HomeMy WebLinkAboutCARMEL E300.pdfSEE MECHANICAL/PLUMBING DRAWINGS FOR EQUIPMENT RATINGS AND SIZES.
PERIODIC SITE OBSERVATION BY THE ENGINEER IS SOLELY FOR THE PURPOSE OF DETERMINING IF THE WORK OF
THE CONTRACTOR IS PROCEEDING IN ACCORDANCE WITH CONTRACT DOCUMENTS. THIS LIMITED SITE
OBSERVATION SHOULD NOT BE CONSTRUED AS EXHAUSTIVE OR CONTINUOUS TO CHECK THE QUALITY OR
QUANTITY OF THE WORK, BUT RATHER PERIODIC IN AN EFFORT TO GUARD THE OWNER AGAINST DEFECTS OR
DEFICIENCIES IN THE WORK OF THE CONTRACTOR.
THE INFORMATION CONTAINED ON THE ELECTRICAL DRAWINGS IS IN ITSELF INCOMPLETE AND VOID UNLESS
USED IN CONJUNCTION WITH ALL OTHER DISCIPLINE DRAWINGS, THE SPECIFICATIONS, TRADE PRACTICES, OR
APPLICABLE STANDARDS, CODES, ETC., AND SHALL BE CONSIDERED THE CONTRACT DOCUMENTS AND WITH
ALL THE IN BY REFERENCE, WHICH THE CONTRACTOR CERTIFIES KNOWLEDGE OF BY SIGNING THE CONTRACT.
CONTRACTOR IS TO ASSUME FULL RESPONSIBILITY, UNRELIEVED BY REVIEW OF SHOP DRAWINGS OR PERIODIC
OBSERVATION OF CONSTRUCTION, FOR COMPLIANCE WITH THE CONTRACT DOCUMENTS, FOR DIMENSIONS TO
BE CONFIRMED AND CORRELATED ON THE JOB SITE AND BETWEEN INDIVIDUAL DRAWINGS OR SETS OF
DRAWINGS FOR FABRICATION PROCESSES AND CONSTRUCTION TECHNIQUES (INCLUDING EXCAVATION,
SHORING, SCAFFOLDING, BRACING, ERECTION, FORMWORK, ETC.), FOR COORDINATION OF THE VARIOUS
TRADES, AND FOR SAFE CONDITIONS ON THE JOB SITE. VARIATIONS IN FIELD CONDITIONS RELATIVE TO THE
CONTRACT DOCUMENTS SHALL BE REPORTED TO THE ENGINEER AS SOON AS THEY ARE FOUND. WORK SHALL
NOT PROGRESS UNTIL WRITTEN PERMISSION FROM THE ENGINEER IS OBTAINED.
DRAWINGS ARE DIAGRAMMATIC. ALL DIMENSIONS SHOWN ARE APPROXIMATE. ALL LOCATIONS
SHALL BE FIELD VERIFIED. THESE DRAWINGS SHALL NOT BE SCALED TO OBTAIN DIMENSIONS. IF
THE DIMENSIONS CANNOT BE DETERMINED BY THE INFORMATION GIVEN, CONTRACTOR SHALL
CONTACT ENGINEER FOR REQUIRED INFORMATION.
ALL WORK SHALL BE IN CONFORMANCE WITH THE NATIONAL ELECTRICAL CODE- LATEST
EDITION ADOPTED BY INDIANA, THE INDIANA ELECTRICAL CODE AMENDMENTS, LOCAL/
MUNICIPAL CODES, AND THE AUTHORITY HAVING JURISDICTION.
ALL CONNECTIONS TO EQUIPMENT SUBJECT TO MOVEMENT OR VIBRATION SHALL BE LIQUID
TIGHT FLEXIBLE METAL CONDUIT, NOT LESS THAN 12" IN LENGTH, NOR GREATER THAN 36" IN
LENGTH.
ALL CONDUIT PENETRATIONS SHALL BE SEALED WITH APPROPRIATE CONDUIT SEALING
MATERIAL.
ELECTRICAL GENERAL NOTES:
HOMERUN CIRCUITS ARE NOTATED BESIDE RECEPTACLES AND EQUIPMENT. ALL HOMERUNS
SHALL BE FED BACK TO PANEL A UNLESS OTHERWISE NOTED.
MAJOR FEEDERS FROM THE SWITCHBOARD TO PANELBOARDS, TRANSFORMERS, MOTORS AND
OTHER LARGE EQUIPMENT ARE NOT SHOWN ON THE PLAN DRAWINGS. THESE FEEDERS ARE
INCLUDED WITHIN THE SCOPE OF THE ELECTRICAL WORK, AND SHALL BE INSTALLED AS INDICATED
ON THE ONE LINE DIAGRAM DRAWING.
REFER TO THE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF BUILDING EXPANSION JOINTS. ALL
CONDUITS CROSSING EXPANSION JOINTS SHALL BE INSTALLED WITH EXPANSION FITTINGS,
UNLESS THE CONDUIT IS BELOW SLAB IN THE COMPACTED GRANULAR FILL. EXPANSION FITTINGS
SHALL BE INSTALLED IN ACCORDANCE WITH THE NEC, AND MANUFACTURER'S WRITTEN
RECOMMENDATIONS.
INDOOR CONTROL EQUIPMENT ENCLOSURES SHALL BE NEMA 1 RATED U.O.N. ALL EXTERIOR
ENCLOSURES SHALL BE NEMA 3R U.O.N.
ALL VOICE/DATA CABLING, SECURITY CONTROL SYSTEM AND ALL OTHER LOW- VOLTAGE
SIGNAL CABLING SHALL BE INSTALLED BY OTHERS.
PENETRATIONS THROUGH FIRE RATED WALLS BY DIVISION 26 CONTRACTOR SHALL BE SEALED
WITH APPROPRIATE FIRE PROOFING MATERIAL TO RESTORE FIRE RATING. SEE ARCHITECTURAL
DRAWINGS FOR FIRE RATED WALLS.
ALL POWER AND LIGHTING CIRCUITS SHALL BE MINIMUM (2)#12, AND (1)#12 G, IN 3/4" C.
UNLESS OTHERWISE NOTED.
ALL CONTROL WIRING SHALL BE NOT LESS THAN 2#14, #14G, 3/4"C, UON.
ALL CABLES SHALL UTILIZE COPPER CONDUCTORS RATED AT 75C.
ALL CABLES INSTALLED IN AIR HANDLING PLENUMS SHALL BE PLENUM RATED CABLE.
HOME RUNS SHALL NOT BE COMBINED IN A RACEWAY UNLESS SHOWN ON THE CONTRACT
DRAWINGS. SINGLE PHASE BRANCH CIRCUIT HOME RUNS MAY BE COMBINED AT THE
CONTRACTOR'S DISCRETION NOT GREATER THAN (3) PHASE CONDUCTORS, (3) NEUTRAL
CONDUCTORS, AND GROUNDING CONDUCTOR.
EACH SINGLE PHASE BRANCH CIRCUIT CONDUCTOR SHALL HAVE A DEDICATED NEUTRAL
BACK TO THE PANELBOARD.
SUPPORTING WIRE FOR THE SUSPENDED CEILING GRID SHALL NOT BE USED AS RACEWAY
SUPPORT.
DISCONNECT SWITCH RATINGS SHALL BE AS INDICATED ON THE DRAWINGS. XXAF, XXAT
DESIGNATES "XX" AMP FRAME WITH "XX" AMP TRIP BREAKER.
HVAC CONTROL WIRING FURNISHED AND INSTALLED BY DIVISION 23. WIRING AND RACEWAY SHALL BE
INSTALLED PER DIV 26 SPECIFICATIONS.
TO REDUCE NOISE BETWEEN WALLS, CONTRACTOR SHALL:
A. AVOID INSTALLING POWER RECEPTACLES OR DATA OUTLETS LOCATED
BACK TO BACK.
B. WHERE OUTLETS ARE REQUIRED TO BE LOCATED BACK TO BACK
CONTRACTOR SHALL PROVIDE SOUNDPROOFING MATERIAL BETWEEN
JUNCTION BOXES.
CONTRACTOR IS RESPONSIBLE FOR FURNISHING AND INSTALLING ALL NECESSARY EQUIPMENT FOR ALL
DEVICES, MATERIALS AND PRODUCTS SHOWN ON THESE PLANS FOR A FULLY FUNCTIONING SYSTEM.
24.
22.
23.
21.
20.
19.
18.
17.
15.
16.
12.
13.
14.
10.
11.
8.
7.
9.
4.
6.
5.
2.
3.
1.
25.
MARK
LIGHTING SCHEDULE
SYMBOL
A
MAKE/ MANUFACTURER
SUSPENDED FLUORESCENT FIXTURE
COOPER LIGHTING
CORELITE i2 FROSTED LENS (48")B
RE-USE 2'X4' EXISTING FLUORESCENT LAY-IN FIXTURES
WITH .125 ACRYLIC PRISMATIC LENS (3) F32T8RS LAMPS WITH RAPID START ELECTRIC BALLAST
PROVIDE (2) BALLASTS PER FIXTURE WHERE DUAL
SWITCHING IS SHOWN. MATCH EXISTING FOR NEW.
BOTTOM OF FIXTURE TO BE 8'-0" A.F.F.
ACOUSTIC CEILING TILE.
RE-INSTALL EXISTING, OR MATCH EXISTING MANUFACTURER & TYPE
FOR NEW.
EXIT CEILING MOUNTED EXIT SIGN WITH 6" RED LED LETTERS & 90 MIN. BATTERY BACKUP.
LITHONIA #LES-1R- 120/277-ELNSD
RE-USE EXISTING FIXTURES. NEW TO MATCH ABOVE.
EMERGENCY LIGHT WITH 90 MIN INVERTER BALLAST
LITHONIA #25P8G-332-A12125-MVOLT-GEB10RS, OR APPROVED EQUAL. MATCH EXISTING FOR NEW
DRAWN BY: WB
DATE-03/27/2013
REVISED-04/02/2013
04/10/2013
SHEET
E300
PROJECT:
MAWR design, inc.
WWW. MAWRDESIGN. COM
architecture. engineering. interior design
849 S. park drive
carmel in 46032
ph-765-453-1745
PROPOSED RENOVATIONS TO SECOND FLOOR UNIT
LOCATED 30 WEST MAIN STREET, CARMEL INDIANA
TO FACILITATE CARMEL REDEVELOPMENT
COMMISSION AND CARMEL UTILITIES
CERTIFICATION