HomeMy WebLinkAbout13040194gMATCHING WIDTH
CASED EVAPORATOR
COIL PIPED PER
MANUFACTURERS
RECOMMENDATIONS
PROVIDE REFRIGERATION LINES
PER MANUFACTURES
RECOMMENDATIONS
6" FRESH AIR DUCT UP
THROUGH ROOF FLASHING
WITH MOTORIZED DAMPER.
3/4" PVC DRAIN LINE
PROVIDE OPEN SITE DRAIN
CONNECTION TO PROTECT
COMBUSTION BLOWER
INDIRECTION CONNECTION TO
FLOOR DRAIN IN SPKLR ROOM
LINED RETURN AIR DUCT
PROVIDE LINED SHEET METAL
RETURN AIR FURNACE BOX EQUIP MANUFACTURER SUPPLIED
UNDER FURNACES. SET IN
CONCENTRIC ROOF VENT
SECONDARY DRAIN PAN WITH
MOISTURE CUT OFF SWITCH.
RUBBER BOOT DECK FLASHING SPECIFICALLY
PVC VENTING PER III' DESIGN FOR METAL ROOF DECK
MANUFACTURERS u u
RECOMMENDATIONS. VENT UP SEAL WITH POLYURETHANE BASED SEALER,
90% THROUGH ROOF MOUNTED 24" SIKAFLEX -221 OR EQUAL. SILICONE SEALANT
UPFLOW CONCENTRIC VENT TERMINAL IS NOT ACCEPTABLE
FURNACE E.
METAL ROOF
WRAPPED SUPPLY AIR DUCT 1X1 STEEL ANGLE BRACE WITH
MANUFACTURERS CLAMP STAINLESS SCREW CLAMP TO
FURNISHED
18" MIN. SUPPORT VENT.
RUNS BETWEEN JOIST, TYPICAL
FURNACE INSTALLATION DETAIL
SCALE: 1/8" = 1' -0"
LOA
min
FIELD ROUTE PVC VENTING IN STRICT
4 ACCORDANCE WITH EQUIP. MANUF.
RECOMMENDATIONS.
CONCENTRIC VENT DETAIL
SCALE: 1/8" = 1' -0"
UPPER FLOOR - HVAC PLAN
SCALE: 1/8" = 1' -0"
GENERAL NOTES:
1, REFERENCE SHEET M -001 FOR LEGENDS,
ABBREVIATIONS, SPECIFICATIONS AND NOTES.
KEY NOTES:
0 REMOVE EXISTING GAS UNIT HEATER IN ENTIRETY
AND EXTEND EXISTING GAS LINE TO NEW GAS
FURNACE.
PROVIDE AND INSTALL NEW 2 TON AIR COOLED 13
SEER CONDENSING UNIT LIKE CARRIER 24ABB024,
208 1 PHASE. MOUNT UNIT LEVEL ON
MANUFACTURERS PLASTIC CONDENSER PAD.
ROUTE REFRIGERATION LINES INTO SPRINKER
RISER ROOM AND UP TO UNDERSIDE OF ROOF
THEN OVER TO A/C COIL, PROVIDE PVC SLEEVE
AND SEAL WALL PENETRATION WATER TIGHT.
O PROVIDE AND INSTALL NEW UP -FLOW 40 MBH HIGH
EFFICIENCY FURNACE WITH 2 TON CASED COIL LIKE
CARRIER SC2A040. PROVIDE MANUFACTURE
CONCENTRIC ROOF VENT. MOUNT FURNACE IN
DRAIN PAN WITH MOISTURE CUT OFF SWITCH. PIPE
CONDENSATE TO SPRINKLER RISER ROOM FLOOR
DRAIN.
KEY NOTES:
4O PROVIDE AND INSTALL 6" MOTORIZED DAMPER AND
OUTSIDE AIR DUCT. ROUTE DUCT THROUGH ROOF
WITH 6'B-VENT FLUE PIPE, TALL CONE FLASHING,
TOPPER AND STORM COLLAR. SEAL WATER TIGHT,
INTERLOCK DAMPER TO OPEN WHEN FAN IS
RUNNING.
O PROVIDE AND INSTALL RESIDENTIAL STYLE LIKE
HART AND COOLEY CEILING MOUNTED 14 X 6
SUPPLY AIR REGISTERS.
(D PROVIDE AND INSTALL RESIDENTIAL STYLE
RETURN AIR STAMPING LIKE HART AND COOLEY
SIZED AT 24 X 16.
7O PROVIDE AND INSTALL RESIDENTIAL STYLE
RETURN AIR STAMPING LIKE HART AND COOLEY
SIZED AT 12 X 12.
G�.J )DEfdUM & ASSOCIATES
Gooderum & Associates, P.C.
874 Cheltenham Way
Avon, Indiana 46123
Phone: (317) 506 -8181
Fax: (317) 745 -5761
FIRST FLOOR - HVAC PLAN
SCALE: 1/8" = 1' -0"
b 04% 0� _5.a a
zu
z
z
i
s
u- 0 '\^%
bi
"w "A .\,
0 �` JI
u-
Ld
0 Coll
0 ON
a
E
0
Ow 0
IM
uj
?0
0.
D Z
I D - X
� ass X
LL
a
E)W10200395g��
STATE OF
a � �
U
Ell N
u
3 ui
I �
�.a
i
E:
N 12 Y ARCHROTS, 0C.
M100