HomeMy WebLinkAboutCarmel UMC COMCheck - Alteration without HVACCOMcheck Software Version 3.9.2
Envelope Compliance Certificate
90.1 (2007) Standard
Section is Project Infor 4tion
Project Type: Alteration
Project Title : Carmel United Methodist Church - addition & renovation
Construction Site:
621 South Range Line Road
Carmel. IN 46032
Owner /Agent:
Karl Maierhofer
Cannel United Methodist Church
621 South Range Line Road
Carmel. IN 46032
Section 2: General Information
Building Location (for weather data): Carmel. Indiana
Climate Zone: 5a
Building Space Conditioning Type(s): Nonresidential
Vertical Glazing l Wall Area Pct.: 21%
Activity Ty
pe sj
Floor Area
Classroom B102 (Common Space
728
Types: C I a ssroomlLectu rafTra inin g )
Classroom 6117 (Common Space
557
Types: C la ssroomlLe ctu re/T ra ini ng )
Classroom B118 (Common Space
557
Types: C I a ssroomlLectu ref Tra ining )
Cry Room B124 (Common Space
195
Types :Classroom /LecturelTraining )
Classroom 6132 (Common Space
546
Types:C I a ssroom/Le ctu rea ra ining )
Narthex B137 (Common Space Types:CarridorlTransition)
601
Storage B140 (Common Space Types:Active Storage)
54
Restroom B141 (Common Space Types: Restrooms)
93
Office B144 (Common Space Types:Office - Enclosed)
195
Gathering 8145 (Common Space Types: Lobby)
3719
Cafe B146 (Common Space Types :Food Preparation)
294
Kitchen B147 (Common Space Types Food Preparation)
120
LibraylConference B148 (Common Space
510
Ty pes: Co of erencelM eetinglM u fti p u rpose )
Vestibule 8149 (Common Space Types: C orridorrl' ra ns Rio n)
199
Corridor 8155 (Common Space Types:CorridorlTransition)
94
CorridorB156 (Common Space Types:CorridorlTransiiion)
273
Reception B157 (Common Space Types:Office - Enclosed)
141
Corridor 13158 (Common Space Types:Corrido rFrra n 9 Rion)
306
Office B159 (Common Space Types:Office - Enclosed)
157
Office B160 (Common Space Types:Office - Enclosed)
373
Office B161 (Common Space Types:Office - Enclosed)
156
Office B163 (Common Space Types:Office - Enclosed)
96
Office 8165 (Common Space Types:Office - Enclosed)
96
Office 8166 (Common Space Types:Office - Enclosed)
96
Office 168 (Common Space Types:Office - Enclosed)
96
Office 169 (Common Space Types:Office - Enclosed)
213
Fa. A 1!51 A,
'M ?04/
I ,el /;//
adlv
Designer/Contractor:
Jon Byrum
Byrum Architects
160 West Carmel Drive
Suite 240
Carmel. IN 46032
317- 574 -8808
Project Title: Carmel United Methodist Church - addition & renovation Report date: 09/03113
Data filename: C:Oocuments and SetfingslHP- AdministratoAMy Documents0rawingM12005 Carmel UMCICOMCheck - CUMC
addition 2013- 09- 03.cck Page 1 of 6
Office 170 (Common Space Types:Office - Enclosed)
96
Office 171 (Common Space Types:Office - Enclosed)
110
Corridor 172 (Common Space Types:Office - Enclosed)
123
Office 173 (Common Space Types: Cc rrid or/Tra n sit ion)
149
Office 175 (Common Space Types:Office - Enclosed)
91
Classroom BO 11 (Common Space
1116
Types :Classroom /Lect u relTra inin g )
0.400
Restroom B025 (Common Space Types: Restrooms)
40
Corridor B049 (Common Space Type s :CorridorlTransition)
350
Cafe B053 - seating (Common Space Types:Dining Area -
697
General)
Cafe B053 - prep area (Gammon Space Types:Food Preparation)
135
Classroom B057 (Common Space
2115
Types :ClassroomfLecture /Training )
Classroom B058 (Common Space
1469
Types :ClassroomlLecturefrraining)
Corridor B059 (Common Space Types: CorridorfTransilion)
167
Mechanical 161 (Common Space Types:ElectricallMechanical)
43
Section 3: Envelope Assemblies
,Envelope PASSES
Climate- Specific Requirements:
Post - Alteration Assembly
Window 1: Metal Frame Curtain WalllStorefron[:Double Pane with
Law -E, Tinted
Window 2: Metal Frame Curtain Wall /StorefronLDouble Pane with
Low -E, Tinted
Window 3: Metal Frame Curtain WalllStorefront:Double Pane with
Low -E, Tinted
Window 4: Metal Frame Curtain WalllStorefront:Double Pane with
Low -E, Tinted
Door 1: Glass (> 50% glazing):Metal Frame, Tinted, Entrance
Door, Entrance Door
Door 2: Glass (> 50% glazing):Metal Frame, Tinted, Non- Entrance
Door. Non - Entrance Moor
R -Value Proposed Max. Allowed
Cavity Cont. U- Factor SHGC U- Factor SHGC
-- --- 0.450 0.400 0.450 4.400
--- 0.450 0.400 0.450 0.400
— -- 0.450
0.400
0.450
0.400
0.450
0.400
0.450
0.400
- -- 0.800
0.400
0.800
0.400
– — 0,550
0.400
17.550
0.400
Section 4: Compliance Statement
Compliance Statement: The proposed envelope alteration project represented in this document is consistent with the building plans,
specifications and other calculations submitted with this permit application. The proposed envelope alteration project has been designed to
meet the 90.1 (2007) Standard requirements in COMcheck Version 3.9.2 and to comply with the mandatory requirements in the Requirements
Checklist 'A All 4 144 ....... I ......
Na a -Title Y Signatu t!� 41�iii Date
- �YRU / // //.
1tED •.;Cl SIP f:
" t ar
Project Title: Carmel United Methodist Church - addition & renovation Report date: 09103/13
Data filename: C:0ocuments and SettingslHP- AdministratorNy DocumentslDrawings112005 Carmel UMCICOMCheck - CU MC
addition - 2013- 09 -03.cck Page 2 of 6
COMcheck Software Version 3,9.2
Interior Lighting and Bower
Compliance certificate
90.1 (2007) Standard
Section 1: Project Information
8
Project Type: Alteration
D
Project Title : Carmel United Methodist Church - addition & renovation
Floor Area
Construction Site: Owner /Agent:
Designer /Contractor:
621 South Range Line Road Karl Maierhofer
Jon Hyrum
Carmel, IN 46032 Carmel United Methodist Church
Byrum Architects
621 South Range Line Road
160 West Carmel Drive
Carmel, IN 46032
Suite 240
Classroom 13117 (Common Space Types:Classraom /Lecture /Training)
Carmel, IN 46032
1.4
317- 574 -8808
Section 2: Interior Lighting and Power Calculation
A
8
C
D
Area Category
Floor Area
Allowed
Allowed Watts
(ft2)
Watts 1 ft2
(B x C)
Classroom B102 (Common Space Types :Classroom /Lecturefrrainingj
728
1.4
1019
Classroom 13117 (Common Space Types:Classraom /Lecture /Training)
557
1.4
780
Classroom 13118 (Common Space Types :Classroom /LecturelTraining)
557
1.4
780
Cry Room 8124 (Common Space Types: C lassroom/Lectu re/T ra i ni ng)
195
1.4
273
Classroom B132 (Common Space Types :Classroom /Lecture/Training)
546
1.4
764
Narthex 8137 (Common Space Types:CorridorfTransition)
601
0.5
301
Storage 8140 (Common Space TypesActive Storage)
54
0.8
43
Restroom B141 (Common Space Types:Restrooms)
93
0.9
84
Office 8144 (Common Space Types:OIfice - Enclosed)
195
1.1
215
Gathering B145 (Common Space Types:Lobby)
3719
13
4835
Cafe B146 (Common Space Types:Food Preparation)
294
1.2
353
Kitchen B147 (Common Space Types:Food Preparation)
120
1.2
144
Libray /Conference B148 (Common Space
510
1.3
663
Types: Conference /M eet in g IM u lti p u rpose )
Vestibule B149 (Common Space Types:CorridorfTransilion)
199
0.5
100
Corridor B155 (Common Space Types:Corridor /Transilion)
94
0.5
47
CorridorS156 (Common Space Types:CorrldorfTransition)
273
0.5
137
Reception 8157 (Common Space Types:Office - Enclosed)
141
1.1
155
Corridor B158 (Common Space Types:Corridor[Transition)
306
0.5
153
Office B159 (Common Space Types:Office - Enclosed)
157
1.1
173
Office B160 (Common Space Types:Office - Enclosed)
373
1.1
410
Office B161 (Common Space Types:Office - Enclosed)
156
1.1
172
Office B163 (Common Space Types:Office - Enclosed)
96
1.1
106
Office B165 (Common Space Types:Office - Enclosed)
96
1.1
106
Office B166 (Common. Space Types:Office - Enclosed)
96
1.1
106
Office 168 (Common Space Types:Office - Enclosed)
96
1.1
106
Office 169 (Common. Space Types:Office - Enclosed)
213
1.1
234
Office 170 (Common Space Types:Office - Enclosed)
96
1.1
106
Office 171 (Common Space Types:Office - Enclosed)
110
1.1
121
Corridor 172 (Common Space Types:Office - Enclosed)
123
1.1
135
Office 173 (Common Space Types:CorrldorfTransition)
149
0.5
75
Office 175 (Common Space Types:Office - Enclosed)
91
1.1
100
Classroom BO 11 (Common Space Types :Classroom /Lectureffraining)
1116
1.4
1562
Project Title: Carmel United Methodist Church - addition & renovation Report date: 09103/13
Data filename: C:0ocuments and Settings' HP- AdministratorWy ❑ocuments0mwing02005 Carmel UMCICOMCheck - CUMC
addition 2013 -09- 03.cck Page 3 of 6
Restroom 8025 (Common Space Types:Restrooms)
40
0.9
36
Corridor 8049 (Common Space Types:CorridorfTransition)
350
0.5
175
Cafe 8053 - seating (Common Space Types:Dining Area - General)
697
0.9
627
Cafe B053 - prep area (Common Space Types:Food Preparation)
135
1.2
162
Classroom B057 (Common Space Types: ClassroomlLecture+'Training)
2115
1.4
2961
Classroom 8058 (Common Space Types: ClassroomlLecturefT rain ing)
1469
1.4
2057
Corridor 8059 (Common Space Types:Corrfdor/Transition)
167
0.5
64
Mechanical 161 (Common Space Types: Etectrical/Mechanica1)
43
1 5
65
Total Allowed Waits = 20520
Section 3: Interior Lighting Fixture Schedule
A
B C
D
E
Fixture ID : Description / Lamp / Wattage Per Lamp 1 Ballast
Lamps/ # of
Fixture
(C X D)
Fixture Fixtures
Watt.
Classroom 8102 ( Common Space Types :Classroom /LecturefTraining 728 sq.ft.)
Linear Fluorescent 1: 48" T8 32W: Electronic:
2 11
64
704
Classroom B117 ( Common Space Types :Classroom /Lecture/Training 557 sq.ft.)
Linear Fluorescent 2: 48" T8 32W: Electronic:
2 10
64
640
Classroom 13118 ( Common Space Types:Classroom/Lecture /Training 557 sq.ft.)
Linear Fluorescent 3: 48" T8 32W: Electronic:
2 10
64
640
Cry Room 6124 ( Common Space Types:Classroom /Lecture/Training 195 sq.tt.)
Linear Fluorescent 4: 48" T8 32W Electronic:
2 2
64
128
Classroom 8132 ( Common Space Types.-Classroom/Lecture/Training 546 sq.ft.)
Linear Fluorescent 5: 48 " T8 32W Electronic:
2 8
64
512
Narthex 6137 ( Common Space Types:Corridor[Transilion 601 sq.ft.)
Compact. Fluorescent 1: Twin Tube 13W: Electronic
3 2
39
78
Storage B140 ( Common Space Types-.Active Storage 54 sq.ft.)
Compact Fluorescent 2: Chad 2 -pin 26W: Electronic:
1 1
26
26
Restroom 8141 ( Common Space Types:Restmoms 93 sq.ft,)
Compact Fluorescent 3: Quad 2 -pin 26W: Electronic:
1 1
26
26
Incandescent 1: Incandescent 50W:
1 1
50
50
Office 8144 ( Common Space Types:Office - Enclosed 195 sq.ft.)
Linear Fluorescent 6: 48" T8 32W: Electronic:
2 3
64
192
Gathering 8145 ( Common Space Types:Lobby 3719 sq.ft.)
Linear Fluorescent 7. 48" T8 32W: Electronic:
2 34
64
2176
Linear Fluorescent 8: 48" T8 32W: Electronic:
1 1
32
32
Track lighting 1: Wattage based on 40 feet of track
0 0
0
1200
Compact Fluorescent 4: Quad 2 -pin 26W: Electronic:
4 2
104
208
Incandescent 2: existing sconces: Incandescent 60W:
1 6
60
360
Cafe 8146 (Common Space Types:Food Preparation 294 sq.ft.)
Compact Fluorescent 5: Quad 2 -pin 26W: Electronic:
1 9
26
234
Compact Fluorescent 6: Twin Tube 13W: Electronic:
1 4
13
52
Kitchen 8147 ( Common Space Types:Food Preparation 120 sq.ft.)
Linear Fluorescent 9: 48" T8 32W: Electronic:
2 2
64
128
Libray /Conference 8148 ( Common Space Types: Conference /Meeting /Multipurpose 510 sq.ft.)
Linear Fluorescent 10.48" T8 32W: Electronic:
2 8
64
512
Vestibule 8149 ( Common Space Types:CorridorfTransition 199 sq.ft.)
Linear Fluorescent 11: 48" T8 32W: Electronic:
2 2
64
128
Corridor B155 ( Common Space Types:Corridor/Tra ns Rion 94 sq.ft.)
Linear Fluorescent 12: 48" T8 32W: Electronic:
1 1
32
32
CorridorB156 ( Common Space Types:Corridorfrransition 273 sq.ft.)
Linear Fluorescent 13:48" T8 32W: Electronic:
1 3
32
96
Reception 8157 ( Common Space Types --Office - Enclosed 141 sq.ft.)
Linear Fluorescent 14: 48" T8 32W: Electronic:
2 2
64
128
Corridor 8158 ( Common Space Types.CorridorfTransdion 306 sq.ft.)
Linear Fluorescent 15: 48" T8 32W: Electronic:
1 4
32
128
Office 6159 ( Common Space Types:Office - Enclosed 157 sqA.)
Linear Fluorescent 16: 48" T8 32W: Electronic-
2 2
64
128
Office 6160 ( Common Space Types:Office - Enclosed 373 sq.ft.)
Project Title: Carmel United Methodist Church - addition & renovation Report date: 09/03113
Data filename: C:1Documents and S etti ngs%HP-Adm inistratorlMy Documentsl0rawings112005 Carmel UM=0MCheck - CUMC
addition 2013- 09- 03.cck Page 4 of 6
Linear Fluorescent 17. 48" T8 32W: Electronic:
2
4
64
256
Office B161 ( Common Space Types:Office - Enclosed 156 sq.ft.)
Linear Fluorescent 18 48" T8 32W Electronic:
2
2
64
128
Office 6163 ( Common Space Types:Office - Enclosed 96 sq.ft.)
Linear Fluorescent 19: 48" T8 32W: Electronic:
2
2
64
128
Office 6165 ( Common Space Types:Office - Enclosed 96 sq.ft.)
Linear Fluorescent 20: 48" T8 32W: Electronic:
2
2
64
128
Office 6166 ( Common Space Types:Office - Enclosed 96 sq.ft.)
Linear Fluorescent 21. 48" T8 32W Electronic
2
2
64
128
Office 168 ( Common Space Types:Office - Enclosed 96 sq.ft.)
Linear Fluorescent 22 48" T8 32W: Electronic:
2
2
64
128
Office 169 ( Common Space Types:Office - Enclosed 213 sq.ft.)
Linear Fluorescent 23: 48" T8 32W: Electronic:
2
2
64
128
Office 170 ( Common Space Types:Office - Enclosed 96 sq.ft.)
Linear Fluorescent 24 48" T8 32W Electronic
2
2
64
128
Office 171 ( Common Space Types:Office - Enclosed 110 sq.ft.)
Linear Fluorescent 25: 48" T8 32W: Electronic:
2
2
64
128
Corridor 172 ( Common Space Types:Office - Enclosed 123 sq.ft.)
Linear Fluorescent 26 48" TS 32W: Electronic
2
2
64
128
Office 173 ( Common Space Types: Corridorrrransition 149 sq.ft.)
Linear Fluorescent 27: 48" T8 32W: Electronic:
1
2
32
64
Office 175 ( Common Space Types:Office - Enclosed 91 sq.ft.)
Linear Fluorescent 28: 48" T8 32W: Electronic:
2
2
64
128
Classroom B011 ( Common Space Types : Classroom /Lecture/7raining 1116 sq.ft.)
Linear Fluorescent 29: 48" T8 32W Electronic:
2
20
64
1280
Restroom B025 ( Common Space Types:Restrooms 40 sq.ft.)
Incandescent 3: Incandescent 50W
1
1
50
50
Corridor 8049 ( Common Space Types:CorridorlTransition 350 sq.ft.)
Linear Fluorescent 30- 48" T8 32W Electronic:
2
2
64
128
Cafe B053 - seating ( Common Space Types:Dining Area - General 697 sq.ft.)
Linear Fluorescent 31 48" T8 32W7 Electronic:
2
10
64
640
Track lighting 2: Wattage Based on 12 feet of track
0
0
0
360
Cafe B053 - prep area ( Common Space Types:Food Preparation 135 sq.ft.)
Compact Fluorescent 7 Twin Tube 13W: Electronic:
1
4
13
52
Track lighting 3: Wattage based on 16 feet of track
0
0
0
480
Classroom B057 ( Common Space Types :ClassroomlLecturetTraining 2115 sq.ft.)
Linear Fluorescent 32 48" T8 32W Electronic:
2
28
64
1792
Compact Fluorescent 8: Quad 2 -pin 26W: Electronic
1
3
28
84
Classroom B058 ( Common Space Types :ClassroomlLecturefTraining 1469 sq.ft.)
Linear Fluorescent 33: 48" T8 32W Electronic:
2
16
64
1024
Linear Fluorescent 34:48" T8 32W Electronic:
1
4
32
128
Corridor B059 ( Common Space Types:CorridorrTransition 167 sq.ft,)
Linear Fluorescent 35: 48" T8 32W: Electronic:
2
1
64
64
Mechanical 161 ( Common Space Types: ElectdcalfMechanical 43 sq.ft.)
Compact Fluorescent 9: Quad 2 -pin 26W Electronic:
1
1
26
26
Total Proposed Watts = 16246
Interior Lighting PASSES
Section 4: Compliance Statement
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans, specifications and
other calculations submitted with this permit application. The proposed ligh g system has been designed to meet the 90.1 (2007) Standard
requir enls in COMcheck Version 3.9.2 an d, mply with the mandat uirements in the Requirements Checklist.
r11111111I101111Ntpr' r.
ame - Tit e 7 V Sig, t rr: `�`�at` •.. �e��'fr=
Section 5: Post Construction Compliance ter
Record Drawings and Operating and Maintenance Manuals: = z : c
Project Title: Carmel United Methodist Church - addition & renovation g ��'V,,.�r g ..... 11`� Report date: 09103113
Data filename: C:1Documents and Settin sWP- Administrato6M Documents0rawin s112005 Gr� I t�, ^ ^. eck • CUMC
addition_2013- 09- 03,cck + tIHl1 Page 5 of 6
❑ 1 Construction documents with record drawings and operating and maintenance manuals provided to the owner
Lighting Designer or Contractor Name
Signature Date
Project Tine: Carmel United Methodist Church - addition & renovation Report date: 09/03/13
Data Filename: C:1Documents and SettingMHP- AdministratoAMV Documents0rawings112005 Carmel UMC1COMCheck - CUMC
addition 2013 -09- 03.cck Page 6 of 6
6 COMIcheck Software Version 3.9.2
�( Inspection Checklist
Requirements: 100.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions " column is provided by the user in the COMcheck Requirements screen. For each requirement,
the user certifies that a code requirement will be met and how that is documented, or that an exception is being_ claimed. Where
compliance is itemized in a separate table, a reference to that table is provided.
F1 fHigh Impact (Tier 1 ) J 2 1 Medium Impact ('Pier 2) 3 1 Low Impact (Tier 3)
Project Title: Carmel United Methodist Church - addition & renovation Report date: 08!03113
Data filename: C:IDocuments and Settings\HP- AdministratorWy Documents\Drawings112005 Carmel Page 1 of 8
UMOCCIMCheck - CUMC addition 2013- 09- 03.cck
90.1 (2007)
Standard
Plan Review
Com- plies?
Comments/Assumptions
42.2
Plans and/or specifications provide all
❑Complies
Requirement will be met.
[PR1j'
information with which compliance can be
013aes Not Comply
determined for the building envelope and
❑Not Observable
Location on plans /spec: A201 - A205, A401, A402, A501
document where exceptions to the standard
❑Not Applicable
are claimed.
4.2.2
Plans, specifications. and/or calculations
❑Complies
Requirement will be met.
[PR41'
provide all information with which
'E]poes Not Comply
compliance can be determined for the
❑Not Observable
Location on plans /spec: E201 - E203
lighting and electrical systems and
❑Not Applicable
equipment and document where exceptions
to the standard are claimed. Information
provided should include interior lighting
power calculations, wattage of bulbs and
ballasts, transformers and control devices.
8.4.1.1.
Plans. specifications, and /or calculations
❑complies
Requirement will be met.
8.41.2
provide all information with which
❑Does Not Comply
[pR612
compliance can be determined for the
❑Not Observable
Location on plans /spec: E201 - E203
electrical systems and equipment and
[]Not Applicable
document where exceptions are claimed
Feeder connectors sized in accordance
with approved plans and branch circuits
sized for maximum drop of 3 %.
Additional CommentslAssumptions:
111 High Impact (Tier 1) 1 2 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Carmel United Methodist Church - addition & renovation Report date: 09103/13
Data filename: C:\Documents and Settings\HP- Administrator\My DocumentslDrawings112005 Carmel Page 2 of 8
UMCICOMCheck - CUMC addition 2013- 09- 03.cck
90.1 (2007)
Standard
Footing 1 Foundation Inspection
Plans Verified Field Verified
Value Value
Complies? CammentsiAssutnptions
5.5.3,3
Below -grade wall insulation R- value. R-
R-
❑Complies See the Eoovekipe. Assemblies fable
[FO11'
❑Does Not Comply for values.
5.8.1 T3
Insulation in contact with the ground
❑Complies Requirement will be met.
[]Not Observable
has —0.3% water absorption rate per
❑Does Not Comply
❑Not Applicable
5.5.3.5
Slab edge insulation R- value. R-
R-
❑Complies See the Envelope Assemblies fable
[F031'
E] Unheated
[:] Unheated
❑Does Not Comply for values-
❑ Heated
❑ Heated
❑Not Observable
❑Not Applicable
5.5.3.5
Slab edge insulation depthllength. ft
ft ❑Complies See the Envelope Assemblies table
[FO51"
❑Does Not Comply , for values.
❑Not Observable
❑Not Applicable
5.8.1 T3
Insulation in contact with the ground
❑Complies Requirement will be met.
[F07j'
has —0.3% water absorption rate per
❑Does Not Comply
ASTNI 0272-
❑Not observable Location on planslspec: does
❑Not Applicable not apply
Additional Comments /Assumptions:
1 1 High Impact (Tier 1 ) 1 2 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3}
Project Title: Carmel United Methodist Church - addition & renovation Report date: 09/03/13
Data filename: C:0ocuments and SettingslWP- AdministratorWy Documents0rawingsl12005 Carmel Page 3 of 8
UMCICDMCheck - CUMC addition 2013- 09- 03.cck
90.1 (2007)
Standard
Framing ! Rough-In Inspection
Plans Verified
Valera
Field Verified
Value
Complies?
CorrfinentelAssumptlona
5.4.32
Factory -built fenestration and doors
Fenestration
Fenestration ❑Complies Requirement will he met.
[FR113
are labeled as meeting air leakage
cfMM2
cfmlft2 ❑Does Not Comply
requirements.
Doors
Doors ❑Not Observable Location on plansispec: Does
cfmlft2
cfmlff2 ❑Not Applicable not apply.
5.4.3.4
Vestibules are installed where
❑Complies Exception: Doors not intended
[FR413
building entrances separate
❑Does Not Comply to be used as a building
conditioned space from the exterior,
❑Not Observable entrance.
and meet exterior envelope
❑Not Applicable
requirements. Doors have self - closing
devices, and are 7 ft apart.
5.5.4.3a
Vertical fenestration U- Factor.
U-
U- ❑Complies See the Envelope Assemblies table
[FR81'
ElDoes Not Comply for values.
❑Nat Observable
❑Not Applicable
5.5.4.3b
Skylight fenestration U- Factor.
U-
U- ❑Complies see the Envelope Assemblies table
[FR911
❑Does Nat Comply for values.
❑Nat Observable
❑Not Applicable
5.5.4.4.1
Vertical fenestration SHGC value.
SHGC: _
SHGC: ❑ Complies See The Envelope Assemblies table
[FR1611
❑Does Not Comply for values.
[]Not Observable
[]Not Applicable
5.5.4.4.2
Skylight SHGC value.
SHGC:
SHGC: ❑Complies See the Envelope Assemblies table
[FR1111
❑Does Not Comply for values.
❑Not Observable
❑Not Applicable
5.8.2.1,
Fenestration products rated in
❑Complies Exception: Default values are
5.82.4
accordance with NFRC.
❑Does Not Comply used_
[FR1212
❑Not Observable
❑Not Applicable
5.8.2.2
Fenestration products are certified as
❑Complies Exception: The Installer or
[FR13]1
to performance labels or certificates
❑Does Not Comply supplier has provided certification
provided.
❑Nat Observable listing U- factor. SHGC, and air
❑Not Applicable leakage rate.
5.8.2.3,
U- factor of opaque doors associated
U-
U- []Complies See (he Envelope Assemblies table
5.5.3.6
with the building thermal envelope
❑ Swinging
Swinging ❑Does Not Comply for values.
[FR14]2
meets requirements.
❑ Nonswinging
® Nonswinging []Not observable
❑Not Applicable
Additional CommentslAssumptions:
1 Hlgh Impact (Tier 1 ) 2 1 Medium Impact (Tier 2) 1 3 Low Impart (Tier 3)
Project Title: Carmel United Methodist Church - addition & renovation Report date: 09103/13
Data filename: C :\Documents and Settings\HP- AdministratorWy Documents \Drawings\12005 Carmel Page 4 of 8
UMCICOMCheck - CUMC addition 2013- 09- 03.cck
90.1 (2007)
Standard
Rough -In Electrical Inspection
Complies?
CommentslAssumptions
9.4 1.1
Automatic controls to shut off all building
❑Complies
Requirement will be met
[EL1]2
fighting installed in buildings X5,000 ft2.
❑Does Not Comply
❑Not Observable
Location on plans/spec: E201 - Electrical General Notes
❑Not Applicable
9.4.1.2
Independent lighting controls installed per
❑Complies
Requirement will be met.
[EL2]2
approved lighting plans and all manual
❑Does Not Comply
controls readily accessible and visible to
❑Not Observable
Location on planslspec: E201 - E203
occupants.
❑Not Applicable
9.4.1.4
Separate lighting control devices for specific
❑Complies
Requirement will be met.
[EL411
uses installed per approved lighting plans.
❑Does Not Comply
❑Not Observable
Location on planslspec: E201 - E203
❑Not Applicable
9.4.2
Ballasted one and three lamp fixtures with
❑Complies
Exception: Electronic high - frequency ballasts,
[EL511
>30 WAamp have two lamp tandem wired
❑Does Not Comply
ballasts when n =2 fixtures in same space
❑Not Observable
on same control.
❑Not Applicable
9.4.3
Exit signs do not exceed 5 watts per face.
❑Complies
Requirement will be met.
[EL6]1
❑Does Not Comply
❑Not Observable
Location an planslspec: E201 - schedule
❑Not Applicable _
9.6.2
Additional interior lighting power allowed for
❑Complies
Requirement will be met.
[EL$]1
special functions per the approved lighting
❑Does Not Comply
plans and is automatically controlled and
❑Nat Observable
Location an planslspec: Does not apply.
separated from general lighting.
❑Mot Applicable
Additional CornmentslAssurttptions:
1 1 High Impact (Tier 1) 12 1 Medium Impact (Tier 2) 13 1 Low Impact (Tier 3)
Project Title: Carmel United Methodist Church - addition & renovation Report date: 09/03/13
Data filename: C:0oculnents and SettingslHP- AdministratorWy Documents0ravvings112005 Carmel Page 5 of 8
UMC1COMCheck - CUMC addition 2013- 09- 03.cck
90.1 (2007)
Standard
Insulation Inspection
Plans Verified
Value
Field Verified
Value
Complies?
Comments/Assumptions
5.4.3.1
All sources of air leakage in the
❑Complies
Requirement will be met.
[IN1]'
building thermal envelope are sealed,
❑Does Not Comply
caulked, gasketed, weather stripped
❑Nat Observable
Location on planslspec: A4 01
or wrapped with moisture vapor-
❑Not Applicable
permeable wrapping material to
minimize air leakage.
5.5.3.1
Roof R- value. For some ceiling
R-
R- ❑Complies
See The Envelope Assemblies lable
[IN2]'
systems, verification may need to
❑ Above deck
[] Above deck ❑Does Not Comply
for values,
occur during Framing Inspection.
❑ Metal
❑ Metal ❑Not Observable
❑ Attic
❑ Attic ❑Not Applicable
5.5.3.2
Above -grade wall insulation R- value.
R-
R- ❑Complies
see the Envelope Assemblies table
[ING]"
❑ Mass
❑ Mass ❑Does Not Comply
for values-
El Metal
❑ Metal ❑Not Observable
❑ steel
® Steel []Not Applicable
❑ Wood
❑ Wood
5.5.3 4
Floor insulation R- value.
R-
R- ❑ Complies
See fhe Envelope Assemblies table
[IN8]1
❑ Mass
❑ Mass []Does Not Comply
fpr values.
❑ steel
❑ steel ❑Not Observable
❑ Wood
❑ Wood ❑Nat Applicable
5.8.1.1
Building envelope insulation is labeled
❑Complies
Requirement will be met.
[IN1012
with R -value or insulation certificate
❑Does Not Comply
providing R -value and other relevant
❑Not Observable
data.
❑Not Applicable
5.8.1.4
Eaves are baffled to deflect air to
DComplies
Requirement will be met.
[IN11]2
above the insulation.
❑Does Not Comply
❑Not Observable
Location on planslspec: Does
❑Not Applicable
not apply. No new eaves for
alterations.
5.8.1.5
Insulation is installed in substantial
❑Complies
Requirement will be met.
[IN12]2
contact with the inside surface
❑Does Not Comply
separating conditioned space from
' ❑Not Observable
Location on planslspec: A461
unconditional space.
❑Not. Applicable
5.8.1.6
Recessed equipment installed in
❑Complies
Requirement will be met.
[IN13]2
building envelope assemblies does
❑Does Not Comply
not compress the adjacent insulation.
;❑Not Observable
;❑Not Applicable
5.8.1.7
Exterior insulation is protected from
❑Complies
Requirement wilt be met.
[IN14]2
damage with a protective material.
❑Does Not Comply
Verification for exposed foundation
[]Not Observable
Location on plans/spec- Does
insulation may need to occur during
❑Not Applicable
not apply to alteration.
Foundation Inspection,
5.8.1.7.1
Attics and mechanical rooms have
❑Complies
Requirement will be met.
[IN15]2
insulation protected where adjacent to
❑Does Not Comply
attic or equipment access.
[]Not Observable
Location on planslspec: Does
❑Not Applicable
not apply to this alteration.
5.8.1.7.2
Foundation vents do not interfere with
❑Complies
Requirement will be met.
[IN18]2
insulation.
❑Does Not Comply
❑Not Observable
Location on planslspec: Does
❑Not Applicable
not apply to this alteration.
Additional CommentslAssumptions:
1 High Impact (Tier 1 ) 12 1 Medium Impact (Tier 2) 13 Low Impact (Tier 3) I
Project Title: Carmel United Methodist Church - addition & renovation Report date: 09/03113
data filename: C: Documents and Settings\HP- AdministratorWy Qocuments0rawings112005 Carmel Page 6 of 8
UMCICOMCheck - CUMC addition 2013- 09- 03.cck
111 High Impact (Tier 1 ) 12 1 Medium Impact (Tier 2) 1 s 1 Low Impact (Tier 3) 1
Project Title: Carmel United Methodist Church - addition & renovation Report date: 03/03113
Data ftlename: CADocuments and Settings\HP- Administrator\My DocumentsOrawings112005 Carmel Page 7 of 8
UMCICOMCheck - CUMC addition 2013- 09- 03.cck
90.1 (2007),
Standard
Final Inspection
Complies?
CommentslAssumptions
5-4.33
Weatherseals installed on all loading dock
❑Complies
Exception: Requirement does not apply.
(Fill'
cargo doors in Climate Zones 4 -8.
[]Does Not Comply
[]Not Observable
[]Not Applicable
81.1
Furnished as -built drawings for electric
[]Complies
Requirement will be met.
[FI16]3
power systems within aft days of system
[]Does Not Comply
acceptance.
❑Not Observable
❑Not Applicable
8.7.2
Fumished O &M instructions for systems
❑Complies
Requirement will be met.
[FI17]3
and equipment to the building owner or
❑Does Not Comply
designated representative.
❑Not Observable
❑Not Applicable
9.2.2.3
Interior installed lamp and fixture lighting
❑Complies
See the Interim Lrghrrng fixture schedufe for values.
[F 1181'
power is consistent with what is shown on
❑Does Not Comply
the approved lighting plans, demonstrating
❑Not Observable
proposed watts are less than or equal to
[]Not Applicable
allowed watts.
Additional Comm entslAssumptions:
1 High Impact (Tier 1 ) 2 1 Medium Impact (Tier 2) 3 Law Impact (Tier 3)
Project Title: Carmel United Methodist Church - addition & renovation Report 09/03/13
Data filename: C:1Documents and SettingslHP- AdministratorWly Documents0rawingsl12005 Carmel Page 8 of 8
UMCICOMCheck - CUMC addition 2013- 09- 03.cck