HomeMy WebLinkAboutCOMcheck Lighting Report.pdfProject Title: Carmel Senior Living Report date: 07/11/13
Data filename: Z:\13\13.128\Design\13.128 Spectrum Carmel - Lighting.cckPage 1 of 6
COMcheck Software Version 3.9.2
Interior Lighting Compliance
Certificate
2009 IECC
Section 1: Project Information
Project Type: New Construction
Project Title : Carmel Senior Living
Construction Site:Owner/Agent:Designer/Contractor:
Carmel, INMichael Longfellow
Spectrum Retirement Communities, LLC
200 Spruce Street, #200
Denver, CO 80230
303-360-8812
mlongfellow@spectrumretirement.com
Kirk Gastinger
Gastinger Walker Harden Architects
817 Wyandotte
Kansas City, MO 64105
816 421 8200
kgastinger@designwithinsight.com
Section 2: Interior Lighting and Power Calculation
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B x C)
COMMON SPACES (Dormitory)50465150465
Total Allowed Watts =50465
Section 3: Interior Lighting Fixture Schedule
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
D
Fixture
Watt.
E
(C X D)
COMMON SPACES ( Dormitory 50465 sq.ft.)
Linear Fluorescent 1: A: WILLIAMS DI SERIES: 24" T8 17W: Electronic:2196346664
Linear Fluorescent 1A: A1: WILLIAMS DI SERIES: 48" T8 32W: Electronic:216641024
Linear Fluorescent 1B: A2: WILLIAMS DI SERIES: 48" T8 32W: Electronic:3596480
Compact Fluorescent 1: B: WILLIAMS PV60: Triple 4-pin 32W: Electronic:1267328544
Compact Fluorescent 2: B1: WILLIAMS PV60 WW: Triple 4-pin 32W: Electronic:11032320
Compact Fluorescent 3: B2: WILLIAMS PV60 SS: Triple 4-pin 32W: Electronic:1832256
Linear Fluorescent 2: C: WILLIAMS ASM SERIES: 48" T8 32W: Electronic:236642304
Linear Fluorescent 3: D: WILLIAMS SERIES 21: 48" T8 32W: Electronic:222641408
Linear Fluorescent 4: F: WILLIAMS SERIES 77: 48" T8 32W: Electronic:245642880
Linear Fluorescent 5: F1: WILLIAMS SERIES 22 2': 24" T8 17W: Electronic:223468
Linear Fluorescent 6: G: WILLIAMS SERIES 50: 48" T8 32W: Electronic:325962400
Linear Fluorescent 6A: G1: WILLIAMS SERIES 50: 48" T8 32W: Electronic:21064640
Linear Fluorescent 7: G2: WILLIAMS SERIES 50 22: 24" T8 17W: Electronic:3351153
Linear Fluorescent 7A: G3: WILLIAMS SERIES 50 22: 24" T8 17W: Electronic:213434
Compact Fluorescent 4: H: WILLIAMS PH75: Triple 4-pin 42W: Electronic:214841176
Compact Fluorescent 5: H1: WILLIAMS PH75: Triple 4-pin 32W: Electronic:2964576
Track lighting 1: K: LSI LN30: Wattage based on total luminaires00500500
Linear Fluorescent 8: L: WILLIAMS SERIES 29: 48" T8 32W: Electronic:242642688
Incandescent 1: O1: KICHLER 8405: Incandescent 60W:24120480
Compact Fluorescent 6: O2: AM. FL. LANCET: Quad 2-pin 13W: Magnetic:250261300
Incandescent 2: O3: CANDELLA C169: Incandescent 40W:61240240
Incandescent 3: O4: CANDELLA C169: Incandescent 60W:61360360
Incandescent 4: O5: KICHLER 3677: Incandescent 60W:4402409600
Incandescent 5: O6: MINKA-LAVERY: Incandescent 60W:11560900
Project Title: Carmel Senior Living Report date: 07/11/13
Data filename: Z:\13\13.128\Design\13.128 Spectrum Carmel - Lighting.cckPage 2 of 6
Incandescent 8: O7: KICHLER 3475: Incandescent 100W:19100900
Linear Fluorescent 9: P: WILLIAMS SERIES 16: 24" T8 17W: Electronic:3251102
Incandescent 9: Q: PROGRESS P2781: Incandescent 60W:3101801800
Incandescent 7: W: HUBBELL VAPORTITE: Incandescent 150W:13150450
Total Proposed Watts =48247
Section 4: Requirements Checklist
Interior Lighting PASSES: Design 4% better than code.
Lighting Wattage:
❑1.Total proposed watts must be less than or equal to total allowed watts.
Allowed Watts Proposed Watts Complies 50465 48247 YES
Controls, Switching, and Wiring:
❑2.Daylight zones under skylights more than 15 feet from the perimeter have lighting controls separate from daylight zones adjacent to
vertical fenestration.
❑3.Daylight zones have individual lighting controls independent from that of the general area lighting.
Exceptions:
❑Contiguous daylight zones spanning no more than two orientations are allowed to be controlled by a single controlling device.
❑Daylight spaces enclosed by walls or ceiling height partitions and containing two or fewer light fixtures are not required to have a
separate switch for general area lighting.
❑4.Independent controls for each space (switch/occupancy sensor).
Exceptions:
❑Areas designated as security or emergency areas that must be continuously illuminated.
❑Lighting in stairways or corridors that are elements of the means of egress.
❑5.Master switch at entry to hotel/motel guest room.
❑6.Individual dwelling units separately metered.
❑7.Medical task lighting or art/history display lighting claimed to be exempt from compliance has a control device independent of the control
of the nonexempt lighting.
❑8.Each space required to have a manual control also allows for reducing the connected lighting load by at least 50 percent by either
controlling all luminaires, dual switching of alternate rows of luminaires, alternate luminaires, or alternate lamps, switching the middle
lamp luminaires independently of other lamps, or switching each luminaire or each lamp.
Exceptions:
❑Only one luminaire in space.
❑An occupant-sensing device controls the area.
❑The area is a corridor, storeroom, restroom, public lobby or sleeping unit.
❑Areas that use less than 0.6 Watts/sq.ft.
❑9.Automatic lighting shutoff control in buildings larger than 5,000 sq.ft.
Exceptions:
❑Sleeping units, patient care areas; and spaces where automatic shutoff would endanger safety or security.
❑10.Photocell/astronomical time switch on exterior lights.
Exceptions:
❑Lighting intended for 24 hour use.
❑11.Tandem wired one-lamp and three-lamp ballasted luminaires (No single-lamp ballasts).
Exceptions:
❑Electronic high-frequency ballasts; Luminaires on emergency circuits or with no available pair.
Section 5: Compliance Statement
Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2009 IECC
requirements in COMcheck Version 3.9.2 and to comply with the mandatory requirements in the Requirements Checklist.
Project Title: Carmel Senior Living Report date: 07/11/13
Data filename: Z:\13\13.128\Design\13.128 Spectrum Carmel - Lighting.cckPage 3 of 6
Name - TitleSignatureDate
Kevin Zimmerman - Principal 7/11/13
Project Title: Carmel Senior Living Report date: 07/11/13
Data filename: Z:\13\13.128\Design\13.128 Spectrum Carmel - Lighting.cckPage 4 of 6
COMcheck Software Version 3.9.2
Exterior Lighting Compliance
Certificate
2009 IECC
Section 1: Project Information
Project Type: New Construction
Project Title : Carmel Senior Living
Exterior Lighting Zone: 3 (Other)
Construction Site:Owner/Agent:Designer/Contractor:
Carmel, INMichael Longfellow
Spectrum Retirement Communities, LLC
200 Spruce Street, #200
Denver, CO 80230
303-360-8812
mlongfellow@spectrumretirement.com
Kirk Gastinger
Gastinger Walker Harden Architects
817 Wyandotte
Kansas City, MO 64105
816 421 8200
kgastinger@designwithinsight.com
Section 2: Exterior Lighting Area/Surface Power Calculation
A
Exterior Area/Surface
B
Quantity
C
Allowed
Watts
/ Unit
D
Tradable
Wattage
E
Allowed
Watts
(B x C)
F
Proposed
Watts
Front Entrance (Entry canopy)1400 ft20.4Yes560585
Total of 16 Doors - (11) 3'-0", and (5) 6'-0" (Other door
(not main entry))
63 ft of door width20Yes12601629
Memory Care Garden (Plaza area)4100 ft20.16Yes656380
AL Entrance (Entry canopy)188 ft20.4Yes75253
Rear Patio (Plaza area)2750 ft20.16Yes440680
Sky Deck (Plaza area)670 ft20.16Yes107294
Front, East Parking (Parking area)49780 ft20.1Yes49783920
NW Parking (Parking area)3125 ft20.1Yes313275
West Parking (Parking area)5610 ft20.1Yes561275
Main Entrance, SW Drive (Driveway)5950 ft20.1Yes595550
West Drive (Driveway)4440 ft20.1Yes444550
NW Drive (Driveway)6525 ft20.1Yes653550
Garden Path (Walkway < 10 feet wide)500 ft of walkway length0.8Yes400910
Total Tradable Watts* =1104110851
Total Allowed Watts =11041
Total Allowed Supplemental Watts** =750
* Wattage tradeoffs are only allowed between tradable areas/surfaces.
** A supplemental allowance equal to 750 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Section 3: Exterior Lighting Fixture Schedule
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
D
Fixture
Watt.
E
(C X D)
Front Entrance ( Entry canopy 1400 ft2): Tradable Wattage
HID 2: U: WILLIAMS MH75: Metal Halide: Standard:14125500
HID 3: Y: AAL SCSQ: Metal Halide: Standard:118585
Total of 16 Doors - (11) 3'-0", and (5) 6'-0" ( Other door (not main entry) 63 ft of door width): Tradable Wattage
HID 4: R: INVUE ENV SERIES: Metal Halide: Pulse start:191251125
Compact Fluorescent 1: H2: WILLIAMS H75 SERIES: Quad 4-pin 42W: Electronic:2684504
Project Title: Carmel Senior Living Report date: 07/11/13
Data filename: Z:\13\13.128\Design\13.128 Spectrum Carmel - Lighting.cckPage 5 of 6
Memory Care Garden ( Plaza area 4100 ft2): Tradable Wattage
HID 4: R: INVUE ENV SERIES: Metal Halide: Pulse start:11125125
HID 5: S: TERON FAZIO: Metal Halide: Standard:1385255
AL Entrance ( Entry canopy 188 ft2): Tradable Wattage
HID 3: Y: AAL SCSQ: Metal Halide: Standard:118585
Compact Fluorescent 1: Quad 4-pin 42W: Electronic:2284168
Rear Patio ( Plaza area 2750 ft2): Tradable Wattage
HID 5: S: TERON FAZIO: Metal Halide: Standard:1885680
Sky Deck ( Plaza area 670 ft2): Tradable Wattage
HID 5: S: TERON FAZIO: Metal Halide: Standard:1385255
Compact Fluorescent 3: T: BEGA STEP LIGHT: Twin Tube 13W: Electronic:131339
Front, East Parking ( Parking area 49780 ft2): Tradable Wattage
HID 9: S1, S1A: Spaulding CR1: Metal Halide: Pulse start:164252550
HID 9b: S1B: Spaulding CR1: Metal Halide: Pulse start:11275275
HID 9c: S1C: Spaulding CR1: Metal Halide: Pulse start:21900900
HID 11: S2: Kim CFL: Metal Halide: Pulse start:1365195
NW Parking ( Parking area 3125 ft2): Tradable Wattage
HID 9b: S1B: Spaulding CR1: Metal Halide: Pulse start:11275275
West Parking ( Parking area 5610 ft2): Tradable Wattage
HID 9b: S1B: Spaulding CR1: Metal Halide: Pulse start:11275275
Main Entrance, SW Drive ( Driveway 5950 ft2): Tradable Wattage
HID 9b: S1B: Spaulding CR1: Metal Halide: Pulse start:12275550
West Drive ( Driveway 4440 ft2): Tradable Wattage
HID 9b: S1B: Spaulding CR1: Metal Halide: Pulse start:12275550
NW Drive ( Driveway 6525 ft2): Tradable Wattage
HID 9b: S1B: Spaulding CR1: Metal Halide: Pulse start:12275550
Garden Path ( Walkway < 10 feet wide 500 ft of walkway length): Tradable Wattage
HID 13: S3: Kim CB32: Metal Halide: Pulse start:11465910
Total Tradable Proposed Watts =10851
Section 4: Requirements Checklist
Lighting Wattage:
❑1.Within each non-tradable area/surface, total proposed watts must be less than or equal to total allowed watts. Across all tradable
areas/surfaces, total proposed watts must be less than or equal to total allowed watts.
Compliance:Passes.
Controls, Switching, and Wiring:
❑2.All exemption claims are associated with fixtures that have a control device independent of the control of the nonexempt lighting.
❑3.Lighting not designated for dusk-to-dawn operation is controlled by either a a photosensor (with time switch), or an astronomical time
switch.
❑4.Lighting designated for dusk-to-dawn operation is controlled by an astronomical time switch or photosensor.
❑5.All time switches are capable of retaining programming and the time setting during loss of power for a period of at least 10 hours.
Exterior Lighting Efficacy:
❑6.All exterior building grounds luminaires that operate at greater than 100W have minimum efficacy of 60 lumen/watt.
Exceptions:
❑Lighting that has been claimed as exempt and is identified as such in Section 3 table above.
❑Lighting that is specifically designated as required by a health or life safety statue, ordinance, or regulation.
❑Emergency lighting that is automatically off during normal building operation.
❑Lighting that is controlled by motion sensor.
Section 5: Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans, specifications
and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2009 IECC
requirements in COMcheck Version 3.9.2 and to comply with the mandatory requirements in the Requirements Checklist.
Project Title: Carmel Senior Living Report date: 07/11/13
Data filename: Z:\13\13.128\Design\13.128 Spectrum Carmel - Lighting.cckPage 6 of 6
Name - TitleSignatureDate
Kevin Zimmerman - Principal 7/11/13