To: Owner / Architect I Engineer
pE~ATON AND HANCOCK ASSOCIATES INC ULA S EATON 00093
2066 OLDFIELDS CIRCLE
INDIANAPOLIS iN 46228 '
Fax & e-mail: 31729594S2, eatonhancock~aot.com
The plans, specifications and app[~ca ion subnitted for the above referenced project have been review ed for comp isnce with th~
of the Fire Prevention and Building Safety CorriTission, The p~oject is released for construction subject to. but not n~,cessarily limited to, the
condition~ listed below. THIS IS NOT A BUILDING F~IT. Al required ioca pe;'~r~ a~d ~enses trust be obiained [~'~0r'{~ beginning construction
work. A I cons ruction work rr~st be in full complience W ~ at[ applicable State rules~Any changes in the released plans and/or specifications must
be filed w ~[h and released by this Office before
error in violation of any rules of the Cornr~ss~n 0rif ~ is base~d on3ncqrre?t 0r.~sufh¢lent ,nformation. Th~s ra~e~s~ish~!!.f~xplre by ,r~tabon, and
becom~ null and vole, if the w 0rk authorized is not commenced w ~d~kq one (1) year.from the above date. : ~ ~; ~ -; :
CONDITIONS: .
Note :(alu & al B): ~n accordance with the affleavit sw om under penelt es of perjury in the application lot consb'action design re~ease the plans
and specifications f led n ~onjunc~i0n w ifh th s project shell comply w ith all of the applicable rules and iow s of F~re Prevention and Building Safety
Com~.ssiom Provioin§ fa~.e information cOns~utes an act of perjury, w hieh is a Qass D felony punishable by a prison term and a ~ine up to $10,000.
~n accordance w ith Section 19 of the General Adn~[stratNe Rules (675 [AC 12-6-19) a complete set of plans and specEications that coqform
exacgy to the des gr~ that w as re~eased ~3y the office of the state building comr~ssicner shall be mainta,ned on the construction ]obs~te as w ell as a
copy o[ the design release.
3B1004G Fire-resistance-rated corridors shall be continuous from the point of entry and shall not be interrupted
by interv.ening rooms in accordance w ith Section 1004.3.2.5, IBC (675 lAC 13-2.4).
3BI004E Where more than one exr{ or exit access doorw ay is required, the exit access shall be arranged such
that there ara no dead ends in corridors more than 20 feet in length in accordance with Section
1004,3.2.3, IBC (675 lAC 13-2.4).
3B1004D1 Exit corridors shalL be fire-resistance rated in accordance with Section 1004~3.2.1 and Table
1004.3.2.1, IBC (675 lAC 13-2.4).
3B1004F Corridors shall not serve as suppy return, exhaust, relief or ventiation air ducts or plenums
accordance W ]th Section 1004.3.2.4, ISG (675 lAC 13-2.4).
3B111.2 Buildings shall be accessible to persons w ith disabilities in accordance with Section 1.2 (1 through 5)
and (2), Part 1, Chapter 11, IBC (875 ]AC 13-2.4).
3G0501a Buldngs the are heated or mechanically cooled shal be constructed so as to provde the requred
thermal performance of the various components in accordance w ith Secton 501 1, tEGC (675 lAC '[9-
4G0618AK "Alternates~ to plans are not part of a release and will only be considered as part of this project if
submitted as addenda in accordance with 675 lAC 12-6-18
THIS CONSTRUCTION DESIGN IS A CORRECTED RELEASE TO CHANGE THE COUNTY