Loading...
HomeMy WebLinkAbout15670.pdf BICKFORD OF CARMEL, IN 12/12/2012 CONDENSING UNITS 15670-1 SECTION 15670 CONDENSING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work of this section. 1.2 SUBMITTALS: A. Product Data: Submit manufacturer's technical product data, including rated capacities of selected model clearly indicated, weights (shipping, installed, and operating), dimensions, required clearances, and methods of assembly of components, furnished specialties and accessories; and installation and start-up instructions. 1.3 QUALITY ASSURANCE: A. Codes and Standards: 1. Capacity ratings for condensing units shall be in accordance with ARI Standard 360 "Standard for Commercial and Industrial Unitary Air-Conditioning Equipment", and/or ARI Standard 210/240. 2. Refrigeration system of condensing units shall be constructed in accordance with ASHRAE Standard ASHRAE 15 "Safety Code for Mechanical Refrigeration". 3. Condensing units shall be listed by UL and have UL label affixed. All units to include service valves. 1.4 SPECIAL PROJECT WARRANTY: A. Warranty on Motor/Compressor: Provide written warranty, signed by manufacturer, agreeing to replace/repair, within warranty period, motors/compressors with inadequate or defective materials and workmanship, including leakage, breakage, improper assembly, or failure to perform as required; provided manufacturer's instructions for handling, installing, protecting, and maintaining units have been adhered to during warranty period. Replacement is limited to component replacement only, and does not include labor for removal and reinstallation. B. Type of Compressor: Units shall include “Scroll” type compressors, SEER of units shall be per schedule. All cooling coils are to use thermal expansion valves for refrigerant control. C. Warranty Period: 5 years from date of substantial completion. PART 2 - PRODUCTS 2.1 AIR-COOLED CONDENSING UNITS: A. Manufacturers: Subject to compliance with requirements, provide air-cooled condensing units of one of the following: BICKFORD OF CARMEL, IN 12/12/2012 CONDENSING UNITS 15670-2 Bryant Carrier Trane Rheem Lennox (design based on this equipment) B. General: Factory-assembled and tested air-cooled condensing units, consisting of compressor, condenser coil, fan, motor, refrigerant reservoir, and operating controls. Capacity and electrical characteristics are as indicated. All units provided with hail guards, mounting base, low ambient cut-off switch plus an indoor blower-off delay relay. Provide high pressure switch and loss of charge kit. C. Casing: Galvanized steel finished with baked enamel, complete with removable panels for access to controls, weep holes for water drainage, and mounting holes in base. Unit shall be complete with brass service valves, fittings, and gage ports on exterior of casing. D. Compressor: Hermetically sealed, scroll type, with built-in overloads and vibration isolation. Compressor motor, shall have thermal and current sensitive overload devices, internal high-pressure protection, high and low pressure cutout switches, start capacitor and relay, 2-pole contactor, crankcase heater, and temperature actuated switch and timer to prevent compressor rapid cycle. E. Condenser: Coil shall have copper tubes and aluminum fins; complete with liquid accumulator and liquid sub-cooler. Aluminum propeller fan shall be direct driven, with permanently lubricated fan motor having thermal overload protection. PART 3 - EXECUTION 3.1 INSTALLATION: A. General: Install condensing units in accordance with manufacturer’s installation instructions. Install units plumb and level, firmly anchored in locations indicated, and maintain manufacturer's recommended clearances. 3.2 START-UP: A. Start-up of the condensing unit shall be by a factory trained start-up technician. Provide full operating charge of refrigerant as required for proper operation. 3.3 WARRANTY: A. Provide a five (5) year warranty for compressor. 3.4 DEMONSTRATION: A. Test controls for compliance with requirements. Replace damaged or malfunctioning controls and equipment. Demonstrate system operation to the satisfaction of the owner. END OF SECTION