TELEC�M
R��M
UP T❑'
4TH � .:: ..
FL❑❑R
ELECTRICAL
R❑❑M
PARTIAL FIRST FLOOR ELECTRICAL PLAN
SCALE� 1/8' = 1'-0'
EXISTING PANEL SCHEDULE
PANEL NAME: 4PE LOCATION: 4TH FLOOR TELECOM RM PROJECT INFQ
VOLTAGE: 120/208 VOLT, 3 PH, 4 WIRE MOUNTING: SURFACE PROJECT NAME: BLACKBAUD
RATING: 250 AMP, MAIN LUGS FED FROM: PANEL 4PA 200A CIRCUIT BREAKER PROJECT NO: 13-068
ENCLOSURE: NEMA 1 5/31/2013
BREAKE LOAD IN KVA LOAD IN KVA BREAKE
CKT DESCRIPTION P TRIP LTS RECP MOTO HEAT MISC "A" "B" "C" LTS RECP OTO HEAT MISC P TRIP DESCR{PTION CKT
1 WORKSTATION RECP 1 20 0.4 0.7 0.4 1 20 TRAINING ROOM RECP 2
3 WORKSTATION RECP 1 20 0.4 0.7 0.4 1 20 TRAINING ROOM RECP 4
5 WORKSTATION RECP 1 20 0.4 0.7 0.4 1 20 TRAINING ROOM RECP 6
7 WORKSTATION RECP 1 20 0.4 0.7 0.4 1 20 TRAINING ROOM RECP 8
9 SPARE 1 20 0.0 1 20 SPARE 10
11 SERVER ROOM RECP 1 20 0.5 0.5 1 20 SPARE 12
13 SERVER/RACK-UPS 2 30 3.0 3.0 1 20 SPARE 14
15 3.0 3.0 1 20 SPARE 16
17 SERVER/RACK-UPS 2 30 3.0 3.0 1 20 SPARE 18
�g 3.0 3.0 1 20 SPARE 20
21 SERVER/RACK-UPS 2 30 3.0 3.0 1 20 SPARE 22
2g 3.0 3.0 1 20 SPARE 24
25 SERVER/RACK-UPS 2 30 3.0 3.0 1 20 SPARE 26
2� 3.0 3.0 1 20 SPARE 28
29 SERVER/RACK-UPS 2 30 3.0 3.0 1 20 SPARE 30
31 3.0 3.0 1 20 SPARE 32
33 SERVER/RACK-UPS 2 30 3.0 3.0 1 20 SPARE 34
35 3.0 3.0 1 20 SPARE 36
g7 5.0 5.0 1 20 SPARE 38
39 15KVA TRANSFORMER FOR 3 50 5.0 5.0 1 20 SPARE 40
41 LIEBERT UNIT 5.0 5.0 1 20 SPARE 42
18 18 18
TOTAL CONNECTED LIGHIING LOAD (KVA) 0 TOTAL DEMAND LIGHTING LOAD (KVA) 1.0 0 NOTFS: EMERGENCY POWER FEED: 57KW
TOTAL CONNECTED RECP LOAD (KVA) 3 TOTAL DEMAND RECEPTACLE LOAD (KVA) 1 3 GENERATOR
TOTAL CONNECTED MOTOR LOAD (KVA) 0 TOTAL DEMAND MOTOR LOAD (KVA) 1 0
TOTAL CONNECTED HEATING LOAD (KVA} 0 TOTAL DEMAND HEATING LOAD (KVA) 1 0
TOTAL CONNECTED MISC. LOAD (KVA) 51 TOTAL DEMAND MISC. LOAD (KVA) 1. 51
TOTAL CONNECTED LOAD (KVA) 54 TOTAL DEMAND LOAD (KVA) DF 54
EXISTING
�ANDSCAP
AREA
i
I
�
i
i
I
�
i
�
1�
: I�
��
�
�i
�i
I�i
� i�
3 __ _
EXISTING
LANDSCAPE
AREA
C�NTROLS TD ATS �7
P�WER T❑ ATS 7O
.�,°"„'",,,""""",",,,,,,,,,,, ELECTRICA� SCOPE ❑F W❑RK
��.��� ��SN A P,y �. �ii,,��
��-Q:.�'��STfR••:F� '� . ADDED NEW C�NDUIT AND FEEDER C❑NDUCTORS FR�M REL�CATED
:��.ti <``p••: , 57kw GENERATOR T❑ F�URTH �L��R TELEC�M ROOM.
: No. PE10100899`_ ' � NOTED L�CATI❑N ❑F RELOCATED AUT�MATIC TRANSFER SWITCH
'' ��� IN F�URTH FLDOR TELEC�M RODM AND ADDED NEW SAFETY
� sTarE oF :' ��`
� ' �N�lANP.'' : SWITCH,
°''%i,,, 0 A E�°° . ADDED NEW 208V - 200A BREAKER IN EXISTING PANEL 4PA F❑R
� �� THE ATS NORMAL POWER FEED,
5� ���3 • NOTED UTILIZING EXISTING PANEL 4PE F�R EMERGENCY P�WER
❑NLY, ADDED A NEW 208V - SOA BREAKER FOR NEW 15KVA
TRANSFORMER FEED.
• ADDED A NEW 15KVA 208V - 480V STEP UP TRANSFORMER AND
480V - 20A BREAKERS THAT FEED EXISTING S T�N, 480V
LIEBERT CO�LING UNIT T� BE ON EMERGENCY P�WER,
• ADDED NEW 277V NORMAL P❑WER CIRCUITS F�R NINE C9) NEW
HEAT PUMPS THAT SUPPORT AREAS ❑N THE F�URTH FLDOR.
-ENCE
�HER
ING RELOCATED
'AT�R
*�-
GENERAL N�TES�
1. CONTRACTOR SHALL EXCAVATE ENTIRE RACEWAY LENGTH BEF�RE
BEGINNING INSTALLATI�N. FIELD VERIFY ALL INTERFERENCE WITH
BURIED UTILITIES.
2. C�NTRACTOR SHALL FIELD VERIFY EXACT L�CATIONS ❑F EXISTING
UTILITIES (TYPICAL), IMMEDIATELY REP❑RT ANY DISCREPANCIES T❑
THE ENGINEER THAT MAY INTERFERE WITH THE INSTALLATIDN ❑F
NEW WORK.
3, C�NTRACTOR SHALL VERIFY ALL DIMENSIDNS CVERTICAL AND
H�RIZONTAL) IN THE FIELD PRI�R T� STARTING CONSTRUCTIDN,
C❑NTRACT�R SHALL BE RESPONSIBLE FOR ALL FIELD DIMENSIONS, IF
ANY DISCREPANCIES ARE F❑UND IN THESE PLANS FR�M THE ACTUAL
FIELD CONDITIONS, CONTRACT�R SHALL N❑TIFY THE ENGINEER
IMMEDIATELY,
4, ALL W�RK SHALL CONF❑RM T� STATE AND L❑CAL REGULATIDNS.
5, EXCAVATING CONTRACT�R SHALL TAKE PARTICULAR CARE WHEN
EXCAVATING IN AND AROUND EXISTING UTILITY LINES, EQUIPMENT
AND EXISTING STRUCTURES, VERIFY C�VER REQUIREMENTS BY
UTILITY C�NTRACT❑RS AND UTILITY C�MPANIES S❑ AS NOT T� CAUSE
DAMAGE. CONTRACT❑R MAY NEED T❑ HAND DIG IN AREAS CLOSE T❑
UTILITIES AND THE BUILDING STRUCTURE.
6. C❑NTRACT❑R SHALL N�TIFY ❑WNER AND ALL UTILITY C❑MPANIES A
MINIMUM �F 72 H�URS BEF�RE C❑NSTRUCTION IS T� START, T❑
VERIFY IF ANY UTILITIES ARE PRESENT ❑N SITE, ALL
VERIFICATIONS (LOCATI�N, SIZE, AND DEPTH> SHALL BE MADE BY
THE APPROPRIATE UTILITY COMPANIES. WHEN EXCAVATING IS AROUND
❑R ❑VER EXISTING UTILITIES, THE CONTRACT❑R SHALL N❑TIFY THE
UTI�ITY COMPANY S❑ A REPRESENTATIVE ❑F THAT UTILITY COMPANY
MAY BE PRESENT T❑ INSTRUCT AND ❑BSERVE DURING C�NSTRUCTION,
7, C�NTRACT❑R SHALL SUPPORT ALL PIPING, DUCTBANK, AND C�NDUITS
SPANNING THE TRENCH EXCAVATI�N.
8. CONTRACT�R SHAL� MAINTAIN A MINIMUM COVER ❑F 3'-0' FOR ALL
ELECTRICAL RACEWAYS UNLESS �THERWISE N❑TED,
9, ALL CUTTING, PATCHING, TRENCHING, �R SITE W�RK REQUIRED SHALL
BE PAID FOR BY THIS C�NTRACT�R AND PERF�RMED BY THE
APPROPRIATE TRADE, AT PROJECT C�MPLETION SITE WHERE BURIED
C�NDUIT T❑OK PLACE SHALL MATCH EXISTING C❑NDITI�NS,
10. PLACEMENT �F GENERAT�R AND GENERAT❑R PAD SHALL BE BY
❑THERS,
11, LANDSCAPING PLAN AND NEW PRIVACY FENCE SHALL BE BY OTHERS,
MINIMUM DISTANCES SHALL BE MAINTAINED F�R CLEAR W�RKING
SPACE AND AIR FL�W AR�UND GENERAT�R,
12. USE EMT C�NDUIT(S) INSIDE THE BUILDING.
13. STRAP/SUPP�RT VERTICAL C�NDUITCS) USING UNISTRUT AND 'C'
CLAMPS.
14, USE PVC-40 C❑NDUITCS) F❑R UNDER GR�UND C�NDUIT. STUB-UP
ELBOW WILL BE 'GRC',
�
/
' •
C /
`
�
PLAN N�TES�
O1 C�NTRACTOR SHALL SHALL COORDINATE WITH UTILITY C�MPANY T❑
PR❑VIDE NATURAL GAS CONNECTI❑N T� THE GENERAT❑R AND
C�NNECTI❑N T❑ THE NEW GAS METER.
O2 CONTRACTOR SHALL TRENCH NEW RACEWAY FROM GENERATOR T❑ �
BUILDING. C�ORDINATE STUB UP LOCATION WITH SH�P DRAWINGS ❑N
EXISTING GENERATpR, �
F-
O3 C�NTRACT�R SHALL R�UTE RACEWAY ABOVE LAY-IN CEILING T❑ J W
FIRST FL��R ELECTRICAL RO�M. Q Q W
4 O C�NTRACTOR SHALL INSTALL 3/4" DIAM E T E R B Y 8'- 0' L O N G C O P P E R V/ a O,
CLAD GR�UND R❑D DRIVEN INT� GR�UND. C�NNECT T❑ GENERAT�R � � I
G R O UND WITH #1/ 0 C OPPER CABLE. J W a
F- �
5O C❑NTRACTOR SHALL C�RE DRILL EXTERI�R WALL AT FIRST FL❑OR � I
FINISH FLO�R LEVEL, PENETRATI�N SHALL BE SEALED WATER TIGHT, � O Z'
PR❑VIDE LB AT EXTERI�R WALL PENETRATI�N, � � z�
O6 CONTRACT�R SHALL C❑RE DRIL� FL❑ORS AND FIRE ST�P AS Q V�
REQUIRED UP TO F�URTH F�O�R ELECTRICAL RD❑M. �
Z
Q �
U7 REFER T❑ P❑WER SCHEMA7IC ❑N SHEET E-302 FOR ADDITI�NAL p Q
SC❑PE, � � Y
W
8O C�NTRACT�R SHAL� PROVIDE PULL BOX. SIZE ❑F PULL B❑X SHALL � Q
COMPLY WITH NATIpNAL ELECTRIC CODE. Z -�
O m
�
I •
/ / •
I�t10W W�'tat'8 ��OW.
Cetll be�ore you d�g.
b
KEYPLAN
SCALE� NONE
PROJECT NO.:
DWG FILE:
13-0�
DATE
DWG SCALE:
1 /�
PLOT SCALE:
DRAWN BY: