MECHANICAL DETAIL NOTES:
1O ROUTE 16x8 DUCT DROP DOWN IN SOFFITT TO WALL SUPPLY SUPPLY GRILLE.
- -- COORDINATE WITH ARCHITECTURAL DRAWINGS AND EXISTING CONDITIONS.
i1
1 FIRST FLOOR MECHANICAL PLAN P.,.
SCALE: 1/4"= 1 9_099
MAKEUP AIR UNIT
ALTERNATE LAYERS OF RIGID TYPE, ROOF
INSULATION AND 5/8" SHEET ROCK
(FILL ENTIRE CURB SPACE)
PREFABRICATED ROOF CURB
FASTEN SECURELY TO ROOF
PATCH AND INSTALL ROOFING MATERIAL
TO MATCH ROOFING AND MAKE WEATHERTIGHT
ROOF INSULATION
.
t
r t
ROOF - -- --...----------
CAULK OPENING AROUND SUPPLY AND
RETURN DUCTS
2 ROOF CURB
NO SCALE
Imo:
GAS FIRED
ROOFTOP
UNIT
EQUIPMENT
CURB
R(
IVIIIYIIVIVIVI J 11UVYL 1 \VVI
INSTALL
PIPE
REDUCER FROM
BRANCH
PIPE SIZE
TO UNIT
CONNECTION
SIZE AT
UNIT
CONNECTION STUB
ONLY
ELECTRICAL
GROUND
JOINT PIPE
UNION
ESP
PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST AS REQUIRED.
VERIFY CONNECTION LOCATIONS BEFORE INSTALLING PIPE RUNS.
REFER TO SPECIFICATIONS FOR MORE INFORMATION.
MAKE -UP
NOT TO SCALE
IR UNIT CO
GAS COCK
BRANCH PIPE: SEE
PLAN FOR SIZE
BRANCH OFF TOP
TOP OF GAS PIPE
SUPPORT PIPING ON
ROOF PER
SPECIFICATIONS
O2 INSTALL CARBON MONOXIDE SENSOR, KELE KCO SERIES OR PRE - APPROVED EQUAL,
AT MINIMUM 2' -0" AFF AND MAXIMUM 4' -0" AFF. COORDINATE EXACT LOCATION
WITH ARCHITECT. CARBON MONOXIDE SENSER SHALL BE PROGRAMMED TO
DISCONNECT POWER TO PATIO HEATERS WHEN CO LEVELS EXCEED 100 PPM.
O3 VERIFY OUTSIDE AIR INTAKE IS MINIMUM 10' -0" AWAY FROM ANY EXHAUST OR
VENT DISCHARGE ON ROOF.
® ROUTE 1 -1/2" NATURAL GAS TO NEAREST 2 -1/2" GAS LINE AND CONNECT. FIELD
VERIFY EXACT SIZE AND LOCATION.
GENERAL NEW NOTES:
1. PRIOR TO SUBMITTING BID, VISIT THE JOB SITE AND BECOME FULLY ACQUAINTED
WITH THE EXISTING CONDITIONS OF THE PROJECT. REVIEW THE GENERAL NOTES,
SPECIFICATIONS AND OTHER DRAWINGS FOR ADDITIONAL REQUIREMENTS WHICH MAY
NOT BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE CONSTRUCTION
DOCUMENTS. NOTIFY ARCHITECT, ENGINEER AND /OR OWNER OF CONFLICTS OR
DISCREPANCIES PRIOR TO SUBMISSION OF BID.
2. EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL DRAWINGS AND SITE VISITS AND
MAY NOT REFLECT EXACT "AS- BUILT" CONDITIONS. FIELD VERIFY EXISTING
CONDITIONS PRIOR TO SUBMITTING FINAL BIDS. COORDINATE NEW WORK AND
DEMOLITION WITH OTHER DISCIPLINES AND EXISTING CONDITIONS PRIOR TO
CONSTRUCTION.
3. COORDINATE THE INSTALLATION OF THE MECHANICAL SYSTEMS WITH OTHER TRADES
TA
TO ENSURE A NEAT AND ORDERLY INSTALLATION. COORDINATE INSTALLATION OF
DUCTWORK TO AVOID CONFLICTS WITH ELECTRICAL PANELS, LIGHTING FIXTURES,
ETC.
4. AVOID DAMAGING EXISTING SURFACES AND EQUIPMENT TO REMAIN FOR NEW
INSTALLATION DURING WORK. REPAIR DAMAGE CAUSED DURING CONSTRUCTION AT
NO EXTRA COST TO THE OWNER.
5. ALL MECHANICAL EQUIPMENT SHOWN ON THE MECHANICAL PLANS SHALL BE
PROVIDED BY THE MECHANICAL CONTRACTOR UNLESS OTHERWISE NOTED.
6. NEW MECHANICAL EQUIPMENT AND DUCTWORK ARE SHOWN AT APPROXIMATE
LOCATIONS. FIELD MEASURE FINAL DUCTWORK LOCATIONS PRIOR TO FABRICATION
AND MAKE ADJUSTMENTS AS REQUIRED TO FIT THE DUCTWORK WITHIN THE
AVAILABLE SPACE. VERIFY THAT FINAL EQUIPMENT LOCATIONS MEET
MANUFACTURER'S RECOMMENDATIONS REGARDING SERVICE CLEARANCE AND
PROPER AIRFLOW CLEARANCE AROUND EQUIPMENT.
7. REFER TO ARCHITECTURAL DRAWINGS FOR RELATED CONSTRUCTION DETAILS AS
APPLICABLE TO THE HVAC SYSTEM. VERIFY CHASES AND PENETRATIONS SHOWN ON
ARCHITECTURAL DRAWINGS THAT ARE INTENDED FOR DUCTWORK MEET
REQUIREMENTS.
8. COORDINATE LOCATION OF ROOF MOUNTED HVAC EQUIPMENT AND ROOF
PENETRATIONS WITH THE ARCHITECTURAL AND STRUCTURAL DRAWINGS.
9. INSTALL DUCTWORK PARALLEL TO BUILDING COLUMN LINES UNLESS OTHERWISE
SHOWN OR NOTED.
10. OVERHEAD HANGERS AND SUPPORTS FOR EQUIPMENT AND DUCTWORK SHALL BE
FASTENED TO BUILDING JOISTS OR BEAMS. DO NOT ATTACH HANGERS AND
SUPPORTS TO THE ABOVE FLOOR SLAB OR ROOF.
11. SEAL PENETRATIONS THROUGH THE BUILDING COMPONENTS IN ACCORDANCE WITH
THE CONTRACT SPECIFICATIONS. FIREPROOF PENETRATIONS THROUGH FIRE RATED
COMPONENTS IN ACCORDANCE WITH U.L. REQUIREMENTS.
12. COORDINATE THE EXACT MOUNTING SIZE AND FRAME TYPE OF DIFFUSERS, REGISTERS
AND GRILLES WITH THE SUPPLIER TO MEET THE CEILING, WALL AND DUCT
INSTALLATION REQUIREMENTS.
13. ADJUST LOCATION OF CEILING DIFFUSERS, REGISTERS AND GRILLES AS REQUIRED TO
ACCOMMODATE FINAL CEILING GRID AND LIGHTING LOCATIONS.
14. DUCTWORK CROSSING FIRE RATED WALLS OR OTHER FIRE RATED ASSEMBLIES SHALL
BE MINIMUM 26 GAUGE SHEET METAL.
15. LOCATE AND SET THERMOSTATS AND CO SENSORS FOR WIRING UNDER DIVISION 15
AND IN CONDUIT UNDER DIVISION 16. VERIFY EXACT LOCATIONS WITH ARCHITECT
PRIOR TO INSTALLATION. INSTALL DEVICES 48" AFF TO MEET ADA REQUIREMENTS
UNLESS NOTED OTHERWISE ON PLANS. PROVIDE INSULATED BACKING FOR
THERMOSTATS MOUNTED ON EXTERIOR BUILDING WALLS.
16. COORDINATE THE LOCATION AND ELEVATION OF WALL - MOUNTED DEVICES WITH
PRESENTATION BOARDS, DISPLAY CABINETS, SHELVES OR OTHER COMPONENTS
SHOWN ON THE ARCHITECTURAL DRAWINGS THAT ARE TO BE INSTALLED UNDER
OTHER DIVISIONS. CONTRACTOR WILL NOT BE REIMBURSED FOR RELOCATION OF
WALL - MOUNTED DEVICES CAUSED BY A LACK OF COORDINATION.
17. PROVIDE A MANUAL BALANCING DAMPER IN EACH BRANCH DUCT TAKEOFF FROM
MAIN SUPPLY, RETURN, OUTDOOR AND EXHAUST AIR DUCTS.
18. PROVIDE A PREFABRICATED 45 DEGREE, HIGH EFFICIENCY, RECTANGULAR /ROUND
BRANCH DUCT TAKEOFF FITTING WITH MANUAL BALANCING DAMPER AND LOCKING
QUADRANT FOR BRANCH DUCT CONNECTIONS AND TAKE -OFFS TO INDIVIDUAL
DIFFUSERS, REGISTERS AND GRILLES.
19. BRANCH DUCTWORK TO AIR OUTLETS SHALL BE SAME SIZE AS OUTLET NECK SIZE
UNLESS OTHERWISE NOTED.
20. RIGID DUCTWORK INSULATION: FURNISH AND INSTALL 1" THICK, 3 LB DENSITY
INTERNAL DUCT LINER ON ROUND AND RECTANGULAR SUPPLY AIR DUCTS. DUCT
SIZES ON MECHANICAL PLANS INDICATE CLEAR INSIDE AIRFLOW DIMENSIONS,
INCREASE SHEET METAL SIZES ACCORDINGLY.
21. PROVIDE THERMAFLEX TYPE G -KM, FLEXMASTER TYPE 8, OR APPROVED EQUAL
FLEXIBLE DUCTWORK. FLEXIBLE DUCTWORK SHALL BE LISTED UNDER UL 181 AS
CLASS 1 AIR DUCT AND BE PROVIDED WITH INTEGRAL 1 -1/2" THICK, 3/4 LB DENSITY
FIBERGLASS INSULATION. FLEXIBLE DUCTWORK SHALL NOT EXCEED 5' -0" IN LENGTH
AND SHALL BE INSTALLED AND SUPPORTED TO AVOID SHARP BENDS AND SAGGING.
22. PROVIDE WALL MOUNTED LOUVERS AND DAMPERS WITH SUITABLE MOUNTING FRAME
TO MATCH WALL CONSTRUCTION. COORDINATE WITH ARCHITECTURAL DRAWINGS.
23. PROVIDE A NEW SET OF AIR FILTERS IN UNITS JUST BEFORE TURNING SYSTEM(S) OVER
TO OWNER.
24. INDOOR AIR QUALITY MEASURES: PROTECT INSIDE OF (INSTALLED AND DELIVERED)
DUCTWORK AND HVAC UNITS FROM EXPOSURE TO DUST, DIRT, PAINT AND
MOISTURE. REPLACE INSULATION THAT HAS GOTTEN WET AT ANY TIME DURING
CONSTRUCTION, DRYING THE INSULATION IS NOT ACCEPTABLE. SEAL ANY TEARS OR
JOINTS OF INTERNAL FIBERGLASS INSULATION. REMOVE DEBRIS FROM
CEILING /RETURN AIR PLENUM INCLUDING DUST. AN INDEPENDENT, PROFESSIONAL
DUCT CLEANING COMPANY SHALL VACUUM CLEAN ANY DUCTWORK CONNECTED TO
HVAC UNITS THAT WERE OPERATED DURING THE CONSTRUCTION PERIOD AFTER NEW
FILTERS ARE INSTALLED AND PRIOR TO TURNING SYSTEM OVER TO THE OWNER.
NATURAL GAS OR
CONDENSATE DRAIN
PIPE. REFER TO
DRAWINGS FOR PIPE
SIZE(S) AND PROVIDE
APPROPRIATE BLOCK
AND CLAMP,
RECOMMENDED BY
MANUFACTURER
6" HIGH UV- RESISTANT
POLYETHYLENE FOAM
BLOCK WITH INTEGRAL
STRUT CHANNEL,
ERICO "PIPE PIER"
PROVIDE 24 "x24"
BASE SHEET OF ROOF
WALKWAY MATERIAL,
SET ON BARE
ROOFING MEMBRANE,
NOT ON AGGREGATE -
LOCATE SUPPORTS AT 4' SPACING FOR PLASTIC PIPE AND AT THE FOLLOWING
SPACING FOR METAL PIPE: 5 " =16' 4 " =14' 3 " =12' 2- 1/2 " =11' 2 " =10'
1-1/2"=9' 1-1/4"=8' 1"=7' 3/4 " =6'. PLACE A SUPPORT AS CLOSE AS POSSIBLE
TO EACH ELBOW AND TEE. PLACE BASE SHEETS ON ROOFING BEFORE GRAVEL IF
ANY. SET BLOCKS FREE ON BASE SHEETS. STACK BLOCKS AND NAIL THEM
TOGETHER WHERE REQUIRED TO ELEVATE PIPING. INSTALL PIPE TO ALLOW FOR
EXPANSION AND CONTRACTION.
NOT TO SCALE
)N ROOF
LOUVER SCHEDULE
ROOFTOP MAKEUP AIR UNIT SCHEDULE
(NATURAL GAS HEAT)
MARK
MANUFACTURER
MODEL
UNIT
SUPPLY FAN
FACE
HEAIING COIL
ELECTRICAL
NOTES
FAN
CFM
ESP
MIN.
MAX. INPUT
MIN. OUTPUT
MIN. EFF.
GAS VALVE
V PH
TYPE
LOCATION
0.05
IN
L -2
TYPE
RUSKIN
DROP IN. W.C.
66x12
1200
SD -1
TITUS
TYPE
LOUVERED
I IN
I HP
MBH )
(MBH)
%
TYPE
0.1
TYPE
TYPE
WSR -1
TITUS
MAU -1
CAPTIVE -AIRE
A1- D.250 -G10
DIRECT
FC
1,8001
1
1 1.5
275
135
80
MODULATING
480/3
NF
MAG.
A - K
NOTES:
A.
PROVIDE 1" ALUMINUM MESH AIR FILTERS.
B.
PROVIDE MANUFACTURER'S STANDARD INSULATED ROOF CURB WITH MINIMUM HEIGHT
OF 20 ".
C.
PROVIDE WITH DISCHARGE DUCT SENSOR TO MAINTAIN MINIMUM 60 DEGREES WITH
STAGED HEATING CAPABILIITY
AS
REQUIRED FOR OPERATION OF HEATING CONTROLS.
E.
D.
SPECIFIED FAN ESP DOES NOT INCLUDE LOSSES FOR DIRTY FILTERS.
E.
DIVISION 16 CONTRACTOR TO FURNISH AND INSTALL SMOKE DETECTORS IN THE
SUPPLY AIR DUCT WITH TEST SWITCH AND INDICATING LIGHT.
F.
PROVIDE WITH STAINLESS STEEL HEAT EXCHANGER.
G.
PROVIDE ALL ALUMINUM CONSTRUCTION.
G.
DESIGN UNIT FOR NATURAL GAS AT A GAS SUPPLY PRESSURE OF 7 -10" W.C.
H.
H.
PROVIDE FACTORY MOUNTED DISCONNECT SWITCH.
CEILINGS /WALLS.
J.
STARTER FURNISHED BY MANUFACTURER.
DAMAGE TO FINISH
AND ANY NEED FOR
K.
UNIT ELECTRICAL COMPONENTS SHALL BE RATED TO WITHSTAND MINIMUM SHORT CIRCUIT OF NOT LESS THAN THE PANELBOARD SERVING THE EQUIPMENT.
LOUVER SCHEDULE
GRILLE, REGISTER AND DIFFUSER SCHEDULE
MARK
MANUFACTURER
MODEL
FACE
MOUNTING
CFM
FACE SIZE
MAX. VEL.
FPM
MAX.
NOTES
MAX. PRESS.
NOTES
RUSKIN
ELF6375DX
36x12
600
TYPE
LOCATION
0.05
IN
L -2
NC
RUSKIN
DROP IN. W.C.
66x12
1200
SD -1
TITUS
TMS -AA
LOUVERED
CEILING
24x24
30
0.1
A,B,C,D,E,F,G,H,J
WSR -1
TITUS
S300FS
LOUVERED
WALL
SEE P
PLANS
30
0.08
ADHJK
1 1 ,
NOTES:
A.
NECK SIZE SHOWN ON DRAWINGS.
B.
4 -WAY THROW PATTERN UNLESS OTHERWISE SHOWN ON DRAWINGS.
C.
BRANCH DUCT SIZE SHALL BE SAME AS NECK SIZE UNLESS OTHERWISE SHOWN ON DRAWINGS.
D.
PROVIDE NECK FOR DUCT CONNECTION.
E.
FRAME TYPE TO MATCH CEILING CONSTRUCTION, COORDINATE WITH ARCHITECTURAL REFLECTED CEILING
PLAN.
F.
PROVIDE WITH 'TRM' RAPID MOUNT FRAME FOR INSTALLATION IN GYP. BOARD CEILINGS.
G.
PROVIDE ALL ALUMINUM CONSTRUCTION.
H.
PROVIDE FACTORY BAKED ENAMEL COLOR TO MATCH SURROUNDING CEILING OR WALL COLOR IN
HARD /GYP BOARD
CEILINGS /WALLS.
J.
PROTECT AIR DEVICE DURING SHIPMENT, CONSTRUCTION, STORAGE, AND INSTALLATION TO AVOID
DAMAGE TO FINISH
AND ANY NEED FOR
FIELD PAINTING.
K.
PROVIDE WITH OPERABLE DAMPER ADJUSTABLE FROM FACE OF GRILLE.
LOUVER SCHEDULE
MARK
SERVICE
MANUFACTURER
MODEL
SIZE
L" x W"
CFM
MIN. FREE AREA
SF
MAX. VEL.
FPM
MAX. P.D.
IN. W. C.)
NOTES
L -1
RELIEF
RUSKIN
ELF6375DX
36x12
600
1
650
0.05
A -C
L -2
RELIEF
RUSKIN
ELF6375DX
66x12
1200
1.9
650
0.05
A -C
NOTES:
A. PROVIDE 1/4" MESH STAINLESS STEEL BIRD SCREEN.
B. PROVIDE FACTORY ANODIZED FINISH. COLOR TO BE MEDIUM BRONZE AS SELECTED BY ARCHITECT.
C. FRAME TYPE SHALL MATCH WALL CONSTRUCTION, COORDINATE WITH ARCHITECT.
HENDERSON
ENGINEERS
INCORPORATED
8325 LENEXA DRIVE, SUITE 400
LENEXA, KANSAS 6621 4 -1 695
PH 913.307.5300
FX 91 3.307.5400
WWW.HENDERSONENGINEERS.COM
0650001 752.000
Aria
Group
Architects
Inc.
830 North Blvd.
Oak Park, Illinois
60301
708.445.8400
708.445.1788 Fax
z
W
M0
U
U
a_
Cn
D
M
Ld
U
W
g
U
FIELD VERIFICATION
Contractor shall verify all figured dimensions
and conditions at the job site and notify Aria
Group Architects, Inc. of any dimensional
errors, omissions or discrepancies before
beginning or fabricating any work. Do not
scale these drawings.
COPYRIGHT
Aria Group Architects, Inc. shall retain all
common law, statutory and other reserved
rights. These drawings and related
documents shall not be duplicated, disclosed
or otherwise without written consent of Aria
Group Architects, Inc.
:I`�� S
s
60920153
STATE OF
AL
O '• .�tiDfAN* �
Drawing Title
MECHANICAL
PLAN
Job No. Drawn
051241 CA
Scale Date
114" = I' -0" 12/01/06
Sheet No.
M1.1