HomeMy WebLinkAbout16910.pdfBICKFORD OF CARMEL, IN 12/12/2012
TRANSFER SWITCHES 263600 - 1
SECTION 16910 - TRANSFER SWITCHES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes transfer switches rated 600 V and less, including the following:
1. Automatic transfer switches.
B. Related Sections include the following:
1. Division 21 for automatic transfer switches for fire pumps.
1.3 SUBMITTALS
A. Product Data: For each type of product indicated. Include rated capacities, weights, operating
characteristics, furnished specialties, and accessories.
B. Shop Drawings: Dimensioned plans, elevations, sections, and details showing minimum
clearances, conductor entry provisions, gutter space, installed features and devices, and material
lists for each switch specified.
C. Operation and Maintenance Data: For each type of product to include in emergency, operation,
and maintenance manuals. In addition to items specified in Division 01 Section "Operation and
Maintenance Data," include the following:
1. Features and operating sequences, both automatic and manual.
2. List of all factory settings of relays; provide relay-setting and calibration instructions,
including software, where applicable.
1.4 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
B. Comply with NEMA ICS 1.
C. Comply with NFPA 70.
BICKFORD OF CARMEL, IN 12/12/2012
TRANSFER SWITCHES 263600 - 2
D. Comply with NFPA 110.
E. Comply with UL 1008 unless requirements of these Specifications are stricter.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the
following:
1. Contactor Transfer Switches:
a. Caterpillar; Engine Div.
b. Emerson; ASCO Power Technologies, LP.
c. Generac Power Systems, Inc.
d. Kohler Power Systems; Generator Division.
e. Onan/Cummins Power Generation; Industrial Business Group.
f. Russelectric, Inc.
g. Spectrum Detroit Diesel.
2.2 GENERAL TRANSFER-SWITCH PRODUCT REQUIREMENTS
A. Indicated Current Ratings: Apply as defined in UL 1008 for continuous loading and total
system transfer, including tungsten filament lamp loads not exceeding 30 percent of switch
ampere rating, unless otherwise indicated.
B. Tested Fault-Current Closing and Withstand Ratings: Adequate for duty imposed by protective
devices at installation locations in Project under the fault conditions indicated, based on testing
according to UL 1008.
C. Solid-State Controls: Repetitive accuracy of all settings shall be plus or minus 2 percent or
better over an operating temperature range of minus 20 to plus 70 deg C.
D. Resistance to Damage by Voltage Transients: Components shall meet or exceed voltage-surge
withstand capability requirements when tested according to IEEE C62.41. Components shall
meet or exceed voltage-impulse withstand test of NEMA ICS 1.
E. Electrical Operation: Accomplish by a nonfused, momentarily energized solenoid or electric-
motor-operated mechanism, mechanically and electrically interlocked in both directions.
F. Switch Characteristics: Designed for continuous-duty repetitive transfer of full-rated current
between active power sources.
1. Limitation: Switches using molded-case switches or circuit breakers or insulated-case
circuit-breaker components are not acceptable.
2. Switch Action: Double throw; mechanically held in both directions.
BICKFORD OF CARMEL, IN 12/12/2012
TRANSFER SWITCHES 263600 - 3
3. Contacts: Silver composition or silver alloy for load-current switching. Conventional
automatic transfer-switch units, rated 225 A and higher, shall have separate arcing
contacts.
G. Neutral Switching. Where four-pole switches are indicated, provide neutral pole switched
simultaneously with phase poles.
H. Factory Wiring: Train and bundle factory wiring and label, consistent with Shop Drawings,
either by color-code or by numbered or lettered wire and cable tape markers at terminations.
Color-coding and wire and cable tape markers are specified in Division 26 Section
"Identification for Electrical Systems."
1. Designated Terminals: Pressure type, suitable for types and sizes of field wiring
indicated.
2. Power-Terminal Arrangement and Field-Wiring Space: Suitable for top, side, or bottom
entrance of feeder conductors as indicated.
3. Control Wiring: Equipped with lugs suitable for connection to terminal strips.
I. Enclosures: General-purpose NEMA 250, Type 1, complying with NEMA ICS 6 and UL 508,
unless otherwise indicated.
2.3 AUTOMATIC TRANSFER SWITCHES
A. Comply with Level 1 equipment according to NFPA 110.
B. Switching Arrangement: Double-throw type, incapable of pauses or intermediate position stops
during normal functioning, unless otherwise indicated.
C. Manual Switch Operation: Unloaded. Control circuit automatically disconnects from electrical
operator during manual operation.
D. Signal-Before-Transfer Contacts: A set of normally open/normally closed dry contacts operates
in advance of retransfer to normal source. Interval is adjustable from 1 to 30 seconds.
E. Automatic Closed-Transition Transfer Switches: Include the following functions and
characteristics:
1. Fully automatic make-before-break operation.
2. Load transfer without interruption, through momentary interconnection of both power
sources not exceeding 100 ms.
3. Initiation of No-Interruption Transfer: Controlled by in-phase monitor and sensors
confirming both sources are present and acceptable.
a. Initiation occurs without active control of generator.
b. Controls ensure that closed-transition load transfer closure occurs only when the 2
sources are within plus or minus 5 electrical degrees maximum, and plus or minus
5 percent maximum voltage difference.
4. Failure of power source serving load initiates automatic break-before-make transfer.
BICKFORD OF CARMEL, IN 12/12/2012
TRANSFER SWITCHES 263600 - 4
F. In-Phase Monitor: Factory-wired, internal relay controls transfer so it occurs only when the two
sources are synchronized in phase. Relay compares phase relationship and frequency difference
between normal and emergency sources and initiates transfer when both sources are within 15
electrical degrees, and only if transfer can be completed within 60 electrical degrees. Transfer
is initiated only if both sources are within 2 Hz of nominal frequency and 70 percent or more of
nominal voltage.
G. Automatic Transfer-Switch Features:
1. Undervoltage Sensing for Each Phase of Normal Source: Sense low phase-to-ground
voltage on each phase. Pickup voltage shall be adjustable from 85 to 100 percent of
nominal, and dropout voltage is adjustable from 75 to 98 percent of pickup value.
Factory set for pickup at 90 percent and dropout at 85 percent.
2. Adjustable Time Delay: For override of normal-source voltage sensing to delay transfer
and engine start signals. Adjustable from zero to six seconds, and factory set for one
second.
3. Voltage/Frequency Lockout Relay: Prevent premature transfer to generator. Pickup
voltage shall be adjustable from 85 to 100 percent of nominal. Factory set for pickup at
90 percent. Pickup frequency shall be adjustable from 90 to 100 percent of nominal.
Factory set for pickup at 95 percent.
4. Time Delay for Retransfer to Normal Source: Adjustable from 0 to 30 minutes, and
factory set for 10 minutes to automatically defeat delay on loss of voltage or sustained
undervoltage of emergency source, provided normal supply has been restored.
5. Test Switch: Simulate normal-source failure.
6. Switch-Position Pilot Lights: Indicate source to which load is connected.
7. Source-Available Indicating Lights: Supervise sources via transfer-switch normal- and
emergency-source sensing circuits.
a. Normal Power Supervision: Green light with nameplate engraved "Normal Source
Available."
b. Emergency Power Supervision: Red light with nameplate engraved "Emergency
Source Available."
8. Unassigned Auxiliary Contacts: Two normally open, single-pole, double-throw contacts
for each switch position, rated 10 A at 240-V ac.
9. Transfer Override Switch: Overrides automatic retransfer control so automatic transfer
switch will remain connected to emergency power source regardless of condition of
normal source. Pilot light indicates override status.
10. Engine Starting Contacts: One isolated and normally closed, and one isolated and
normally open; rated 10 A at 32-V dc minimum.
11. Engine Shutdown Contacts: Time delay adjustable from zero to five minutes, and factory
set for five minutes. Contacts shall initiate shutdown at remote engine-generator controls
after retransfer of load to normal source.
12. Engine-Generator Exerciser: Solid-state, programmable-time switch starts engine
generator and transfers load to it from normal source for a preset time, then retransfers
and shuts down engine after a preset cool-down period. Initiates exercise cycle at preset
intervals adjustable from 7 to 30 days. Running periods are adjustable from 10 to 30
minutes. Factory settings are for 7-day exercise cycle, 20-minute running period, and 5-
minute cool-down period. Exerciser features include the following:
BICKFORD OF CARMEL, IN 12/12/2012
TRANSFER SWITCHES 263600 - 5
a. Exerciser Transfer Selector Switch: Permits selection of exercise with and without
load transfer.
b. Push-button programming control with digital display of settings.
c. Integral battery operation of time switch when normal control power is not
available.
2.4 REMOTE ANNUNCIATOR AND CONTROL SYSTEM
A. Functional Description: Include the following functions for indicated transfer switches:
1. Indication of sources available as defined by actual pickup and dropout settings of
transfer-switch controls.
2. Indication of switch position.
3. Indication of switch in test mode.
4. Indication of failure of digital communication link.
5. Control of switch-test initiation.
6. Control of switch operation in either direction.
7. Control of time-delay bypass for transfer to normal source.
B. Malfunction of annunciator, annunciation and control panel, or communication link shall not
affect functions of automatic transfer switch. In the event of failure of communication link,
automatic transfer switch automatically reverts to stand-alone, self-contained operation.
Automatic transfer-switch sensing, controlling, or operating function shall not depend on
remote panel for proper operation.
C. Remote Annunciation and Control Panel: Solid-state components. Include the following
features:
1. Controls and indicating lights grouped together for each transfer switch.
2. Label each indicating light control group. Indicate transfer switch it controls, location of
switch, and load it serves.
3. Digital Communication Capability: Matched to that of transfer switches supervised.
4. Mounting: Flush, modular, steel cabinet, unless otherwise indicated.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Identify components according to Division 26 Section "Identification for Electrical Systems."
B. Set field-adjustable intervals and delays, relays, and engine exerciser clock.
3.2 CONNECTIONS
A. Wiring to Remote Components: Match type and number of cables and conductors to control
and communication requirements of transfer switches as recommended by manufacturer.
Increase raceway sizes at no additional cost to Owner if necessary to accommodate required
wiring.
BICKFORD OF CARMEL, IN 12/12/2012
TRANSFER SWITCHES 263600 - 6
B. Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical
Systems."
C. Connect wiring according to Division 26 Section "Low-Voltage Electrical Power Conductors
and Cables."
3.3 FIELD QUALITY CONTROL
A. Perform tests and inspections and prepare test reports.
1. Manufacturer's Field Service: Engage a factory-authorized service representative to
inspect components, assemblies, and equipment installation, including connections, and
to assist in testing.
2. After installing equipment and after electrical circuitry has been energized, test for
compliance with requirements.
3. Perform each visual and mechanical inspection and electrical test stated in NETA
Acceptance Testing Specification. Certify compliance with test parameters.
4. Measure insulation resistance phase-to-phase and phase-to-ground with insulation-
resistance tester. Include external annunciation and control circuits. Use test voltages
and procedure recommended by manufacturer. Comply with manufacturer's specified
minimum resistance.
a. Check for electrical continuity of circuits and for short circuits.
b. Inspect for physical damage, proper installation and connection, and integrity of
barriers, covers, and safety features.
c. Verify that manual transfer warnings are properly placed.
d. Perform manual transfer operation.
5. After energizing circuits, demonstrate interlocking sequence and operational function for
each switch at least three times.
a. Simulate power failures of normal source to automatic transfer switches and of
emergency source with normal source available.
b. Simulate loss of phase-to-ground voltage for each phase of normal source.
c. Verify time-delay settings.
d. Verify pickup and dropout voltages by data readout or inspection of control
settings.
e. Verify proper sequence and correct timing of automatic engine starting, transfer
time delay, retransfer time delay on restoration of normal power, and engine cool-
down and shutdown.
B. Coordinate tests with tests of generator and run them concurrently.
C. Report results of tests and inspections in writing. Record adjustable relay settings and measured
insulation and contact resistances and time delays. Attach a label or tag to each tested
component indicating satisfactory completion of tests.
D. Remove and replace malfunctioning units and retest as specified above.
BICKFORD OF CARMEL, IN 12/12/2012
TRANSFER SWITCHES 263600 - 7
3.4 DEMONSTRATION
A. Engage a factory-authorized service representative to train Owner's maintenance personnel to
adjust, operate, and maintain transfer switches and related equipment as specified below. Refer
to Division 01 Section "Demonstration and Training."
B. Coordinate this training with that for generator equipment.
END OF SECTION 16910