HomeMy WebLinkAbout16050.pdf BICKFORD OF CARMEL, IN 12/12/2012
BASIC ELECTRICAL MATERIALS AND METHODS 16050 - 1
SECTION 16050 - BASIC ELECTRICAL MATERIALS AND METHODS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following:
1. Electrical equipment coordination and installation.
2. Sleeves for raceways and cables.
3. Sleeve seals.
4. Common electrical installation requirements.
1.3 DEFINITIONS
A. ATS: Acceptance Testing Specifications.
B. EPDM: Ethylene-propylene-diene terpolymer rubber.
C. NBR: Acrylonitrile-butadiene rubber.
1.4 SUBMITTALS
A. Product Data: For each type of product indicated.
1.5 QUALITY ASSURANCE
A. Test Equipment Suitability and Calibration: Comply with NETA ATS, "Suitability of Test
Equipment" and "Test Instrument Calibration."
1.6 COORDINATION
A. Coordinate arrangement, mounting, and support of electrical equipment:
1. To allow maximum possible headroom unless specific mounting heights that reduce
headroom are indicated.
2. To provide for ease of disconnecting the equipment with minimum interference to other
installations.
3. To allow right of way for piping and conduit installed at required slope.
BICKFORD OF CARMEL, IN 12/12/2012
BASIC ELECTRICAL MATERIALS AND METHODS 16050 - 2
4. So connecting raceways, cables, wireways, cable trays, and busways will be clear of
obstructions and of the working and access space of other equipment.
B. Coordinate installation of required supporting devices and set sleeves in cast-in-place concrete,
masonry walls, and other structural components as they are constructed.
C. Coordinate location of access panels and doors for electrical items that are behind finished
surfaces or otherwise concealed. Access doors and panels are specified in Section "Access
Doors and Frames."
D. Coordinate electrical testing of electrical, mechanical, and architectural items, so equipment and
systems that are functionally interdependent are tested to demonstrate successful
interoperability.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. In other Part 2 articles where titles below introduce lists, the following requirements apply to
product selection:
1. Available Manufacturers: Subject to compliance with requirements, manufacturers
offering products that may be incorporated into the Work include, but are not limited to,
manufacturers specified.
2. Manufacturers: Subject to compliance with requirements, provide products by one of the
manufacturers specified.
2.2 SLEEVES FOR RACEWAYS AND CABLES
A. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized steel, plain
ends.
B. Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure pipe,
with plain ends and integral waterstop, unless otherwise indicated.
C. Sleeves for Rectangular Openings: Galvanized sheet steel with minimum 0.052- or 0.138-inch
thickness as indicated and of length to suit application.
D. Coordinate sleeve selection and application with selection and application of firestopping
specified in Division 7 Section "Through-Penetration Firestop Systems."
E. Provide a 2” minimum sleeve for each low voltage system.
2.3 SLEEVE SEALS
A. Description: Modular sealing device, designed for field assembly, to fill annular space between
sleeve and raceway or cable.
BICKFORD OF CARMEL, IN 12/12/2012
BASIC ELECTRICAL MATERIALS AND METHODS 16050 - 3
1. Manufacturers:
a. Advance Products & Systems, Inc.
b. Calpico, Inc.
c. Metraflex Co.
d. Pipeline Seal and Insulator, Inc.
2. Sealing Elements: EPDM interlocking links shaped to fit surface of cable or conduit.
Include type and number required for material and size of raceway or cable.
3. Pressure Plates: Plastic. Include two for each sealing element.
4. Connecting Bolts and Nuts: Carbon steel with corrosion-resistant coating of length
required to secure pressure plates to sealing elements. Include one for each sealing
element.
PART 3 - EXECUTION
3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION
A. Comply with NECA 1.
B. Measure indicated mounting heights to bottom of unit for suspended items and to center of unit
for wall-mounting items.
C. Headroom Maintenance: If mounting heights or other location criteria are not indicated,
arrange and install components and equipment to provide maximum possible headroom
consistent with these requirements.
D. Equipment: Install to facilitate service, maintenance, and repair or replacement of components
of both electrical equipment and other nearby installations. Connect in such a way as to
facilitate future disconnecting with minimum interference with other items in the vicinity.
E. Right of Way: Give to raceways and piping systems installed at a required slope.
3.2 SLEEVE INSTALLATION FOR ELECTRICAL PENETRATIONS
A. Electrical penetrations occur when raceways, cables, wireways, cable trays, or busways
penetrate concrete slabs, concrete or masonry walls, or fire-rated floor and wall assemblies.
B. Coordinate sleeve selection and application with selection and application of firestopping
specified in Division 7 Section "Through-Penetration Firestop Systems."
C. Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or formed
openings are used. Install sleeves during erection of slabs and walls.
D. Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.
E. Rectangular Sleeve Minimum Metal Thickness:
BICKFORD OF CARMEL, IN 12/12/2012
BASIC ELECTRICAL MATERIALS AND METHODS 16050 - 4
1. For sleeve cross-section rectangle perimeter less than 50 inches and no side greater than
16 inches, thickness shall be 0.052 inch.
2. For sleeve cross-section rectangle perimeter equal to, or greater than, 50 inches and 1 or
more sides equal to, or greater than, 16 inches, thickness shall be 0.138 inch.
F. Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall assemblies
unless openings compatible with firestop system used are fabricated during construction of floor
or wall.
G. Cut sleeves to length for mounting flush with both surfaces of walls.
H. Extend sleeves installed in floors 2 inches above finished floor level.
I. Size pipe sleeves to provide 1/4-inch annular clear space between sleeve and raceway or cable
unless sleeve seal is to be installed.
J. Seal space outside of sleeves with grout for penetrations of concrete and masonry and with
approved joint compound for gypsum board assemblies.
K. Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between sleeve
and raceway or cable, using joint sealant appropriate for size, depth, and location of joint. Refer
to Section "Joint Sealants" for materials and installation.
L. Fire-Rated-Assembly Penetrations: Maintain indicated fire rating of walls, partitions, ceilings,
and floors at raceway and cable penetrations. Install sleeves and seal raceway and cable
penetration sleeves with firestop materials. Comply with Division 7 Section "Through-
Penetration Firestop Systems."
M. Roof-Penetration Sleeves: Seal penetration of individual raceways and cables with flexible
boot-type flashing units applied in coordination with roofing work.
N. Aboveground, Exterior-Wall Penetrations: Seal penetrations using sleeves and mechanical
sleeve seals. Select sleeve size to allow for 1-inch annular clear space between pipe and sleeve
for installing mechanical sleeve seals.
O. Underground, Exterior-Wall Penetrations: Install cast-iron "wall pipes" for sleeves. Size
sleeves to allow for 1-inch annular clear space between raceway or cable and sleeve for
installing mechanical sleeve seals.
3.3 SLEEVE-SEAL INSTALLATION
A. Install to seal underground, exterior wall penetrations.
B. Use type and number of sealing elements recommended by manufacturer for raceway or cable
material and size. Position raceway or cable in center of sleeve. Assemble mechanical sleeve
seals and install in annular space between raceway or cable and sleeve. Tighten bolts against
pressure plates that cause sealing elements to expand and make watertight seal.
BICKFORD OF CARMEL, IN 12/12/2012
BASIC ELECTRICAL MATERIALS AND METHODS 16050 - 5
3.4 FIRESTOPPING
A. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore
original fire-resistance rating of assembly. Firestopping materials and installation requirements
are specified in Division 7 Section "Through-Penetration Firestop Systems."
3.5 FIELD QUALITY CONTROL
A. Inspect installed sleeve and sleeve-seal installations and associated firestopping for damage and
faulty work.
END OF SECTION 16050