CITY OF CARMEL 2005 COVER AND BACKFILL POLICY
9/8/06
STORM SEWERS UNDER PAVEMENT, SIDEWALK, PAVED AREAS AND WITHIN RIGHT -OF -WAY
BEDDING AND HAUNCHING
BEDDING AND HAUNCHING FOR ALL REINFORCED CONCRETE PIPE INSTALLATIONS SHALL BE #8 STONE MEETING
THE MATERIAL REQUIREMENTS OF THE INDOT. THE MATERIAL SHALL BE APPROVED BY THE CITY OF CARMEL
DEPARTMENT OF ENGINEERING AT TIME OF INSTALLATION. BEDDING SHALL BE PLACED IN THE TRENCH BOTTOM
SUCH THAT AFTER THE PIPE IS INSTALLED TO GRADE AND LINE, THERE REMAINS A 4 -INCH MINIMUM DEPTH OF
MATERIAL BELOW THE PIPE BARREL AND A MINIMUM OF 3- INCHES BELOW THE BELL. FOR PIPE SIZES 66- INCHES
AND LARGER, THE MINIMUM DEPTH OF MATERIAL BELOW THE PIPE BARREL SHALL BE 6- INCHES.
BEDDING SHALL BE PLACED TO BE UNIFORM AS POSSIBLE, BUT SHALL BE LOOSELY PLACED UNCOMPACTED
MATERIAL UNDER THE MIDDLE THIRD OF THE PIPE PRIOR TO PLACEMENT OF THE PIPE. IF THE UNDERLYING
SOILS OF THE TRENCH BOTTOM ARE SOFT OR YIELDING, THE SOIL SHALL BE UNDERCUT TO SUCH A DEPTH THAT
WHEN REPAIRED WITH #2 STONE IT WILL PRODUCE A UNIFORM AND STABLE FOUNDATION ALONG THE ENTIRE
LENGTH OF THE PIPE. HAUNCHING SHALL BE COMPACTED IN 8 -INCH MAXIMUM LIFTS TO NOT LESS THAN 90%
STANDARD PROCTOR DENSITY FOR THE ENTIRE DEPTH OF THE MATERIAL PLACED. THE BACKFILL SHALL BE
BROUGHT UP EVENLY ON BOTH SIDES OF THE PIPE FOR THE FULL LENGTH OF THE PIPE, HAUNCHING SHALL
EXTEND TO THE SPRINGLINE OF THE PIPE. MINIMUM TRENCH WIDTH SHALL BE THE OUTSIDE DIAMETER OF THE
PIPE PLUS 18- INCHES.
FINAL BACKFILL
FINAL BACKFILL FOR ALL REINFORCED CONCRETE PIPE INSTALLATIONS UNDER AND WITHIN 5 -FEET OF PAVEMENT
OR SIDEWALK OR OTHER PAVED AREAS AND FOR ALL INSTALLATIONS WITHIN CITY RIGHT -OF -WAY SHALL BE
STRUCTURE FOR B BORROW O S BACKFILL MEETING THE MATERIAL REQUIREMENTS OF THE INDICT. THE MATERIAL
SHALL BE APPROVED BY THE CITY OF CARMEL DEPARTMENT OF ENGINEERING AT TIME OF INSTALLATION. FINAL
BACKFILL SHALL BE COMPACTED IN 6 -INCH MAXIMUM LIFTS TO NOT LESS THAN 95% STANDARD PROCTOR
DENSITY FOR THE ENTIRE DEPTH OF THE MATERIAL PLACED- THE BACKFILL FOR THE TOP 6- INCHES OF THE
EXCAVATION BELOW THE START OF THE AGGREGATE SUB -BASE OF THE PAVEMENT SHALL BE NO. 53 STONE
MEETING THE MATERIAL REQUIREMENTS OF THE INDOT AND SHALL BE COMPACTED TO NOT LESS THAN 95%
STANDARD PROCTOR DENSITY. FINAL BACKFILL FOR ALL REINFORCED CONCRETE PIPE INSTALLATIONS GREATER
THAN 5 -FEET FROM PAVEMENT, SIDEWALK, OTHER PAVED AREAS OR THE LIMIT OF CITY RIGHT -OF -WAY SHALL
BE CLEAN FILL MATERIAL FREE OF ROCKS LARGER THAN 6- INCHES IN DIAMETER, FROZEN LUMPS OF SOIL, WOOD
OR OTHER EXTRANEOUS MATERIAL, COMPACTED IN 12 -INCH MAXIMUM LIFTS TO NOT LESS THAN 90% STANDARD
PROCTOR DENSITY FOR THE ENTIRE DEPTH OF THE EXCAVATION. THE FINAL 6- INCHES OF THE EXCAVATION
SHALL CONSIST OF TOPSOIL.
WATER AND SEWER UNDER PAVEMENT, SIDEWALK, PAVED AREAS AND WITHIN RIGHT -OF -WAY
BEDDING, HAUNCHING, INITIAL BACKFILL
BEDDING, HAUNCHING AND INITIAL BACKFILL MATERIALS, PLACEMENT AND COMPACTION FOR WATER MAINS, WATER
SERVICE LATERALS, SANITARY MAINS AND SANITARY SERVICE LATERALS SHALL BE IN ACCORDANCE WITH THE
STANDARD PRACTICE OF THE UTILITY THAT HAS JURISDICTION OVER THE INSTALLATION.
FINAL BACKFILL
FINAL BACKFILL FOR WATER MAINS. WATER SERVICE LATERALS, SANITARY MAINS AND SANITARY SERVICE
LATERALS UNDER AND WITHIN 5 -FEET OF PAVEMENT OR SIDEWALK OR OTHER PAVED AREAS AND FOR ALL
INSTALLATIONS WITHIN CITY RIGHT -OF -WAY SHALL BE B- BORROW FOR STRUCTURE BACKFILL MEETING THE
MATERIAL REQUIREMENTS OF THE INDOT. THE MATERIAL SHALL BE APPROVED BY THE CITY OF CARMEL
DEPARTMENT OF ENGINEERING AT TIME OF INSTALLATION. FINAL BACKFILL SHALL BE COMPACTED IN 6 -INCH
MAXIMUM LIFTS TO NOT LESS THAN 953 STANDARD PROCTOR DENSITY FOR THE ENTIRE DEPTH OF THE MATERIAL
PLACED, THE BACKFILL FOR THE TOP 6- INCHES OF THE EXCAVATION BELOW THE START OF THE AGGREGATE
SUB -BASE OF THE PAVEMENT SHALL BE NO. 53 STONE MEETING THE MATERIAL REQUIREMENTS OF THE INDOT
AND SHALL BE COMPACTED TO NOT LESS THAN 95% STANDARD PROCTOR DENSITY. IF THE STANDARD PRACTICE
OF THE UTILITY THAT HAS JURISDICTION OVER THE INSTALLATION HAS A MORE STRINGENT FINAL BACKFILL
REQUIREMENT, THE MORE STRINGENT REQUIREMENT SHALL GOVERN.
MINIMUM COVER FOR PIPE CROSSINGS WITHIN CITY RIGHT -OF -WAY
FOR INSTALLATION OF STORM MAINS, WATER MAINS, SANITARY MAINS, WATER SERVICE LATERALS, SANITARY
SERVICE LATERALS UNDER CITY STREETS, REGARDLESS OF THE JURISDICTION OF THE UTILITY, THE MINIMUM
COVER FROM THE TOP OF THE INSTALLED PAVEMENT TO THE TOP OF THE INSTALLED PIPE SHALL BE THE
PAVEMENT SECTION THICKNESS (ALL BITUMINOUS AND AGGREGATE MATERIAL ABOVE THE SUBGRADE) PLUS 1 -D ",
BUT UNDER NO CIRCUMSTANCES SHALL THE COVER ALONG ANY PART OF THE PIPE FROM THE FINAL PAVEMENT
ELEVATION TO THE TOP OF THE PIPE BE LESS THAN 2.5 -FEET. IF THE STANDARD PRACTICE OF THE UTILITY
THAT HAS JURISDICTION OVER THE INSTALLATION HAS A MORE STRINGENT COVER REQUIREMENT, THE MORE
STRINGENT REQUIREMENT SHALL GOVERN.
COVER HEIGHTS FOR REINFORCED CONCRETE PIPE STORM SEWER THAT ARE LESS THAN THOSE REQUIRED WILL BE
EVALUATED ON A CASE BY CASE CONDITION AND APPROVED ONLY WITH WRITTEN PERMISSION BY THE CITY
ENGINEER.
SOIL EROSION CONTROL SUMMARY
CONTRACTOR SHALL INSTALL SEDIMENT TRAPS AND CONTRUCTION EROSION CONTROL
DEVICES AS SHOWN.
2.
MASS GRADE THE SITE (SIDES OF SWALES, AND MOUNDS TO BE SODDED OR SEEDED AND
MULCHED IMMEDIATELY UPON COMPLETION). TEMPORARY SEEDING SHALL BE RECOMMENDED
FOR ALL SWALES AND DISTURBED AREAS THAT CANNOT BE FINAL SEEDED WITHIN A TIME
PERIOD THAT WILL PREVENT SOIL EROSION, FOR TEMPORARY SEEDING THE CONTRACTOR
SHALL UTILIZE A FAST GROWING SEED OF EITHER OATS, ANNUAL RYEGRASS, WHEAT OR RYE
DEPENDING UPON TIME OF YEAR. DISTURBED AREAS SHOULD BE KEPT TO A MINIMUM AT
ALL TIMES.
3.
CONTRACTOR SHALL CONTROL MUD ACCUMULATION ON ALL STREETS SURROUNDING THE
PROJECT BY INSTALLING STONE SURFACE AT ALL LOCATIONS WHERE CONSTRUCTION
TRAFFIC LEAVES THE SITE. DUST SHALL BE KEPT TO A MINIMUM BY UTILIZING
SPRINKLING, CALCIUM CHLORIDE, VEGETATIVE COVER, SPRAY ON ADDITIVES OR OTHER
APPROVED METHODS. CLEANING OF STREET SHALL BE REQUIRED AS DIRECTED BY LOCAL
AUTHORITIES, OWNER, ARCHITECT, OR ENGINEER.
4.
MAINTAIN ALL FILTERS AND TRAPS DURING CONSTRUCTION TO PREVENT ANY BLOCKAGES
FROM ACCUMULATED SEDIMENT, ADDITIONAL SEEDING AND STRAW BALES MAY BE REQUIRED
ATI
DURING CONSTRUCTION AS SPECIFIED BY ENGINEER OR SOI L CONSERVATION SERVICE. RIP
RAP SHALL BE PLACED IN AREAS OF HIGH VELOCITY STREAM FLOW (MINIMUM SIZE 1/3
CU.FT.). PAYMENT FOR ADDITIONAL STRAW BALES AND RIP RAP NOT SHOWN ON PLANS
AND SEEDING SHALL BE ON A UNIT BASIS.
5.
CONTRACTOR SHALL INSTALL ALL STORM SEWER INLET FILTERS AS STORM SEWER SYSTEM IS
INSTALLED.
6.
ALL PROPOSED PARKING AREAS TO BE PAVED AS SOON AS POSSIBLE AFTER SUBGRADE
IS PREPARED.
7.
CONTRACTOR SHALL REMOVE ALL TEMPORARY EROSION AND SEDIMENT CONTROLS ONLY
WHEN THERE IS A SUFFICIENT GROWTH OF GROUND COVER TO PREVENT FURTHER
EROSION.
8.
ALL SWALES SHALL BE SEEDED IMMEDIATELY AFTER FINAL GRADING.
PARKING LOT STRIPING
1. PAINT MATERIAL SHALL COMPLY WITH FEDERAL SPECIFICATION TT- P -115A FOR
TRAFFIC PAINT WITHOUT GLASS SPHERES. (COLOR BY OWNER SELECTION).
2. STRIPE PARKING LINES AS SHOWN ON DRAWINGS WITH STRIPING PAINT.
SUBCONTRACTOR TO PERFORM ALL FIELD LAYOUT WORK NECESSARY TO ACHIEVE
STRAIGHT AND TRUE LINES. ASPHALT MUST BE CLEANED WITH POWER BROOM AND
HAND BROOM TO REMOVE ALL LOOSE MATERIAL BEFORE STRIPING. THE
SUBCONTRACTOR TO PROVIDE BARRIERS TO PREVENT MARRING OF LINES BY VEHICLES
UNTIL PAINT HAS DRIED. STRIPING PAINT SHALL BE APPLIED AT THE MINIMUM RATE OF
ONE GALLON PER 10D SQUARE FEET OF PAINT (BASED ON 39% SOLIDS) AT A WIDTH OF
FOUR INCHES.
PAVEMENT CONSTRUCTION
1. THE INDIANA DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS, LATEST
EDITION SHALL APPLY TO WORKMANSHIP AND MATERIALS IN CONSTRUCTION OF
SUBGRADE, PAVEMENT, CURBS AND WALKS.
o. PREPARE THE SUBGRADE IN ACCORDANCE WITH INDOT SECTION 207. NO
TRAFFIC WILL BE PERMITTED ON THE PREPARED SUBGRADE PRIOR TO PAVING.
b. BITUMINOUS PAVEMENT IN ACCORDANCE WITH INDICT SECTION 402.
c. FINISHING EARTH GRADED SHOULDERS, DITCHES AND SLOPES IN ACCORDANCE
WITH INGOT SECTION 208.
CONCRETE CURB AND WALKS
1. SEE DETAIL SHEET FOR TYPE AND DETAILS.
2. CONCRETE SHALL BE READY MIXED PORTLAND CEMENT AND WATER CONFORMING TO
A.S.T.M C -150. AGGREGATES SHALL CONFORM TO A.S.T.M, C -33. COMPRESSIVE
STRENGTH OF CONCRETE AT 28 DAYS SHALL BE 4000 P.S.I. WHERE REQUIRED,
REINFORCEMENT SHALL BE WELDED STEEL WIRE FABRIC CONFORMING TO A.S.T.M.
A -185.
3. ALL EXTERIOR CONCRETE SHALL CONTAIN 3% TO 6% AIR ENTRAINMENT.
4. APPLICATION
a, PLACE CONCRETE ONLY ON A MOIST, COMPACT SUBGRADE OR BASE FREE FROM
LOOSE MATERIAL. PLACE NO CONCRETE ON MUDDY OR FROZEN SUBGRADE IN
ACCORDANCE WITH INDOT SECTION 604 AND 605.
b. CONCRETE SHALL BE DEPOSITED SO AS TO REQUIRE AS LITTLE REHANDLING AS
PRACTICAL. WHEN CONCRETE IS TO BE PLACED AT AN ATMOSPHERIC
TEMPERATURE OF 35 DEGREES F OR LESS, PARAGRAPH 702.11 OF THE INDOT
SPECIFICATIONS SHALL APPLY.
c. EXCEPT AS OTHERWISE SPECIFIED, CURE ALL CONCRETE BY ONE OF THE
METHODS DESCRIBED IN INDOT SECTION 501.17.
5. TOP OF CASTING ELEVATIONS REFER TO THE CASTING'S RIM OR TOP OF CURB. THE
CURB CONTRACTOR SHALL INSURE THAT CURB INLET CASTINGS ARE SET AT PROPER
ELEVATION PRIOR TO CONSTRUCTION OF ADJACENT CURB.
DEMOLITION
1. THE CONTRACTOR SHALL EXCAVATE, DEMOLISH, REMOVE AND DISPOSE OF THE DEBRIS
FROM THE AREAS SHOWN ON THE SITE DEVELOPMENT PLAN.
a. BUILDING WALLS.
b. FOUNDATIONS.
c. PAVEMENT (CONCRETE, ASPHALT AND BRICK).
d. CONCRETE SLABS.
2. ALL MATERIAL AS A RESULT OF THE GENERAL DEMOLITION SHALL BE THE PROPERTY OF
THE CONTRACTOR, THE CONTRACTOR'S LUMP SUM BID PRICE FOR THE DEMOLITION SHALL
TAKE INTO ACCOUNT THE SALVAGEABLE VALUE OF MATERIALS AND SAID BID PRICE SHALL
REFLECT SAID SAVINGS.
3. THE CONTRACTOR SHALL BE REQUIRED TO DEMOLISH AND REMOVE DESIGNATED
FOUNDATION WALLS, RETAINING WALLS, CURBING, CONCRETE SLABS, PAVING, TANKS,
STRUCTURES, PIPES, MANHOLES AS SHOWN ON THE CONTRACT DOCUMENTS. ALL EXISTING
BASEMENT FLOOR SLABS THAT ARE NOT REMOVED SHALL BE BROKEN UP SUFFICIENTLY TO
PERMIT DRAINAGE THROUGH THE SLAB. ALL EXISTING BASEMENT WALLS, FOUNDATIONS,
FLOOR SLABS, AND ETC. SHALL BE REMOVED TO AN ELEVATION SUCH THAT THEY WILL NOT
SUPPORT PROPOSED FLOOR SLABS OR PAVEMENTS.
4. THE CONTRACTOR SHALL OBTAIN FROM THE CITY OF CARMEL, AND ALL OTHER APPLICABLE
GOVERNMENTAL AUTHORITIES, NECESSARY PERMITS REQUIRED, A COPY OF SUCH PERMITS TO
BE FURNISHED TO THE OWNER PRIOR TO COMMENCEMENT OF ANY WORK REQUIRED HEREIN.
THE CONTRACTOR SHALL FURTHER FURNISH TO THE OWNER PROOF THAT HE HAS COMPLIED
WITH THE PROVISIONS OF THE MUNICIPAL CODE OF INDIANAPOLIS, INDIANA.
UTILITIES
1. ALL WATER LINES FROM CITY OF CARMEL WATER COMPANY MAIN TO ANY LOT SHALL BE
INSTALLED OF MATERIAL AND WORKMANSHIP AS APPROVED WITH THE CITY OF CARMEL WATER
COMPANY.
2. CONDUIT SHALL BE REQUIRED FOR ALL ELECTRICAL AND TELEPHONE LINES UNDER PAVED
AREAS.
3. COMPACTED GRANULAR BACKFILL SHALL BE REQUIRED FOR ALL CROSSINGS OF PAVED
AREAS PER CITY OF CARMEL DEPARTMENT OF TRANSPORTATION SPECIFICATIONS.
NOTE: THE DEVELOPER/ OWNER AND THE ENGINEER /
FINAL CONSTRUCTION PLANS
NOTE_ PRIOR TO ISSUANCE OF ANY BUILDING PERMITS
9 -16 -08
NOTE. IT 15 THE CONTRACTORS RESPONSIBILITY TO
`,`,`,`ON
R-5050 Series
9 -24 -08
THE BITUMINOUS BASE AND BINDER LAYERS FOR ALL
LL
O Z
COORDINATE WITH PROJECT ENGINEER TO INSURE THE
0
ULTIMATELY RESPONSIBLE TO ENSURE THE PROJECT IS
Automatic Drainage Gate
i..- �.- -.®.o. ".�.-- .. -.-�.
H
OQ
`"'
CONTRACTOR HAS THE MOST CURRENT, COMPLETE.
Automatic drainabe gates are used In areas xith a requirement io prevent back Novo, such
BUILT WITH ALL PLAN COMMISSION CONDITIONS BEING
AND ALL WATER MAINS AND HYDRANTS FOR THE SITE
APPROVED SET OF PLANS AND SPECIFICATIONS FOR THIS
U) /I/111111'11�1�
as storm and sanitari sawar „rsterls
R • wo«a
'Y
PROJECT. ENGINEER DOES NOT ACCEPT RESPONSIBILITY,
STANDArD CATES Furnished w1h tiAe�rtca clo3ure for rrexrnLm eaae of opera -Ion
SPECIFICATIONS AND MADE SERVICEABLE.
u
GENE: Al_ INF3FIUTATION Gates arr made d cast iron. All mcvlrg pars operate un
MEET THE FORESAID CRITERIA.
stainless steel hinge pins. The cover ia hung with cast iron arms (Ductile Iron arms on
'
larger sizes) located at the outer edges near the certer of grave y to ensure sensitive
".�
,
`
s•s�4� evGrx
cpe-ation. For Improvec seating order with naoprena seat at antra cost.
W
U_
Aluminum covers can ba funllshad 4o spec al -ecuirrn -ents, It spe ifiLd Also available on
U.
speaa orde- and at axtra cost are neoprene or 5dlc bronze seat mounts and bronze
z
O
w
tua-lcd hngoa.
J
R
U/
z
z
Q
U
O
O
w
W
For apcilcaUans with ex-reme nead pressure contact Neenan's FXodut
It
~
U
V /
Q
Engneering Depairrent
W
z
LL
LL
>
U
O
�
w
Maxlm.trr heat loss occurs when Flpe is flowing -ull Consider the f-ead loss to L-e one -hall
z
CL
W
U)
the pipe dlame-er
TL
W
O
ix
These flan Cates are self- drainlrq when no .1p- stream Clow exists and nc� head Is or the
C
�
'k
rn
cownstream side
zr
Lin
z
W
0
--ii
Dlmen3tons n inci-es
Catalog No. Catalog No. Catalog No.
Type SF Type CF Type FF Diameter A B
C
D
E
F
N
5
R -5050 SF6 R- 5053 -CFE• -1 5050 -FFE. 6 7 11
13
1
334
7
foul
516
R 5050 �F8 53 F E 8 9
1
1 /"
114
four
5/8
R- 51350 -RF1 5 1 .• 50 10 0 4 1 2
151
a 1 2
1 1/
11 1 4
four
51E
R -�5050- F12 8-5053 -CF12 H-5050 -FF12 12 131 /4 1G 7/8
18
15 3/4
1 116
-31/4
four
5/8
R -5050 -c r1 s R- 5053 -CF15 is 16114 1 Q
21
105/4
11/0
-6 1 /4
four
5/c
R 5060 GF18 R 5063 CF1a p E050 FF18 18 10114 22118
2141/4
22 1/9
1 114
-0 1/4
tour
914
R -5050 SF20 121- 5053 -CF2,0 :1- E050 -17172'0 20 22114 25119
27114
25 118
1 114
22 114
four
314
R -5u15n =1721 R-s,ObO -CF21 2- 22114 25118
271/4
251!9
1 114
221/4
four
?M
_
R-Sn50 PF�)4 R- S)F.71- ,F`4 :� rOSr 1717:'4 ;)4 25114 PR 114
R(' 114
?R 114
1 114
7S 114
SIX
f14
R-15050-5F27 2; 28114 31 114
351/4
91 114
1 114
281/4
six
71E
R- 51)50 -EF30 R- 5050 -CF3D 30 31 114 341/4
3E 12
34 114
11/4
31 114
six
71E
R -5050 SF36 R- 5050 -CF56 36 3711'2 41 112
45112
z-1 1/2
1 316
371/2
Six
7/E
R -9)50 c_F42 R- 5050 -CF42 42 43112 471/2
4S 12
7 112
1 318
491/2
sun
7/E
R -5050 SF46 R- 505D -CF48 48 49112 54
5612
54
1 112
49 112
six
1
III ill
Type SFatfached to Typo CF attached to
I
Type FFaffached to
concrete wall corrugated metal pipe.
fanged Iron pipe
(not II use with hellcat CUP)
NEENAH xqF
FOUNDRY
SOIL EROSION CONTROL SUMMARY
CONTRACTOR SHALL INSTALL SEDIMENT TRAPS AND CONTRUCTION EROSION CONTROL
DEVICES AS SHOWN.
2.
MASS GRADE THE SITE (SIDES OF SWALES, AND MOUNDS TO BE SODDED OR SEEDED AND
MULCHED IMMEDIATELY UPON COMPLETION). TEMPORARY SEEDING SHALL BE RECOMMENDED
FOR ALL SWALES AND DISTURBED AREAS THAT CANNOT BE FINAL SEEDED WITHIN A TIME
PERIOD THAT WILL PREVENT SOIL EROSION, FOR TEMPORARY SEEDING THE CONTRACTOR
SHALL UTILIZE A FAST GROWING SEED OF EITHER OATS, ANNUAL RYEGRASS, WHEAT OR RYE
DEPENDING UPON TIME OF YEAR. DISTURBED AREAS SHOULD BE KEPT TO A MINIMUM AT
ALL TIMES.
3.
CONTRACTOR SHALL CONTROL MUD ACCUMULATION ON ALL STREETS SURROUNDING THE
PROJECT BY INSTALLING STONE SURFACE AT ALL LOCATIONS WHERE CONSTRUCTION
TRAFFIC LEAVES THE SITE. DUST SHALL BE KEPT TO A MINIMUM BY UTILIZING
SPRINKLING, CALCIUM CHLORIDE, VEGETATIVE COVER, SPRAY ON ADDITIVES OR OTHER
APPROVED METHODS. CLEANING OF STREET SHALL BE REQUIRED AS DIRECTED BY LOCAL
AUTHORITIES, OWNER, ARCHITECT, OR ENGINEER.
4.
MAINTAIN ALL FILTERS AND TRAPS DURING CONSTRUCTION TO PREVENT ANY BLOCKAGES
FROM ACCUMULATED SEDIMENT, ADDITIONAL SEEDING AND STRAW BALES MAY BE REQUIRED
ATI
DURING CONSTRUCTION AS SPECIFIED BY ENGINEER OR SOI L CONSERVATION SERVICE. RIP
RAP SHALL BE PLACED IN AREAS OF HIGH VELOCITY STREAM FLOW (MINIMUM SIZE 1/3
CU.FT.). PAYMENT FOR ADDITIONAL STRAW BALES AND RIP RAP NOT SHOWN ON PLANS
AND SEEDING SHALL BE ON A UNIT BASIS.
5.
CONTRACTOR SHALL INSTALL ALL STORM SEWER INLET FILTERS AS STORM SEWER SYSTEM IS
INSTALLED.
6.
ALL PROPOSED PARKING AREAS TO BE PAVED AS SOON AS POSSIBLE AFTER SUBGRADE
IS PREPARED.
7.
CONTRACTOR SHALL REMOVE ALL TEMPORARY EROSION AND SEDIMENT CONTROLS ONLY
WHEN THERE IS A SUFFICIENT GROWTH OF GROUND COVER TO PREVENT FURTHER
EROSION.
8.
ALL SWALES SHALL BE SEEDED IMMEDIATELY AFTER FINAL GRADING.
PARKING LOT STRIPING
1. PAINT MATERIAL SHALL COMPLY WITH FEDERAL SPECIFICATION TT- P -115A FOR
TRAFFIC PAINT WITHOUT GLASS SPHERES. (COLOR BY OWNER SELECTION).
2. STRIPE PARKING LINES AS SHOWN ON DRAWINGS WITH STRIPING PAINT.
SUBCONTRACTOR TO PERFORM ALL FIELD LAYOUT WORK NECESSARY TO ACHIEVE
STRAIGHT AND TRUE LINES. ASPHALT MUST BE CLEANED WITH POWER BROOM AND
HAND BROOM TO REMOVE ALL LOOSE MATERIAL BEFORE STRIPING. THE
SUBCONTRACTOR TO PROVIDE BARRIERS TO PREVENT MARRING OF LINES BY VEHICLES
UNTIL PAINT HAS DRIED. STRIPING PAINT SHALL BE APPLIED AT THE MINIMUM RATE OF
ONE GALLON PER 10D SQUARE FEET OF PAINT (BASED ON 39% SOLIDS) AT A WIDTH OF
FOUR INCHES.
PAVEMENT CONSTRUCTION
1. THE INDIANA DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS, LATEST
EDITION SHALL APPLY TO WORKMANSHIP AND MATERIALS IN CONSTRUCTION OF
SUBGRADE, PAVEMENT, CURBS AND WALKS.
o. PREPARE THE SUBGRADE IN ACCORDANCE WITH INDOT SECTION 207. NO
TRAFFIC WILL BE PERMITTED ON THE PREPARED SUBGRADE PRIOR TO PAVING.
b. BITUMINOUS PAVEMENT IN ACCORDANCE WITH INDICT SECTION 402.
c. FINISHING EARTH GRADED SHOULDERS, DITCHES AND SLOPES IN ACCORDANCE
WITH INGOT SECTION 208.
CONCRETE CURB AND WALKS
1. SEE DETAIL SHEET FOR TYPE AND DETAILS.
2. CONCRETE SHALL BE READY MIXED PORTLAND CEMENT AND WATER CONFORMING TO
A.S.T.M C -150. AGGREGATES SHALL CONFORM TO A.S.T.M, C -33. COMPRESSIVE
STRENGTH OF CONCRETE AT 28 DAYS SHALL BE 4000 P.S.I. WHERE REQUIRED,
REINFORCEMENT SHALL BE WELDED STEEL WIRE FABRIC CONFORMING TO A.S.T.M.
A -185.
3. ALL EXTERIOR CONCRETE SHALL CONTAIN 3% TO 6% AIR ENTRAINMENT.
4. APPLICATION
a, PLACE CONCRETE ONLY ON A MOIST, COMPACT SUBGRADE OR BASE FREE FROM
LOOSE MATERIAL. PLACE NO CONCRETE ON MUDDY OR FROZEN SUBGRADE IN
ACCORDANCE WITH INDOT SECTION 604 AND 605.
b. CONCRETE SHALL BE DEPOSITED SO AS TO REQUIRE AS LITTLE REHANDLING AS
PRACTICAL. WHEN CONCRETE IS TO BE PLACED AT AN ATMOSPHERIC
TEMPERATURE OF 35 DEGREES F OR LESS, PARAGRAPH 702.11 OF THE INDOT
SPECIFICATIONS SHALL APPLY.
c. EXCEPT AS OTHERWISE SPECIFIED, CURE ALL CONCRETE BY ONE OF THE
METHODS DESCRIBED IN INDOT SECTION 501.17.
5. TOP OF CASTING ELEVATIONS REFER TO THE CASTING'S RIM OR TOP OF CURB. THE
CURB CONTRACTOR SHALL INSURE THAT CURB INLET CASTINGS ARE SET AT PROPER
ELEVATION PRIOR TO CONSTRUCTION OF ADJACENT CURB.
DEMOLITION
1. THE CONTRACTOR SHALL EXCAVATE, DEMOLISH, REMOVE AND DISPOSE OF THE DEBRIS
FROM THE AREAS SHOWN ON THE SITE DEVELOPMENT PLAN.
a. BUILDING WALLS.
b. FOUNDATIONS.
c. PAVEMENT (CONCRETE, ASPHALT AND BRICK).
d. CONCRETE SLABS.
2. ALL MATERIAL AS A RESULT OF THE GENERAL DEMOLITION SHALL BE THE PROPERTY OF
THE CONTRACTOR, THE CONTRACTOR'S LUMP SUM BID PRICE FOR THE DEMOLITION SHALL
TAKE INTO ACCOUNT THE SALVAGEABLE VALUE OF MATERIALS AND SAID BID PRICE SHALL
REFLECT SAID SAVINGS.
3. THE CONTRACTOR SHALL BE REQUIRED TO DEMOLISH AND REMOVE DESIGNATED
FOUNDATION WALLS, RETAINING WALLS, CURBING, CONCRETE SLABS, PAVING, TANKS,
STRUCTURES, PIPES, MANHOLES AS SHOWN ON THE CONTRACT DOCUMENTS. ALL EXISTING
BASEMENT FLOOR SLABS THAT ARE NOT REMOVED SHALL BE BROKEN UP SUFFICIENTLY TO
PERMIT DRAINAGE THROUGH THE SLAB. ALL EXISTING BASEMENT WALLS, FOUNDATIONS,
FLOOR SLABS, AND ETC. SHALL BE REMOVED TO AN ELEVATION SUCH THAT THEY WILL NOT
SUPPORT PROPOSED FLOOR SLABS OR PAVEMENTS.
4. THE CONTRACTOR SHALL OBTAIN FROM THE CITY OF CARMEL, AND ALL OTHER APPLICABLE
GOVERNMENTAL AUTHORITIES, NECESSARY PERMITS REQUIRED, A COPY OF SUCH PERMITS TO
BE FURNISHED TO THE OWNER PRIOR TO COMMENCEMENT OF ANY WORK REQUIRED HEREIN.
THE CONTRACTOR SHALL FURTHER FURNISH TO THE OWNER PROOF THAT HE HAS COMPLIED
WITH THE PROVISIONS OF THE MUNICIPAL CODE OF INDIANAPOLIS, INDIANA.
UTILITIES
1. ALL WATER LINES FROM CITY OF CARMEL WATER COMPANY MAIN TO ANY LOT SHALL BE
INSTALLED OF MATERIAL AND WORKMANSHIP AS APPROVED WITH THE CITY OF CARMEL WATER
COMPANY.
2. CONDUIT SHALL BE REQUIRED FOR ALL ELECTRICAL AND TELEPHONE LINES UNDER PAVED
AREAS.
3. COMPACTED GRANULAR BACKFILL SHALL BE REQUIRED FOR ALL CROSSINGS OF PAVED
AREAS PER CITY OF CARMEL DEPARTMENT OF TRANSPORTATION SPECIFICATIONS.
SANITARY SEWER SPECIFICATIONS
1. STANDARDS SPECIFICATIONS OF CITY OF CITY OF CARMEL UTILITIES, INDIANA DEPARTMENT OF
TRANSPORTATION AND INDIANA DEPARTMENT OF ENVIRONMENTAL MANAGEMENT SHALL APPLY
FOR ALL WORK AND MATERIALS. PIPE SHALL BE INSTALLED IN WITH INDOT SECTION 715,
ASTM AND MANUFACTURER SPECIFICATIONS.
2. SANITARY SEWER PIPE SHALL BE PVC TYPE 1, CONFORMING TO ASTM D -3034 OR PVC IN
ACCORDANCE WITH ASTM D -3034 (S.D.R. 35) AND ASTM 2321. JOINTS FOR P.V.C. SHALL
BE COMPRESSION TYPE FLEXIBLE GASKETED JOINTS.
3. ALL SANITARY SEWER MANHOLES SHALL BE "PRECAST CONCRETE" MANHOLES IN
ACCORDANCE WITH ASTM C -478 AND 720. MANHOLE SECTIONS SHALL HAVE KENT SEAL
AND "0" RING TYPE GASKETS WHICH SHALL CONFORM TO ASTM D -443. BACK PLASTERING
OF ADJUSTING RINGS IS REQUIRED.
4. THE TYPE OF NEW MANHOLE CASTING AND COVER SHALL BE NEENAH R- 1712 -B -SP.
5. THE CASTING ELEVATIONS ARE SET BY PLAN. HOWEVER, THE CASTINGS ARE TO BE
ADJUSTED IN THE FIELD BY THE ENGINEER OR HIS REPRESENTATIVE SHOULD A
DISCREPANCY OCCUR BETWEEN PLAN GRADE AND EXISTING GRADE.
6. NEW MANHOLE RING AND COVER SHALL BE INSTALLED TO ESTABLISHED GRADE.
7. BACKFILL AROUND ALL STRUCTURES AND ALL CUTS UNDER PAVED AREAS WITH
COMPACTED GRANULAR MATERIAL. TRENCH OPENINGS WITHIN 5 FEET OF PAVED
ROADWAYS SHALL BE BACKFILLED WITH COMPACTED GRANULAR MATERIAL IN
ACCORDANCE WITH INDOT SECTION 211.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THAT ALL STATE HIGHWAYS, CITY
AND COUNTY PERMITS HAVE BEEN OBTAINED BY OWNER PRIOR TO START OF CONSTRUCTION.
9. THE CONTRACTOR SHALL BE REQUIRED TO FURNISH THE ENGINEER WITH A SET OF
PRINTS, MARKED IN RED PENCIL, SHOWING ACTUAL SEWER LOCATIONS AND INVERTS TO
INCLUDE LATERAL LOCATIONS, DEPTH AND LENGTHS. SUCH "AS- BUILT" PRINTS MUST BE
RECEIVED BY THE ENGINEER BEFORE THE FINAL CONTRACT PAYMENT CAN BE
AUTHORIZED. THE SANITARY SEWER LATERAL AND STUB TERMINATIONS SHALL BE
INDICATED BY A MAGNETIC TAPE LOCATOR PLACED AT THE END OF EACH LATERAL.
10.ALL SANITARY SEWER LINES UPON COMPLETION WILL BE REQUIRED TO PASS A LOW
PRESSURE AIR TEST, UNLESS OTHERWISE DIRECTED BY ENGINEER. SAID TEST SHALL BE
CONDUCTED ACCORDING TO TEN STATES STANDARDS, INDIANA DEPARTMENT OF
ENVIRONMENTAL MANAGEMENT. AND CITY OF CARMEL DEPARTMENT OF PUBLIC WORKS AND
SHALL BE WITNESSED BY AN ENGINEER. INFILTRATION UNDER TEST SHALL NOT EXCEED 100
GALLONS PER INCH OF INSIDE DIAMETER OF SEWER PIPE PER MILE OF SEWER IN 24 HOURS
AND INCLUSIVE OF ALL APPURTANCES WITHIN THE SECTION BEING TESTED SUCH AS
MANHOLES, HOUSE CONNECTIONS, ETC.
11.DEFLECTION TESTS SHALL BE PERFORMED ON ALL *FLEXIBLE PIPE AFTER THE FINAL
BACKFILL HAS BEEN IN PLACE AT LEAST 30 DAYS. NO PIPE SHALL EXCEED A VERTICAL
DEFLECTION OF 5% ( *THE FOLLOWING ARE CONSIDERED NON- FLEXIBLE PIPES: CONCRETE PIPE,
DUCTILE IRON PIPE, CAST IRON PIPE AND ASBESTOS CEMENT PIPE).
12. ALL TESTING SHALL BE CERTIFIED BY A PROFESSIONAL ENGINEER.
13,THE ENDS OF LATERALS ARE TO BE PLUGGED TIGHT WITH CLAY OR PLASTIC DISC OR CAP
CAPABLE OF WITHSTANDING A LOW PRESSURE AIR TEST WITHOUT LEAKAGE.
14.CLASS I BEDDING AS DESCRIBED IN ASTM -2321 SHALL BE USED, EXCEPT WHERE
SPECIFIED OTHERWISE.
15. WATER AND SEWER LINE CROSSINGS AND SEPARATIONS SHALL BE IN ACCORDANCE WITH TEN
STATES STANDARDS AS SHOWN ON THE DETAIL SHEET.
16. TRENCH SHALL BE OPENED SUFFICIENTLY AHEAD OF PIPE LAYING TO REVEAL
OBSTRUCTIONS, AND SHALL BE PROPERLY PROTECTED AND /OR BARRICADED WHEN LEFT
UNATTENDED.
17,ALTERNATE PRESSURE PIPE MATERIAL SHALL BE POLYVINYL CHLORIDE PLASTIC PIPE WITH A
STANDARD DIMENSION RATIO OF SDR 21 OR AWWA C -900 WITH A SDR OF 21(CLASS 20D)
AND BE DESIGNED FOR A RATED WORKING PRESSURE OF 200 PSI WATER PRESSURE. ALL
PLASTIC WATER MAINS SHALL BE COLORED BLUE. PLASTIC PIPE SHALL BE SUITABLE FOR
USE AT THE MAXIMUM HYDROSTATIC WORKING PRESSURE IDENTIFIED ABOVE, AT 73 DEGREES
F. ALL PIPE SHALL MEET THE REQUIREMENTS AS SET FORTH IN ASTM D -2241, WITH THE
STANDARD DIMENSION RATIO IDENTIFIED ABOVE AND SHALL BEAR THE NATIONAL SANITATION
FOUNDATION (N.S.F.) SEAL OF APPROVAL FOR POTABLE WATER PIPE. PROVISIONS SHALL BE
MADE FOR EXPANSION AND CONTRACTION AT EACH JOINT WITH A RUBBER RING. AND
INTEGRAL THICKENED BELL AS PART OF EACH JOINT. PIPE AND FITTINGS SHALL BE
ASSEMBLED WITH A NONTOXIC LUBRICANT. STANDARD LAYING LENGTHS SHALL BE 20 FEET
PLUS OR MINUS 1 INCH.
18.SANITARY SEWER CONSTRUCTION WILL NOT BE ALLOWED TO COMMENCE UNTIL A VALID 327
IAC ARTICLE 3 IS OBTAINED (WHEN REQUIRED).
19, THE MINIMUM CELL CLASSIFICATION FOR P.V.C. PIPE SHALL BE 12454 -B OR 12454 -C.
20.THE FLOW CHANNELS FOR THE SANITARY SEWER MANHOLES SHALL BE U- SHAPED WITH THE
THE BENCHWALLS EXTENDING TO THE CROWN OF THE INCOMING AND AND OUTGOING PIPES.
21. MANHOLES LINED IN THEIR ENTIRITY SHALL BE VACCUUM TESTED. ALL PIPES ENTERING
THE MANHOLE SHOULD BE PLUGGED, TAKING CARE TO SECURELY PLACE THE PLUG
FROM BEING DRAWN INTO THE MANHOLE, THE TEST HEAD SHALL BE PLACED AND THE
SEAL INFLATED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.
A VACUUM PUMP OF TEN (10) INCHES OF MERCURY SHALL BE DRAWN AND THE VACUUM
PUMP SHUT OFF. WITH THE VALVES CLOSED, THE TIME SHALL BE MEASURED FOR THE
VACUUM TO DROP TO NINE (9) INCHES. FOLLOWING ARE A MINIMUM ALLOWABLE TEST
TIMES FOR MANHOLE ACCEPTANCE AT THE SPECIFIED VACUUM DROP.
DEPTH (FEET) TIME (SECONDS)
48" DIAMETER 60" DIAMATER 72" DIAMETER
4 10 13 16
8 20 26 33
12 30 39 49
16 40 52 67
20 50 65 81
24 59 78 97
ADD FOR 2 FT. MORE DEPTH 5 6.66
8
NOTE: THESE NUMBERS HAVE BEEN TAKEN FROM ASTM C 1244 -93 (REAPPROVED 2000)
IF THE MANHOLE FAILS IN THE INITIAL TEST, REPAIRS AND ADJUSTMENTS NECESSARY
DUE TO EXTENUATING CIRCUMSTANCES (IE. PIPE JOINT, LINER, PLUG SEALING) SHOULD
BE MADE RETESTING SHALL PROCEED UNTIL A SATISFACTORY TEST IS OBTAINED.
STORM SEWER SPECIFICATIONS
1. STANDARD SPECIFICATIONS OF THE CITY OF CARMEL AND INDIANA DEPARTMENT OF
TRANSPORTATION SHALL APPLY FOR ALL WORK AND MATERIALS. PIPE SHALL BE
INSTALLED IN ACCORDANCE WITH INDOT SECTION 715.
2. ALL REINFORCED CONCRETE STORM SEWER PIPE (RCP) SHALL CONFORM TO ASTM
DESIGNATION C -76 CLASS III. ALL HELICALLY CORRUGATED STEEL PIPE (HCSP) SHALL
CONFORM AASHTO M36, 16 GAUGE IN ACCORDANCE WITH INDOT SECTION 908. ALL HIGH
DENSITY POLEYETHELINE (HDPE) SHALL CONFORM TO AASHTO M294 AND SHALL BE TYPE
S WITH MINIMUM CELL CLASS OF d324420C CONFORMING TO ASTM D 3350, FLEXIBILITY
FACTOR NOT TO EXCEED 0.095 AND ALL JOINTS SHALL BE ASTM D3212 & F477. ALL
POLYVINYL CHLORIDE PIPE (PVC) SHALL CONFORM TO AASHTO M3D4 & MINIMUM CELL
CLASS OF 12454C OR 12364C PER ASTM D1784 AND JOINTS SHALL CONFORM TO ASTM
D3212 AND F447.
1 BACKFILL AROUND ALL STRUCTURES AND CUTS UNDER PAVED AREAS WITH COMPACTED
GRANULAR MATERIAL IN ACCORDANCE WITH INDOT SECTION 21.1 AND 715.
4. SEE STANDARD DETAIL SHEET FOR CONSTRUCTION DIMENSIONS OF STORM STRUCTURES.
MANHOLE, INLETS AND CATCH BASINS SHALL BE IN ACCORDANCE WITH INDOT SECTION
720. PRECAST CONCRETE AND STEEL FOR MANHOLES AND INLETS SHALL BE IN
ACCORDANCE WITH ASTM C -478.
5. STORM SEWER DISCHARGE AREAS AND INVERTS ARE TENTATIVE AND ARE SUBJECT TO
FIELD MODIFICATIONS BY THE ENGINEER OR HIS REPRESENTATIVE. THE CONTRACTOR
WILL BE REIMBURSED FOR ANY ADDITIONAL LABOR AND MATERIALS NECESSARY TO
COMPLETE ANY MODIFICATIONS ACCORDING TO THE UNIT PRICES SUBMITTED BY THE
CONTRACTOR OR THE CONTRACT AMOUNT.
6. THE CONTRACTOR SHALL PROVIDE AT LEAST 2' OF COVER OVER ALL STORM SEWERS,
UNLESS OTHERWISE INDICATED BY PLANS.
7. RIP RAP SHALL BE A MINIMUM OF 1/3 CUBIC FOOT IN SIZE AND A MINIMUM 18" IN
DEPTH, DIMENSIONS FOR RIP RAP IN THESE PLANS ARE FOR ESTIMATING PURPOSES
ONLY, ACTUAL BEST PLACEMENT OF RIP RAP SHALL BE DETERMINED BY FIELD
CONDITIONS AND SHALL BE IN ACCORDANCE WITH INDOT SECTION 616.
8. ALL DRAINAGE PIPE AND DITCH OUTFALLS TO RECEIVING STREAMS SHALL BE
CONSTRUCTED IN ACCORDANCE WITH DRAWINGS, SUBJECT HOWEVER, TO ANY
MODIFICATION REQUIRED BY THE ENGINEER AT THE TIME INSTALLATION IS COMPLETED AND
TO ANY ADJUSTMENTS NEEDED FOR FIELD CONDITIONS NOT ADEQUATELY ANTICIPATED BY
THE DESIGN DRAWING.
CASTINGS SHALL BE AS SHOWN ON DETAIL SHEET FOR MANUFACTURER, TYPE AND
9' NUMBER. ALL CASTINGS SHALL BE NEENAH OR EAST JORDAN APPROVED EQUAL.
3
»^
ap
71 1
:1$
a
1b F,
a
M
A
a
O
m
0
DJ
Ir
CL
w
it
a-
NOTE: THE DEVELOPER/ OWNER AND THE ENGINEER /
FINAL CONSTRUCTION PLANS
NOTE_ PRIOR TO ISSUANCE OF ANY BUILDING PERMITS
9 -16 -08
NOTE. IT 15 THE CONTRACTORS RESPONSIBILITY TO
`,`,`,`ON
SURVEYOR FOR THE DEVELOPER/ OWNER ARE
9 -24 -08
THE BITUMINOUS BASE AND BINDER LAYERS FOR ALL
LL
O Z
COORDINATE WITH PROJECT ENGINEER TO INSURE THE
0
ULTIMATELY RESPONSIBLE TO ENSURE THE PROJECT IS
STREETS, DRIVES AND PARKING LOTS TO BE INSTALLED
H
OQ
`"'
CONTRACTOR HAS THE MOST CURRENT, COMPLETE.
BUILT WITH ALL PLAN COMMISSION CONDITIONS BEING
AND ALL WATER MAINS AND HYDRANTS FOR THE SITE
APPROVED SET OF PLANS AND SPECIFICATIONS FOR THIS
U) /I/111111'11�1�
MET AND ALSO PER CITY / TOWN STANDARDS AND
DEVELOPMENT MUST BE INSTALLED PER APPROVED
PROJECT. ENGINEER DOES NOT ACCEPT RESPONSIBILITY,
SPECIFICATIONS.
SPECIFICATIONS AND MADE SERVICEABLE.
SHOULD CONTRACTOR UTILIZE ANY PLANS THAT DO NOT
MEET THE FORESAID CRITERIA.
SANITARY SEWER SPECIFICATIONS
1. STANDARDS SPECIFICATIONS OF CITY OF CITY OF CARMEL UTILITIES, INDIANA DEPARTMENT OF
TRANSPORTATION AND INDIANA DEPARTMENT OF ENVIRONMENTAL MANAGEMENT SHALL APPLY
FOR ALL WORK AND MATERIALS. PIPE SHALL BE INSTALLED IN WITH INDOT SECTION 715,
ASTM AND MANUFACTURER SPECIFICATIONS.
2. SANITARY SEWER PIPE SHALL BE PVC TYPE 1, CONFORMING TO ASTM D -3034 OR PVC IN
ACCORDANCE WITH ASTM D -3034 (S.D.R. 35) AND ASTM 2321. JOINTS FOR P.V.C. SHALL
BE COMPRESSION TYPE FLEXIBLE GASKETED JOINTS.
3. ALL SANITARY SEWER MANHOLES SHALL BE "PRECAST CONCRETE" MANHOLES IN
ACCORDANCE WITH ASTM C -478 AND 720. MANHOLE SECTIONS SHALL HAVE KENT SEAL
AND "0" RING TYPE GASKETS WHICH SHALL CONFORM TO ASTM D -443. BACK PLASTERING
OF ADJUSTING RINGS IS REQUIRED.
4. THE TYPE OF NEW MANHOLE CASTING AND COVER SHALL BE NEENAH R- 1712 -B -SP.
5. THE CASTING ELEVATIONS ARE SET BY PLAN. HOWEVER, THE CASTINGS ARE TO BE
ADJUSTED IN THE FIELD BY THE ENGINEER OR HIS REPRESENTATIVE SHOULD A
DISCREPANCY OCCUR BETWEEN PLAN GRADE AND EXISTING GRADE.
6. NEW MANHOLE RING AND COVER SHALL BE INSTALLED TO ESTABLISHED GRADE.
7. BACKFILL AROUND ALL STRUCTURES AND ALL CUTS UNDER PAVED AREAS WITH
COMPACTED GRANULAR MATERIAL. TRENCH OPENINGS WITHIN 5 FEET OF PAVED
ROADWAYS SHALL BE BACKFILLED WITH COMPACTED GRANULAR MATERIAL IN
ACCORDANCE WITH INDOT SECTION 211.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THAT ALL STATE HIGHWAYS, CITY
AND COUNTY PERMITS HAVE BEEN OBTAINED BY OWNER PRIOR TO START OF CONSTRUCTION.
9. THE CONTRACTOR SHALL BE REQUIRED TO FURNISH THE ENGINEER WITH A SET OF
PRINTS, MARKED IN RED PENCIL, SHOWING ACTUAL SEWER LOCATIONS AND INVERTS TO
INCLUDE LATERAL LOCATIONS, DEPTH AND LENGTHS. SUCH "AS- BUILT" PRINTS MUST BE
RECEIVED BY THE ENGINEER BEFORE THE FINAL CONTRACT PAYMENT CAN BE
AUTHORIZED. THE SANITARY SEWER LATERAL AND STUB TERMINATIONS SHALL BE
INDICATED BY A MAGNETIC TAPE LOCATOR PLACED AT THE END OF EACH LATERAL.
10.ALL SANITARY SEWER LINES UPON COMPLETION WILL BE REQUIRED TO PASS A LOW
PRESSURE AIR TEST, UNLESS OTHERWISE DIRECTED BY ENGINEER. SAID TEST SHALL BE
CONDUCTED ACCORDING TO TEN STATES STANDARDS, INDIANA DEPARTMENT OF
ENVIRONMENTAL MANAGEMENT. AND CITY OF CARMEL DEPARTMENT OF PUBLIC WORKS AND
SHALL BE WITNESSED BY AN ENGINEER. INFILTRATION UNDER TEST SHALL NOT EXCEED 100
GALLONS PER INCH OF INSIDE DIAMETER OF SEWER PIPE PER MILE OF SEWER IN 24 HOURS
AND INCLUSIVE OF ALL APPURTANCES WITHIN THE SECTION BEING TESTED SUCH AS
MANHOLES, HOUSE CONNECTIONS, ETC.
11.DEFLECTION TESTS SHALL BE PERFORMED ON ALL *FLEXIBLE PIPE AFTER THE FINAL
BACKFILL HAS BEEN IN PLACE AT LEAST 30 DAYS. NO PIPE SHALL EXCEED A VERTICAL
DEFLECTION OF 5% ( *THE FOLLOWING ARE CONSIDERED NON- FLEXIBLE PIPES: CONCRETE PIPE,
DUCTILE IRON PIPE, CAST IRON PIPE AND ASBESTOS CEMENT PIPE).
12. ALL TESTING SHALL BE CERTIFIED BY A PROFESSIONAL ENGINEER.
13,THE ENDS OF LATERALS ARE TO BE PLUGGED TIGHT WITH CLAY OR PLASTIC DISC OR CAP
CAPABLE OF WITHSTANDING A LOW PRESSURE AIR TEST WITHOUT LEAKAGE.
14.CLASS I BEDDING AS DESCRIBED IN ASTM -2321 SHALL BE USED, EXCEPT WHERE
SPECIFIED OTHERWISE.
15. WATER AND SEWER LINE CROSSINGS AND SEPARATIONS SHALL BE IN ACCORDANCE WITH TEN
STATES STANDARDS AS SHOWN ON THE DETAIL SHEET.
16. TRENCH SHALL BE OPENED SUFFICIENTLY AHEAD OF PIPE LAYING TO REVEAL
OBSTRUCTIONS, AND SHALL BE PROPERLY PROTECTED AND /OR BARRICADED WHEN LEFT
UNATTENDED.
17,ALTERNATE PRESSURE PIPE MATERIAL SHALL BE POLYVINYL CHLORIDE PLASTIC PIPE WITH A
STANDARD DIMENSION RATIO OF SDR 21 OR AWWA C -900 WITH A SDR OF 21(CLASS 20D)
AND BE DESIGNED FOR A RATED WORKING PRESSURE OF 200 PSI WATER PRESSURE. ALL
PLASTIC WATER MAINS SHALL BE COLORED BLUE. PLASTIC PIPE SHALL BE SUITABLE FOR
USE AT THE MAXIMUM HYDROSTATIC WORKING PRESSURE IDENTIFIED ABOVE, AT 73 DEGREES
F. ALL PIPE SHALL MEET THE REQUIREMENTS AS SET FORTH IN ASTM D -2241, WITH THE
STANDARD DIMENSION RATIO IDENTIFIED ABOVE AND SHALL BEAR THE NATIONAL SANITATION
FOUNDATION (N.S.F.) SEAL OF APPROVAL FOR POTABLE WATER PIPE. PROVISIONS SHALL BE
MADE FOR EXPANSION AND CONTRACTION AT EACH JOINT WITH A RUBBER RING. AND
INTEGRAL THICKENED BELL AS PART OF EACH JOINT. PIPE AND FITTINGS SHALL BE
ASSEMBLED WITH A NONTOXIC LUBRICANT. STANDARD LAYING LENGTHS SHALL BE 20 FEET
PLUS OR MINUS 1 INCH.
18.SANITARY SEWER CONSTRUCTION WILL NOT BE ALLOWED TO COMMENCE UNTIL A VALID 327
IAC ARTICLE 3 IS OBTAINED (WHEN REQUIRED).
19, THE MINIMUM CELL CLASSIFICATION FOR P.V.C. PIPE SHALL BE 12454 -B OR 12454 -C.
20.THE FLOW CHANNELS FOR THE SANITARY SEWER MANHOLES SHALL BE U- SHAPED WITH THE
THE BENCHWALLS EXTENDING TO THE CROWN OF THE INCOMING AND AND OUTGOING PIPES.
21. MANHOLES LINED IN THEIR ENTIRITY SHALL BE VACCUUM TESTED. ALL PIPES ENTERING
THE MANHOLE SHOULD BE PLUGGED, TAKING CARE TO SECURELY PLACE THE PLUG
FROM BEING DRAWN INTO THE MANHOLE, THE TEST HEAD SHALL BE PLACED AND THE
SEAL INFLATED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS.
A VACUUM PUMP OF TEN (10) INCHES OF MERCURY SHALL BE DRAWN AND THE VACUUM
PUMP SHUT OFF. WITH THE VALVES CLOSED, THE TIME SHALL BE MEASURED FOR THE
VACUUM TO DROP TO NINE (9) INCHES. FOLLOWING ARE A MINIMUM ALLOWABLE TEST
TIMES FOR MANHOLE ACCEPTANCE AT THE SPECIFIED VACUUM DROP.
DEPTH (FEET) TIME (SECONDS)
48" DIAMETER 60" DIAMATER 72" DIAMETER
4 10 13 16
8 20 26 33
12 30 39 49
16 40 52 67
20 50 65 81
24 59 78 97
ADD FOR 2 FT. MORE DEPTH 5 6.66
8
NOTE: THESE NUMBERS HAVE BEEN TAKEN FROM ASTM C 1244 -93 (REAPPROVED 2000)
IF THE MANHOLE FAILS IN THE INITIAL TEST, REPAIRS AND ADJUSTMENTS NECESSARY
DUE TO EXTENUATING CIRCUMSTANCES (IE. PIPE JOINT, LINER, PLUG SEALING) SHOULD
BE MADE RETESTING SHALL PROCEED UNTIL A SATISFACTORY TEST IS OBTAINED.
STORM SEWER SPECIFICATIONS
1. STANDARD SPECIFICATIONS OF THE CITY OF CARMEL AND INDIANA DEPARTMENT OF
TRANSPORTATION SHALL APPLY FOR ALL WORK AND MATERIALS. PIPE SHALL BE
INSTALLED IN ACCORDANCE WITH INDOT SECTION 715.
2. ALL REINFORCED CONCRETE STORM SEWER PIPE (RCP) SHALL CONFORM TO ASTM
DESIGNATION C -76 CLASS III. ALL HELICALLY CORRUGATED STEEL PIPE (HCSP) SHALL
CONFORM AASHTO M36, 16 GAUGE IN ACCORDANCE WITH INDOT SECTION 908. ALL HIGH
DENSITY POLEYETHELINE (HDPE) SHALL CONFORM TO AASHTO M294 AND SHALL BE TYPE
S WITH MINIMUM CELL CLASS OF d324420C CONFORMING TO ASTM D 3350, FLEXIBILITY
FACTOR NOT TO EXCEED 0.095 AND ALL JOINTS SHALL BE ASTM D3212 & F477. ALL
POLYVINYL CHLORIDE PIPE (PVC) SHALL CONFORM TO AASHTO M3D4 & MINIMUM CELL
CLASS OF 12454C OR 12364C PER ASTM D1784 AND JOINTS SHALL CONFORM TO ASTM
D3212 AND F447.
1 BACKFILL AROUND ALL STRUCTURES AND CUTS UNDER PAVED AREAS WITH COMPACTED
GRANULAR MATERIAL IN ACCORDANCE WITH INDOT SECTION 21.1 AND 715.
4. SEE STANDARD DETAIL SHEET FOR CONSTRUCTION DIMENSIONS OF STORM STRUCTURES.
MANHOLE, INLETS AND CATCH BASINS SHALL BE IN ACCORDANCE WITH INDOT SECTION
720. PRECAST CONCRETE AND STEEL FOR MANHOLES AND INLETS SHALL BE IN
ACCORDANCE WITH ASTM C -478.
5. STORM SEWER DISCHARGE AREAS AND INVERTS ARE TENTATIVE AND ARE SUBJECT TO
FIELD MODIFICATIONS BY THE ENGINEER OR HIS REPRESENTATIVE. THE CONTRACTOR
WILL BE REIMBURSED FOR ANY ADDITIONAL LABOR AND MATERIALS NECESSARY TO
COMPLETE ANY MODIFICATIONS ACCORDING TO THE UNIT PRICES SUBMITTED BY THE
CONTRACTOR OR THE CONTRACT AMOUNT.
6. THE CONTRACTOR SHALL PROVIDE AT LEAST 2' OF COVER OVER ALL STORM SEWERS,
UNLESS OTHERWISE INDICATED BY PLANS.
7. RIP RAP SHALL BE A MINIMUM OF 1/3 CUBIC FOOT IN SIZE AND A MINIMUM 18" IN
DEPTH, DIMENSIONS FOR RIP RAP IN THESE PLANS ARE FOR ESTIMATING PURPOSES
ONLY, ACTUAL BEST PLACEMENT OF RIP RAP SHALL BE DETERMINED BY FIELD
CONDITIONS AND SHALL BE IN ACCORDANCE WITH INDOT SECTION 616.
8. ALL DRAINAGE PIPE AND DITCH OUTFALLS TO RECEIVING STREAMS SHALL BE
CONSTRUCTED IN ACCORDANCE WITH DRAWINGS, SUBJECT HOWEVER, TO ANY
MODIFICATION REQUIRED BY THE ENGINEER AT THE TIME INSTALLATION IS COMPLETED AND
TO ANY ADJUSTMENTS NEEDED FOR FIELD CONDITIONS NOT ADEQUATELY ANTICIPATED BY
THE DESIGN DRAWING.
CASTINGS SHALL BE AS SHOWN ON DETAIL SHEET FOR MANUFACTURER, TYPE AND
9' NUMBER. ALL CASTINGS SHALL BE NEENAH OR EAST JORDAN APPROVED EQUAL.
3
»^
ap
71 1
:1$
a
1b F,
a
M
A
a
O
m
0
DJ
Ir
CL
w
it
a-
DATE DESCRIPTION
►110111►,,,/,'',''''
FINAL CONSTRUCTION PLANS
9 -16 -08
CITY REVIEW
`,`,`,`ON
9 -24 -08
CITY REVIEW
LL
O Z
0
0
=a �N
DO i�•S�
H
OQ
`"'
U) /I/111111'11�1�
DATE DESCRIPTION
CLIENT NAME:
WOLFSON YOUNG CORPORATION
MR. RICHARD YOUNG
9510 -1 ROSS LANE
INDIANAPOLIS, INDLANA46268
(317) 876 -2300
(317) 876 -2313
© 2005 DeBoy Land Development Services, Inc.
DESIGNED: BAW APPROVED: CRP
DRAWN: CLH / RCB CHECKED BY: MIS
SCALE: NITS DATE: 06 -30 -06
PROJECT NO.: 2006 -0065
c9ml
OF 19
PRO,.FCT: F: \2006 \2006 -0065 - 11505 N. Penn - Wolfson Young \ENGINEERING \DRAWNGS
DWG C9A SITE SPECRCATIONS.dwg
PLOTTED Or R.C. BERGER
DATE. Mondeyr, October 06, 2008 9:40:23 AM
7
9 -5 -08
FINAL CONSTRUCTION PLANS
9 -16 -08
CITY REVIEW
9 -24 -08
CITY REVIEW
10 -06 -08
CITY REVIEW
W
U_
U.
L
z
O
w
J
U/
z
z
Q
U
O
O
w
W
It
~
U
V /
Q
W
z
LL
LL
>
U
O
�
w
z
CL
W
U)
0
TL
W
O
ix
I-
O
z
rn
0
zr
Lin
z
W
CLIENT NAME:
WOLFSON YOUNG CORPORATION
MR. RICHARD YOUNG
9510 -1 ROSS LANE
INDIANAPOLIS, INDLANA46268
(317) 876 -2300
(317) 876 -2313
© 2005 DeBoy Land Development Services, Inc.
DESIGNED: BAW APPROVED: CRP
DRAWN: CLH / RCB CHECKED BY: MIS
SCALE: NITS DATE: 06 -30 -06
PROJECT NO.: 2006 -0065
c9ml
OF 19
PRO,.FCT: F: \2006 \2006 -0065 - 11505 N. Penn - Wolfson Young \ENGINEERING \DRAWNGS
DWG C9A SITE SPECRCATIONS.dwg
PLOTTED Or R.C. BERGER
DATE. Mondeyr, October 06, 2008 9:40:23 AM
7