT MEMBERS, ETC. CABLE SHALL BE
NEATLY INSTALLED AT RIGHT ANGLES TO THE BUILDING LINES. ENGINEER WILL REQUIRE CABLE
TO BE REMOVED AND REINSTALLED IF IT IS NOT INSTALLED IN AN ACCEPTABLE MANNER.
2. REFER TO FLOOR PLANS FOR DEVICE LOCATIONS AND QUANTITY
3. WIRING INSTALLATION:
a. WIRING INSTALLED ABOVE ACCESSABLE CEILINGS MAY BE EXPOSED PLENUM RATED CABLE
b. WIRING INSTALLED IN WALLS, ABOVE INACCESSABLE CEILINGS, OR AREAS WITH EXPOSED CEILINGS
SHALL BE INSTALLED IN CONDUIT COMPLETE.
4. PROVIDE POWER SUPPLY SIMILAR TO AIPHONE PS- 2420UL AS REQUIRED.
CAT 5e PLENUM RATED CABLING
PROVIDE NEW FLUSH MOUNTED
INDOOR SUBSTATION SIMILAR TO
AIPHONE AX -AN. SEE DRAWINGS
FOR QUANTITIES AND LOCATIONS.
PROVIDE NEW CNETRAL EXCHANGE
UNIT. SIMILAR TO AIPHONE AX -248C.
CAT 5e PLENUM RATED CABLING
INTERCOM SYSTEM SCHEMATIC
NO SCALE
SECOND FLOOR
FLOOR
FEEDER AND BRANCH CIRCUIT SCHEDULE
FEEDER/BRANCH CIRCUIT
DESIGNATION
CONDUCTOR SIZE PER CONDUIT
CONDUIT SIZE AND QUANTITY
PHASE &
NEUTRAL
EQUIPMENT
GROUND
1P, 1N, 1G,
2P 1G
2P, 1N, 1G,
3P 1G
3P, 1N, 1G
3P, 2N, 1G
3P, 3N, 1G
3P, 1N, 2G
F20
12
12
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
F30
10
10
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
F40 -50
8
10
3/4"
3/4"
3/4"
1"
1"
3/4"
F60
6
10
3/4"
3/4"
1"
1"
1"
1"
F70 -F80
4
8
3/4"
1"
1 -1/4"
1 -1/4"
1 -1/4"
1 -1/4"
F90 -F100
3
8
1"
1"
1 -1/4"
1 -1/4"
1 -1/2"
1 -1/2"
F110
2
6
1"
1 -1/4"
1 -1/4"
1 -1/2"
1 -1/2"
1 -1/4"
F125
1
6
1 -1/4"
1 -1/4"
1 -1/2"
2"
2"
1 -1/2"
F150
1/0
6
1 -1/4"
1 -1/2"
1 -1/2"
2"
2"
2"
F175
2/0
6
1 -1/4"
1 -1/2"
2"
2"
2 -1/2"
2"
F200
3/0
6
1 -1/2"
2"
2"
2 -1/2"
2 -1/2"
2"
F225
4/0
4
1 -1/2"
2"
2 -1/2"
2 -1/2"
3"
2 -1/2"
F250
250
4
2"
2"
2 -1/2"
3"
3"
2 -1/2"
F300
350
4
2"
2 -1/2"
3"
3"
3 -1/2"
3"
45 KVA
TRANSFORMER
T7
EXISTING 277/480 3P -4W, 2500 AMP
GE SPECTRA SERIES, 65 KAIC.
MSB
EXIST SPARE
F60 �
� F100
F200
MSB
CHP2
—
SPARE SPARE
(1)#4 GND, 1 "C
HB3
TO BUILDING
RP6A
STEAM
GROUNDING
GENERATOR
SYSTEM
SPARE HP3
FUSE AT 200 AMPS.
120/208
EXIST
120/208
3P -4W
3P -4W
200A
EXIST
100A
MCB
EXIST
MCB
EXISTING 277/480 3P -4W, 2500 AMP
GE SPECTRA SERIES, 65 KAIC.
MSB
EXIST SPARE
EXIST
AHU -1
FUSE AT 300 AMPS.
CHP2
CHP3
SPARE SPARE
LP -3
LP-4
STEAM
GENERATOR
SPARE
SPARE HP3
FUSE AT 200 AMPS.
EXIST
EXIST
EXIST
EXIST
EXIST
EXIST
EXIST
ONE LINE RISER DIAGRAM
NO SCALE
NOTE: TERMINATE CONDUIT ABOVE ACCESSIBLE CEILING.
DEVICES LOCATED IN AREAS THAT DO NOT HAVE CEILING
OR HAVE HARD CEILINGS SHALL HAVE CONDUIT
INSTALLED FROM DEVICE TO ABOVE THE NEAREST
CORRIDOR ACCESSABLE CEILING OR AS NOTED ON THE
DRAWINGS. THE INTENT OF THE CONDUIT SYSTEM IS
THAT THERE SHALL BE NO EXPOSED SYSTEMS CABLING
OR CABLING ABOVE HARD CEILINGS.
(1) 3/4 "C FROM BOX TO —
ABOVE ACCESSIBLE CEILING
TERMINATE
WITH BUSHING
TYPICAL
TELEVISION JACK
2 GANG BOX WITH 1 GANG
PASTER RING
TERMINATE
WITH BUSHING
TERMINATE
WITH BUSHING
LONG SWEEP 90
(1) 1 "C FROM BOX TO J
ABOVE ACCESSIBLE CEILING
TYPICAL VOICE /DATA —
TELECOMMUNICATIONS
JACK 2 GANG BOX WITH 1
GANG PASTER RING
MSE
ECTOR CONSULTING LLC
Mechanical & Electrical Engineering
212 West 9 Oth Street, Suite Q395
Indianapolis, Indiana 46202
ph. 317632.4444
fax 317 632.4960
"' "'C FROM BOX TO
ACCESSIBLE CEILING
LONG SWEEP 90
PICAL VOICE ONLY
LECOMMUNICATIONS
'K 2 GANG BOX WITH 1
NG PASTER RING
LOWER LEVEL
TELECOMMUNICATION AND TELEVISION SYSTEM SCHEMATIC
NO SCALE
FLENA1ilE; -
PROJ. NO 06-M
DRAWN BY EAF
PLOT SCALE: AS NOTED
DATE 04MOS
I�
W
Q
NH
w
W
z
� z�
Fq
Q
w ~z
W a
�wz
w
�oQ
W �z
�Qw
w
>*a�
�zo
0
/ ///
R.
No.
10200105
=� STATE OF
'����1111111111 \ \\
A -,r- ID (�—
TM ARCHITECTS, INC.
6535 N. F X1,I1SON STREET
INDIANAPOLIS, INDIANA 46220
PFIOPE (M 255 -475
FWMODM (M 255 -7399
E-U L. T06ARCM*A0LCOM
E4.01