Loading...
HomeMy WebLinkAboutCorrespondenceMarch 11, 2005 Mr. Dave Barnes Weihe Engineers, Inc. 10505 North College Avenue Indianapolis, IN 46280 JAMES BRAINARD, I¥~AYOR RE: Glen Oaks SubdMsion Construction Plans - Review #3 Dear Mr. Barnes: The City has received your comment letter and drawings dated February 28, 2005 based upon the City review of January 12, 2005. The comments from the City review have been satisfactorily addressed with the follovdng exceptions: COMMENTS-CONSTRUCTION PLANS 13. Sheet 4- Site Development Plan · Comment on previous review: "Please indicate a minimum flood protection grade (MFPG) for lots adjacent to 100-year flood source and flood routes. Define MFPG as minimum grade for any structure opening (door, window, window well, outside basement stair access, etc.)" Please add the requested definition to the plans. · Comment on previous review: "Please add minimum pad grades for ones that are indicated With asterisks." Should state something about lowest opening also on pads vdth asterisks. 14. Sheets 5, 6 & 7 - Street Plan and Profile · Comment on previous'review: "Please add the following note to each sheet: Minimum Cover for Pipe Crossings of CiO Streets For installation of Storm Mains, Water Mains, Sanitary Mains, Water Service Laterals, Sanitary Service Laterals under City streets, regardless of the jurisdiction of the utility, the minimum cover from the top of the installed pavement to the top of the installed pipe shall be the pavement section thickness (all bituminous and aggregate material above the subgrade) plus 1-0". If the standard practice of the utility that has jurisdiction over the installation has a more stringent cover requirement, the more stringent requirement shall govern." This note is not complete on the sheets. Please check all instances of this note for compliance with the above requirements. 15. Sheet 9 - Entrance Plan · Comment on previous review: "Please label colors (yellow or white) that the-varioUs lines in the channelization plan are to be." On entrance plan, please indicate 'white lane striping for the deceleration lane and double yellow for entire frontage. · Comment on previous review: "Please provide swale on east side of road to maintain drainage outside of area with curbing." · Comment on previous review: "The West Road right-of-way pavement section must be no less than: 1.5" H.A.C. #11 surface over 2" H.A.C. #8 binder over 3" H.A.C. #SD base over 7" #53 stone over 4" #2 stone." Revise detail on Sheet 28 to this section or call to discuss if we agreed upon a different section during a recent meeting. · Comment on previous review: "Please show installation of subsurface drains under gravel shoulder." Please add to West Road Improvement Section on Sheet 28. Also, subsurface drains are not indicated under shoulder north of entrance. 16. Sheet 10 - Traffic Control Plan · Comment on previous review: "Add note that signs are installed by City and require an Ordinance." Thank you for adding this note. Please clarify the note to be for permanent traffic control devices. 17. Sheet 13 - Storm Plan and Profile · Comment on previous review: "There is not sufficient cover over the storm sewer pipes at structures 721, '/22, 723 and 724. '['he City requires a minimum of one-foot of fill between the top of the pipe and the bottom of the aggregate course of the pavement section." Please edit granular DEPARTMENT OF ENGINEE[dNG Fax 317.571.2439 ONE CIVIC SQUARF., CARMEl, IN 46032 OFF[(;t.: 317.571.2441 E,xk\ll. engineering(O)ci.carmel.in.us backfill notes on profile for these structures to be specifically flowable fill. Also, please specifically indicate that these pipes shall be Class V RCP in lieu of the general note. You may leave the general note on the drawing. · Comment on previous review: "We have determined that several storm sewer structures are impossible to construct because the height of the precast concrete drainage structure is insufficient to accommodate the required pipe size and required minimum cover. These include structures 704, 721,722, 723,724, and 737." The Department is still of the opinion that these structures cannot be constructed and that the frames will rest at or near the top of the pipe. Please confirm with the County that this is acceptable. · Comment on previous review: "Please add the following note to each sheet: Minimum Cover for Pipe Crossings of City Streets For installation of Storm Mains, Water Mains, Sanitary Mains, Water Service Laterals, Sanitary Service Laterals under City streets, regardless of the.jurisdiction of the utility, the minimum cover from the top of the installed pavement to the top of the installed pipe shall be the pavement section thickness (all bituminous and aggregate material above the subgrade) plus 1-0". If the standard practice of the utility that has jurisdiction over the installation has a more stringent cover requirement, the more stringent requirement shall govern." Note is incomplete on sheets. Please edit such that the complete note is on each sheet. 18. Sheets 17 thru 22 - Sanitary Sewer Plan and Profile · Comment on previous review: "Please add the minimum cover note from the attached standard verbage to the water and sanitary details." The note is not complete. Please edit such that the complete note is on each sheet. 20. Sheet 28- Construction Details · Comment on previous review: "Please add the following text to the sidewalk detail notes: "Transverse joints shall be tooled or sawed to a depth of 'A of the walk thickness." Please proofread this note. It contains "wawed" for the word "sawed" and "thiskness" for the word "thickness." · Comment on previous review: "Please include Standard Patch Detail for street cuts." Please add this detail on Sheet 28. 21. Additional comments · Please delete the note related to full depth granular backfill for sanitary sewer laterals on Sheets 17 to 22 or reference the other note on the sheet that was added at the request of the City. · Please respond in writing and address the drainage review comments. These comments represent the Department of Engineering's third review of the construction plans for this project. We request that all responses to our comments be provided in writing. Failure to provide written responses may result in delay of the review process. It is critical that this office be made aware of all modification made on the plans being re-submitted, particularly if any such changes are considered "new" or fall outside of our previous reviews. Please provide revised plans indicating all revisions. Please notify us of any changes and specifically state any changes, including changes resulting from Plan Commissio_n, Special Studies or other committee meetings. All bonds and perfom'~ance guarantees (if required) must be posted prior to Engineering Department approval. Also, Board of Public Works and Safety approval and any other governing agency approvals (if required) must be obtained prior to Engineering Department approval. The Department of Engineering reserves the right to provide additional comments based on subsequent reviews. If you have questions, please contact me at 571-2441. Sincerely, G , Jr., P.E. Assistant City Engineer Department bf Engineering Cc.' Jon Dobosiewicz, Department of Community Services John Duffy, Director Carmel Utilities Paul Pace, Distribution Greg Hoyes, Hamilton County Surveyor's Office John South, Hamilton County Soil & Water Conservation District (w/o encl.) John Edwards, Langston Development Project File Copy Engineering Department Review S :~DH I LL~ ROJ REV05\GLENOAKSSUB DWI S ION REV3 *W'EI H E NGI N EERS, I NC. ~';'i-I~'""E'N'G[NeERS'i"'"~ND SURVEYORS, LAND PLANNERS, LANDSCAPE ARCHITECTS LETTER OF TRANSMITTAL To: City of Carmel Engineering Department Glen Oaks Subdivision One Civic Square Job #: Weihe #W03-0984 "%,:< Carmel, Indiana 46032 Date: February 9, 2005 Phone: 571-2441 Attn: Gary Duncan Fax: We are sending you [2] Attached V! Under separate cover via the following items: V1 Shop Drawings V1 Prints V1 Copy of Letter [2] Product Data F1 Specifications [23 Meeting Minutes VI Samples V1 Change Order(s) [23 Inspection Report [2] [3 Sketches/Drawings [23 Application(s) for Payment Sets Document Document Description Copies Date Number 1 Review letters (Carmel Fire Dept/Carmel Clay Schools) rhese are transmitted as indicated below: F1 Approved F1 Approved as Noted [2] Not Approved, Revise and Resubmit D Action Not Required [3 Action Indicated on Item Transmitted [3 For Signature. Remm .... Copies to Us [3 For Your Review or Use V1 For Your Review & Comment [2] As Requested Fl For Your Records [23 For Your Approval Remarks: Gary: I have contacted the above agencies concerning the cul-de-sac's within the above project and asked for any comments which either body might have pertaining to the project. I am enclosing the review letters from each department as confirmation that this is not an issue with them. Please inClude this information with your fries. Thank you.- Dave Barnes cc: Mr. Jon Dobosiewicz, Carmel Community Services Dave Barnes, Weihe Engineers, Inc. ALLAN H. WEIHE... P.E,, L.S, - PRESIDENT 0505 NORTH COLLEGE; AVENUE INDIANAPOLIS, INDIANA 462:80 (317) Ei46-6611 (800) 452-6408 FAX: (317)843q3546 Jan 12 2005 2:19PM HP LRSERJET 3200 p.2 City of Carmel Fire Department Headquarters 2 CiViC SQUARE' CARMEL, INDIANA 46032 Voice (317) 571-2600 Fax (317) 571-2615 Fire Prevention Bureau Dave Barnes Wethe Engineering 10505 N, College Ave. Indianapolis, IN 46280 RE: Glen Oaks Subdivision LETTER OF APPROVAL The undersigned has reviewed the proposed plans for . Glen Oaks Subdivision and has approved the plans subject to the following: . . Will this project include an amenity.building? If so, our office will request the installation of a of a Knox Box for emergency access. An application for the Knox box can be obtained through our office. Our office, in conjunction with the Department of Community Development, are requesting in newJy platted subdivisions, fire hydrant makers be Installed in the street pavement perpendicular to the fire hydrant, This will allow the fire department to more easily spot fire hydrants during an emergency. Our office is requesting a decrease in size of the main entrance boulevard/sland off West Road. ! am sending you our department's apparatus specifications for your use in designing a more navigable entrance for emergency access~ 4. o . Please respond to the above noted condition(s) in writing and submit to our off.me prior to the scheduled Technical Advisory Meeting for this project. Date: Janua~ 12. 200~ By: Gary Hoyt, Fire Marshal Carmel Fire Department Carmel Clay Schools- Continuing Excellence in Education February 4, 2005 Dave Barnes Weihe Engineers, Inc. 10505 North College Ave. Indianapolis, IN 46280 RE: Glen Oaks Subdivision Dear Mr. Barnes: I have received and reviewed the site plan for the above referenced project. I have no comments on the proposed development. Carmel Clay Schools will be able to service this development for pupil transportation to Carmel Clay Schools. Sincerely, Ron Farrand, Jr. Director of Facilities and Transportation C; T.A.C.- Dept. of Community Services - Carmel Facilities & Transportation Department - 5185 East 131' Street, Carmel, IN 46033 317/844-8207- Fax 317/571-9659 Carmel Clay Schools Education Continuing Excellence in February 4, 2005 Dave Barnes Weihe Engineers, Inc. 10505 North College Ave. Indianapolis, IN 46280 RE: Glen Oaks Subdivision Dear Mr. Barnes: I have received and reviewed the site plan for the above referenced project. I have no comments on the proposed development. Carmel Clay Schools will be able to service this development for pupil transportation to Carmel Clay Schools. Sincerely, Ron Farrand, Jr. Director of Facilities and Transportation C~ T.A.C.- Dept. of Community Services - Carmel Facilities & Transportation Department - 5185 East 131~ Street, Carmel, IN 46033 317/844-8207 - Fax 317/571-9659 January 12, 2005 Mr. Dave Barnes Weihe Engineers, Inc. 10505 North College Avenue Indianapolis, IN 46280 CI EL J.aMES BR)dNARD, MAYOR RE: Glen Oaks Subdivision Construction Plans- Review #2 (1't Review of ConstructiOn Plans) Dear Mr. Barnes: Thank you for submitting responses dated January 5, 2005 to the Department's June 15, 2004 primary plat review comments. The majority of the Department's comments were addressed and incorporated into the current secondary plat set. Any outstanding items related to the Department's review of the primary plat are incorporated in this review. We have reviewed the construction plans submitted for this project for the January 19, 2005 Technical Advisory Committee meeting. We offer the following comments: GENERAL INFORMATION 1. The project site is located within current City of Carmel Corporate Limits. 2. Jurisdictions: · Streets and Right of Way (Interior Streets and West Road) - City of Carmel. · Water- City of Carmel. · Sanitary Sewers - Clay Township Regional Waste District · Storm Sewers/Drainage - Hamilton County Surveyor's Office / City of Carmel. · Regulated/Legal Drains- Hamilton County Surveyor's Office. 3. Board of Public Works and Safety Requirements: · Water Availability · If an irrigation system is planned for this development, additional Board of Public Works and Safety approval will be required. This also applies to planned swimming pools and/or clubhouse. · Temporary Construction Entrance (if applicable and if located at a location other than planned permanent entrances) · Please be advised that any open cuts of dedicated streets will require separate Board of Public Works attd Safety approval (if the sanitary sewer under West Road is to be att open cuO. · Any permanent improvement (including irrigation systems) to be installed within dedicated right of way or dedicated easements. This approval would require a Consent to Encroach Agreement between the Owner and the City of Carmel. · Secondary Plat approval. Att), subntission to the Board requires prior approval by the Carntel Clay Plan Commission attd/or the Board of Zoning Appeals (if applicable) attd completio~t of review by the Technical Advisory Co[nmittee. All written requests to be placed on the Board's agenda must htclude the appropriate Docket Number attd the date (or dates) of approval by the Phtn Conttnission attcl/or the Board of Zonittg Appeals (if applicable). 4. T.A.C. Review/Drawings submitted for approval: We request that all comments and comment letters generated by this office be answered in writing and be accompanied by a drawing reflecting requested revisions. Final drawings will not be approved for construction until all Engineering Department and Utility Department issues have been resolved. The design engineer must certify all drawings submitted for final approval. Because of the dual jurisdiction between the City of Carmel and the Hamilton County Surveyor, we will require a minimum of eight-sets of drawings for approval after all issues have been resolved. The drawings will be stamped as approved and will be signed by the City Engineer and the Director of Carmel Utilities. The eight-sets will then be sent to the Hamilton County Surveyor's Office for approval and signatures. Three approved sets are to be returned to the City of Carmel. The Hamilton County Surveyor's Office xvill retain two-sets. The Developer, the Engineer and the Contractor will each receive one-set. DEPARTMENT OF ENGINEERING ONE CIVIC SQUARE, CARMEl, IN 46032 OFF,CF. 317.571.2441 E.~x~L engineeringO'~:ci.carn-tel.in.us Fax 317.571.2439 5. Please be advised that any installation of signs, walls, irrigation systems, etc. within dedicated right of way or dedicated easements will require a Consent to Encroach A~eement with the City of Carmel's Board of Public Works and Safety. 6. Carmel Utilities should be provided drawings for review of water issues. They will provide a separate review regarding these issues. Please assure that Carmel Utilities receive all drawing subMissions/revisions for their review. 7. Carmel Utilities does not subscribe to "Holey Moley" and should be contacted directly for all water main locations. 8. The following items were provided with our original review and will not be resubmitted unless requested: · Subdivision Project Approval Procedures · Performance Release Procedure · Subdivision Building Permits · Permit Data, Contacts, etc. · Signage Requirements BONDING REQUIREMENTS 9. Individual Performance Guarantees will be required for the following subdivision improvements: · Streets · Curbs · Water Mains · Street Signs · Sidewalks (builders lot sidewalks and common area/perimeter right of way sidewalks may be bonded separately). Sanitary Sewers are under the jurisdiction of he Clay Township Regional Waste District. The Hamilton County Surveyor's Office will require bonding for stoma sewers and monuments & markers. We will not require duplicated bonding. The amount of the Performance Guarantee is based upon a certified Engineer's Estimate for 100% of the cost of labor and materials to construct the individual improvements, to be provided by the design engineer. Please provide detailed Engineers Estimates for each improvement including unit costs, quantities, materials and types of materials, etc. Upon completion and release of individual Performance Guarantees, a three-year Maintenance Guarantee ,,viii be required. The Maintenance Guarantee amount is based upon 15% of the Performance amount for Streets and Curbs and 10% of the Performance amount for all other improvements. Performance Guarantees may be Performance or Subdivision Bonds, Irrevocable Letters of Credit or Cashier's/Certified/Official Checks. Please reference previous enclosures for more detailed explanation of our procedures. AVAILABILITY AND CONNECTION FEES 10. Availability (acreage) Fees must be paid after all other Engineering Department requirements have been satisfied and prior to start of construction activities. Availability Fees are based upon total platted acreage for the development at the rate orS1,010.00 per acre for Water Availability. Based upon the primary plat that was submitted previously, the following current Availability Fees would apply: Water - 42.7 Acres ~ $1,010.00/Acre = $ 43,127.00 Connection Fees are currently $1,310.00 for water per single-family residence. Connection Fees are paid when the infrastructure has been completed, satisfactory test results obtained and the subdivision has been released for permits. Connection Fees are paid on a per-lot basis. · If an irrigation systetn isplanned isplannedfor this, or arty future section of the development, additional Water Connection Fees will be assessed based ttpolt the recommendation of the Director of Carm el Utilities. COMMENTS-CONSTRUCTION PLANS I 1. When will a secondary plat be submitted for review? 12. Sheet 3 - Site Development Plan · We believe unnecessary problems are created by the extremely wide median at the entrance. This xvill be discussed further in the Entrance Plans, Sheet 9 comments. Please confirm with the Carmel Clay' School Transportation Department and the Carmel Fire Department that the 38-foot radii at the cul-de-sac terminal ends are sufficient. The Department of Engineering will require that you obtain written confirmation from these agencies and provide said confirmations to us prior to approval of the plans. f 13. Sheet4- · · · · · · 14. Sheets 5, 15. Sheet 9- · The City prefers that common areas not be located within medians. This complicates maintenance of the right of way. · Please reduce the portions of Dolan Way on either side of the median to be eighteen feet maximum width. Site Development Plan The Department of Engineering will not approve construction drawings for this subdivision until the easement for the off-site sanitary has been secured. · Please make any revisions necessary to locate all portions of the sanitary sewer outside of the right- of-way limits. For the sanitary run between structures 11 and 12, relocate structure 12 so main is out of the right-of-way. Relocate the run between structures 14 and 15 so that this is out of the right-of-way. The sanitary sewer betWeen structures 26 and 22 needs to be realigned and possibly a structure added to get this out of the right-of-way. · Please relocate storm structure 737 to opposite side of Letts Circle to avoid street crossing. Revise downstream piping as needed. · ~Vhat is the feature that looks like a culvert with headwallsjust south of lots 12 and 13.9 Is it proposed or existing and where are the details for this structure.9 °Please provide a thirty-foot b-b pavement width for all streets per City standard. ° We assume the forty-foot right-of-way shown for Letts Circle and sidewalk on only one side of Letts Circle is acceptable to the Department of Community Services. ° A flood route has been indicated, but has been labeled incorrectly in the legend. Please label as FLOOD ROUTE rather than EMERGENCY SPILLWAY. ° Please indicate a minimum flood protection grade (MFPG) for lots adjacent to 100-year flood source and flood routes. Define MFPG as minimum grade for any structure opening (door, window, window well, outside basement stair access, etc.) Please add minimum pad grades for ones that are indicated with asterisks. Please label swale slopes (1% minimum). Swales cannot exceed 400' in length before draining to an inlet. Please provide pond spillway on dry detention basin. Please label bottom elevation, 2-yr elevation, and 10-yr elevation of the pond. Please provide drainage arrows for the-lots and swales. 6 & 7 - Street Plan and Profile Please include curve data for each horizontal curve. Please include curb return radii for street intersections. Please show water mains and sanitary on profiles. Please add the following note to each sheet: Minimum Cover for Pipe Crossings of City Streets For installation of Storm Mains, Water Mains, Sanitary Mains, Water Service Laterals, Sanitary Service Laterals under City streets, regardless of the jurisdiction of the utility, the minimum cover from the top of the installed pavement to the top of the installed pipe shall be the pavement section thickness (all bituminous and aggregate material above the subgrade) plus 1-0". If the standard practice of the utility that has jurisdiction over the installation has a more stringent cover requirement, the more stringent requirement shall govern. Entrance Plan Thank you for adding the auxiliary lanes and for accommodating a left turn lane into the development. The Department understands that the entrance island is being configured to protect the existing trees, however, after reviewing this with Mike McBride, the entrance configuration will not be approved as shown. Please provide a left turn bay for exiting traffic located in front of the entrance island. The median should be a maximum of ten feet wide and the lane on each side of the median should be a maximum of eighteen feet wide and all lanes should be perpendicular to West Road. · Please label colors (yellow or white) that the various lines in the channelization plan are to be. · The cross-hatching on the south side of the plan is angled in the correct direction while the cross- hatching on the north side is not angled in the correct direction. Please refer to the Indiana Manual of Uniform Traffic Control Devices. · Auxiliary lanes will need to be revised after entrance width and geometry is revised. · Please contact the City to arrange a meeting to review the lane shift configuration on West Road. Lane shifts are too short. · Please'add a note to sawcut the existing pavement edge for auxiliary lanes and widening. · Please provide swale on east side of road to maintain drainage outside of area with curbing. · Due to new County requirements, the on-site detention pond must be sized to accommodate detention of the full thoroughfare right-of-way across the property frontage. · Please add note for all pavement markings to be thermoplastic. · Please indicate the proposed West Road right-of-way paving areas with hatching. A separate hatch should be provided for resurfacing and new pavement. · Please show resurfacing of entire mainline across frontage or to limits of auxiliary lanes, whichever is greater. · The West Road right-of-way pavement section must be no less than: 1.5" H.A.C. #11 surface over 2" H.A.C. #8 binder over 3" H.A.C. #SD base over 7" #53 stone over 4" #2 stone. · Please show installation of subsurface drains under gravel shoulder. 16. Sheet 10 - Traffic Control Plan · Add note that signs are installed by City and require an Ordinance. 17. Sheet 13 - Storm Plan and Profile · There is not sufficient cover over the storm sewer pipes at structures 721,722, 723 and 724. The City requires a minimum of one-foot of fill between the top of the pipe and the bottom of the aggregate course of the pavement section. · There are several runs of storm sewer pipe with slopes that are considered too steep according to City standards. The runs that are most extreme are 738-739,749-754, 701-706, and 764-765. · We have determined that several storm sewer structures are impossible to construct because the height of the precast concrete drainage structure is insufficient to accommodate the required pipe size and required minimum cover. These include structures 704, 721,722, 723,724, and 737. · Please match pipe crowns or demonstrate that the pipe crowns not being matched has no negative impact on the hydraulic grade line. · Please add the following note to each sheet: Minimum Cover for Pipe Crossings of City Streets For installation of Storm Mains, Water Mains, Sanitary Mains, Water Service Laterals, Sanitary Service Laterals under City streets, regardless of the jurisdiction of the utility, the minimum cover from the top of the installed pavement to the top of the installed pipe shall be the pavement section thickness (all bituminous and aggregate material above the subgrade) plus 1-0". If the standard practice of the utility that has jurisdiction over the installation has a more stringent cover requirement, the more stringent requirement shall govern. · Please show subsurface drain between structures 713 and 712 on the profile to ensure no conflict. 18. Sheets 17 thru 22 - Sanitary Sewer Plan and Profile · What do the abbreviations "G.O." represent? · Please move water valves outside the pavement. · Please add the following note: "THERE ARE TO BE NO WATER VALVES OR MANHOLES WITHIN THE PAVEMENT, CURBS, OR SIDEWALKS." · Please add the backfill requirements for water and sanitary from the attached standard verbage to the General Notes of water and sanitary sheets. Please revise any details, notes, or specifications. · Please add the minimum cover note from the attached standard verbage to the water and sanitary details. 19. Sheets 26 and 27 - Landscape Plan · Please remove the Landscape Plan from this set of drawings. Approval of the Landscape Plan does not come from the Department of Engineering. 20. Sheet 28 - Construction Details · On the Curb Inlet Detaill why are 2" weep holes shown in the sides of the structure? Please explain the note regarding #2 Stone. · In the note: "SIDEWALK BUILT WITH DRIVEWAY SHALL BE MINIMUM THICKNESS OF 5" OR THICKNESS OF DRIVEWAY, WHICH EVER IS GREATER" please change the ~ thickness from 5" to 6." ' · Please add the following text to the sidewalk detail notes: "Transverse joints shall be tooled or sawed to a depth of IA of the walk thickness." · Please add the following text to the sidewalk detail notes: "The spacing of the transverse joints in sidewalk not to exceed 1.25 times the width of the sidewalk. In the Typical Section - Local Street detail, please change the dimension from the centerline to the back of curb from 14' to 15.' · Please add the following Asphalt Path Pavement Section Detail: 1" H.A.C. #11 surface on 2" H.A.C. #8 binder on 5" #53 stone. · Please add the following Subdivision Street Pavement Section Detail: 1.5 H.A.C. #1 lsurface on 2" H.A.C. #8 binder on 3" H.A.C. #SD base on 7" #53 stone. · Please add the note: "ALL PAVING TO BE COMPLETED IN ONE PAVING SEASON." · Please remove the Hamilton County subsurface drain detail and add the City of Carmel subsurface drain detail. · Please add the attached standard backfill verbage to the Sanitary Trench Details. · Please add the attached standard verbage to the RCP Trench Detail. Please revise details, specifications, and notes. · Please include Standard Patch Detail for street cuts. 21. Additional comments · Please indicate removal and replacement of the 27 x 42 corrugated metal pipe. The Hamilton County Surveyor's Office and Carmel Department of Engineering will conduct an inspection of this structure and determine if this requirement can be waived. · ADA ramps need to be reconfigured at intersections such that the ramps do not conflict with inlet grates. · Delete Details C-l, C-4, P-l, U-2, U-3, S-l, S-2, S-3 from Sheet 30. · Delete Drainage Swale Section from Sheet 28. · Please indicate the extension of all existing storm pipe crossings under West Road to accommodate widening, path, etc. and ensure that drainage system will function. These comments represent the Department of Engineering's initial review of the construction plans for this project. Please provide our office with a follow-up letter and revised plans indicating all revisions. We request that all responses to our comments be provided in writing. Failure to provide written responses may result in delay of the review process. The Department of Engineering reserves the right to provide additional comments based on subsequent reviews. It is critical that this office be made aware of all modification made on the plans being re- submitted, particularly if any such changes are considered "new" or fall outside of our initial review. Please notify us of any changes and specifically state changes. Please be aware that Board of Public Works and Safety approval is required for all pavement cuts, including new curbs. All bonds and performance guarantees (if required) must be posted prior to Engineering Department approval. Also, Board of Public Works and Safety approval and any other governing agency approvals (if required) must be obtained prior to Engineering Department approval. The plans have also been submitted to the City's consultant for drainage review. Comments from the drainage review will be forwarded to your office when the review is complete. If you have questions, please contact me at 571-2441. _Assistant 9ty~E_ngineer Departm~ht of Engineering Cc: · . John Duffy, Director Carmel Utilities (w/o encl.) Paul Pace, Distribution (w/o encl.) Greg Hoyes, Hamilton County Surveyor's Office (w/o encl.) John South, Hamilton County Soil 8,: Water Conservation District (w/o encl.) John Edwards, Langston Development Project File Copy Engineering Department Review S:\DHILL\PROJREV05\GLENOAKSSUBDIVISIONREV2 Via Fax: 317.843.0546 Original by mail January 18th, 2005 Dave Barnes Weihe Engineers, Inc. 10505 N. College Ave. Indianapolis, IN 46280 RE: Glen Oaks, Secondary Plat Application #05010001 SP Dear Mr. Barnes: This letter is in response to your secondary plat application for Glen Oaks Secondary Plat. The following issues must be resolved: The following must be indicated on the plat: o 2. 3. 4. 5. 6. 7. Date of last revision. Registered surveyor's signature, seal, and date. The right of way distance for Boxelder Court (sheet 4). Label all monumentation or indicate monumentation symbols on the legend. Rear and side setbacks for individual lots. Restrictions or covenants must be included. Please provide "key" maps for each sheet. Concerns and Comments are as follow: 1. Please provide details in regards to proposed signage, fencing, and entry features. 2. Please ensure all landscape plantings are outside of drainage easements. 3. A copy of the landscape plan approval letter/e-mail from the Urban Forester is required prior to plat approval and signature. Please provide lighting fixture and location details. All lighting should be indicated on a plan sheet. . Please wait to submit a revised primary plat until after the Technical Advisory Committee (TAC) has met on this application. The resubmitted plat should include edits addressing the above comments along with any requirements that arise from the TAC meeting. Additional comments may be made after the requested revisions have been submitted. Matthew Griffin, A/CIa Planning Administrator Glen Oaks - SP Page 1 ONE CIVIC SQUARE CAP~MEL, INDIANA 46032 317/571-2417 One Civic Square Carmel, IN 4E032 (317) S71-~-4i 7 Fax'. (317) 571-2426 Fax Phone: ,, ,, CC: ,, 1-I Urgent //~' For Review I-1 Please Comment I:Zi Please Reply P/ease Recycle 'WEIH Gl RS, IN,C. N .NEE . CIVIL ENGINEERS, LAND SURVEYORS, LAND PLANNERS, LANDSCAPE ARCHITECTS LETTER OF TRANSMITTAL To-' City of Carmel Community Services Glen Oaks Subdivision/ One Civic Square Job #: Weihe #W030984 Carmel, Indiana 46032 Date: January 14, 2005 Phone: 571-2417 Attn: Mrs. Angelina V. Conn We are sending you V! Attached VI Under separate cover via the following items: [2] Shop Drawings [23 Prints U1 Copy of Letter [2] Product Data 1'3 Specifications F1 Meeting Minutes [3 Samples Fl Change Order(s) [3 Inspection Report F1 l-'l Sketches/Drawings F1 Application(s) for Pa ~ment [23 Sets Document Document Description [23 Copies Date Number 2 sets Requested Secondary Plat for Review These are transmitted as indicated below: [2] Approved Fl Approved as Noted F1 Not Approved, Revise and Resubmit ["I Action Not Required U! Action Indicated on Item Transmitted [3 For Signature. Return Copies to Us Fl For Your Review or Use Fl For Your Review & Comment Fl As Requested F1 For Your Records Fl For Your Approval Remarks: Angie: Enclosed are 2 review sets of the Secondary Plat requested for the above projec~ Please address any concerns to the undersigne& (Me). Thank you. -Dave B. CC: Dave Barnes, Weihe Engineers, Inc. ALLAN H. WEIHE,. P.E.. L$. - PRESIDENT 0505 NORTH COLLEGE AVENUE INDIANAPOLIS, INDIANA, 46280 (317) 846-66 i t (800) 452-6408 FAX: (317)843-0546 City of Carmel Fire Department Headquarters 2 CIVIC SQUARE CARMEL, INDIANA 46032 Voice (317) 571-2600 Fax (317) 571-2615 Fire Prevention Bureau Dave Barnes Weihe Engineering 10505 N. College Ave. Indianapolis, IN 46280 RE: Glen Oaks Subdivision LETTER OF APPROVAL The undersigned has reviewed the proposed plans for Glen Oaks Subdivision and has approved the plans subject to the following- . . Will this project include an amenity building? If so, our office will request the installation of a of a Knox Box for emergency access. An application for the Knox box can be obtained through our office. Our office, in conjunction with the Department of Community Development, are requesting in newly platted subdivisions, fire hydrant makers be installed in the street pavement perpendicular to the fire hydrant. This will allow the fire department to more easily spot fire hydrants during an emergency. Our office is requesting a decrease in size of the main entrance boulevard island off West Road. I am sending you our department's apparatus specifications for your use in designing a more navigable entrance for emergency access. , , . Please respond to the above noted condition(s) in writing and submit to our office prior to the scheduled Technical Advisory Meeting for this project. Date: January 12, 2005 By: Gary Hoyt, Fire Marshal Carmel Fire Department January 12, 2005 Dave Barnes Weihe Engineers, INC. 10505 N. college Avenue Indianapolis, IN 46280 RE: Glen Oaks Subdivision Dear Mr. Barnes: ! have received and reviewed the information for the above-mentioned project. At the present time, I see nothing in the plans that would hamper law enforcement efforts. If we can be of any further assistance to you, please contact us. Respectfully, Michael D. Fogarty Chief of Police MDF:vb CC: Dept. of Community Services (517) 571-2500 A Nationally Accredit~i~{~:Dforcement Agency F~ {5~17} 571-2512 81/13/2885 11'34 3177769628 HAMILTON CO SURVEYOR PAGE 81/84 Sanuary 12, 2005 Weihe Engineering, Inc. ATTN: Dave Barnes 10505 North Coil,ge Avenue Indianapolis, IN 46280 VIA FAC$IMIZE: 843-05~6 COl~lit Re: Glen Oaks SubdMsion Dear Mr. Barnes: We have reviewed the consmmtion plans sub~tted to the Hamilton, County Surveyor's Office on December 13, 2004 for this project and have the following comments: .This .proposed development will. be a Hamilton. County Regulatod Drain Subdivision, subject to approval of the Hamilton County Drainage Board. + Please submit the following procedural items to this office, petition for regulated subdivision, 2 outlet permits (Bellwood Drain), non-enforcement request for subdivision, engineer's estimate, and all associated bonds for 120% of construction cost. The applications are available on our website at llttp://www.¢o.hamilton, in.us, go to Departments, Surveyor, and Forms. 3. The proposed project DOI~S NOT fall in a Carmel Wellhead Protection Area. v All Drainage Easements (D.E.) that have regulated drain pipe need to have a 15' easemerit on each side of the pipe. The easeme~.t location needs to be relative to the cen~rline of the pipe. Several instances are shown in the c, onsmiction plans that the easemmt ends only a few feet from the pipe. 5. Are some of these lots walk-out baseraent lots? Hamilton County 4-26-99-C(7)e requires the finish floor elevation to be a minimum of 2 feet about the 100 year elevation of the lakes. Please provide elevations, MFF, pad grade, or lowest opening elevation, for the lower levels of these lots. Also, several of the other lots do not have elevation provided. 01/13/2005 11:34 3177769628 HANILTON O0 SURVEYOR PAGE 02/04 . The existing det~ation pond do~s not appear to ke,-'p the 1 O0 y~ar storm event within the banks of the .,pond and does not have 2 feet of freeboard as shown on the approved HCSO Lake Stm~ards. Also, does this existing lake have 10' safety ledges? . Thc outlet from the existing pond will need to be replaced with RCP. Thc CMP structure will rust out and drop the pond level, which is a future maintenance issue. The plans call for the widenin/of West Road but do not address the extensions that will be needed to the existing crossing under the roadway. The concrete box will need to be extended well past the stone shoulder required, ffthe north crossing, the CMP pipe, is deteriorating as we strongly suspect, this office would request that it be replaced with RCP. The final call on this replacement will be .made by the City of Carmel Engineering Department. ! The brick wall along the front of the property causes several problcrns. The plans show columus on top of storm pipes, the wall its¢If run parallel to the wall with very little separation, The wall blocks the emergency overflows for the lakes/basin. The wall will need to have removal panels in any location that a regulated drain, storm pipe crosses uudemcath the way. Plea,s~ provide details on the brick wall. 10. Please show an emergency overflow for the dry deterition basin located in C01TlmOll area 11. Please provide the bottom elevation for the proposed pond in common area "B". This lake also does not appear to maintain 2' of freeboard as required by our details. I2. Please show spot elevations for the lots, including high points and flow arrows for the individual lot drainage. Also, please show the HP on the swales. 13. Please show spot elevations on the ~nergcncy overflow muting for thc lake in common area "B", This overflow muting need to be located in D.E. to prevent filling and allow access for maintenance. 1,~. The swale on lot 36 and 37 oeeds to be located with D.E. 15. An existing private tile crosses this site and drains into the existing pond. A breather has been set on this pipe at thc Glen Oak/Claybome property linc. Please show this breather in the constructions plans. This tile will need to be located and crushed across this development to prevent problems with thc building pads or sink hole in the lots. 16..Please label thc pipe size and material for the crossing under Letts Circlc. 01/13/2005 11:34 3177769628 HAMILTON CO SURVEYOR PAGE 03/04 17. Based off of the inverts of the cwssing under Lefts Circle, thc 100 flood elevation of the existing pond will back water up into common area "D." Please show the area this water will back up into and label is as storm water storage area. Also this will need to be labeled on the secondary plat. None ofthis storage area will be allow to encroach on Io the building lots. 18. It was discussed at an onsitc meeting with our office that the driveway crossing pipes for lots 22 and 2~ would bc sized by the engineer and shown in thc construction plans. It was also discussed that thc drain pipe (str. 746) would extel~d to thc NW corn~ of~he Berthold prepay to allow for future access to the drain by thc property owners that have current drainagc problems along 131*t Street. The pipe would need to be sized to allow for some capacity for these property owners. ].9. All Drainage Easements that contain pwposed Regulated Drain pipe MUST be cleared the complete width of ~he easem~t as r~quired by IC 36-9-27-33. The easements that contain just swales can contain Wees with the awales w/nding around them, but this office will NOT maintain these swales. 20. Hamilton County Ordinance 4-26.99-C(7)d(I) requires all pipe to have a minimum of 2' of cover. Any location under pavement that 2' of cover can not b~ attained will requir~ special approval for the City of Carmel Engineering Office. 21. Please show the location of the proposed underdmins on the storm P dc P sheets. It appears that several location exist where a conflict with thc SSD and storm pipe and will need to be addressed. 22. Since the roadway is not centered in thc ROW of Letts Circle and the SSD will be regulated drain, thc HCSO will not allow any tree within 10 feet ofthe back of curb ~o prevent the roots from growing into thc underdrains. The plans do not show the existing trees, but any existing trees within that I0 feet will need to be removed. 23. Please show the pil~ location and essements on the landscape plans. I sec several areas that proposed trees may conflict with the D.E. and storm sewers. 24. Please include ALL applicable HCSO Standard Details in thc construction plans. Also, remove any "generic" details that conflict with our stan~ details. 25. The initial review of the drainage calculations raises some questions. I will await the review by Crossroad Bnlgn~ring and require all comment they make to be addressed before at~mval. 26. All casting should b~ labeled "Dump No Waste- Drains to Waterway," which are readily available now from local casting distributors. Please add the complete language to a note in the construction plans. 01/13/2005 11:34 3177769628 H~MILTON CO SURVEYOR PAGE 0~/0~ 27. Please note the additional comments may b~ warranted at a later datz. Should you have any ques~ons, I can be reached at ;317-776-8495. Sincerely, Greg Hoyes Plan Reviewer CC: Jon Dobosic~ricz- Carmel DOCD John South- HCSWCD Dick Hill- Carmel Engineering John l~dwards -- Langston Development Construction/Stormwater Pollution Prevention Plan - Technical Review and Comment I[Project Name: Glen Oaks Subdivision IDate Reviewed: 01/06/05 B2- the sequence is still not adequate.- Line B needs to include the installation of the sed. Basin # 1 in the NW comer. Show a minimum area of land disturbance (draw a labeled line on the plan) on the plan to build the basin. Line C- Where is the topsoil placed? Finish grade and seed the mounds. Start mass earthwork as mounds are being seeded. Finish grade and seed common areas, pond banks and rear half of lots while mass earthwork is finishing. Eliminate the statement about the temp. sed basin because it will be installed prior to mass earthwork. Line F. Much of the finish grading and seeding needs to be completed by this time. Please revise B4. A sediment trap or basin is needed in the north west comer of the site before the stormwater is released offsite. The silt fence is not adequate for the size of the watershed. The sed. basin detail provides the wrong impression. There is no sanitary pipe of other storm sewers. Just show the dam contours with labels, the basin contours, pipe inverts, sizes and length. Provide calculations that basin # 1 is adequately sized. What height is the stone weir? It needs to satisfy the storage requirements. C- A seeding specifications is needed for the alternative grasses in the dry basin. cc: Carmel, Surveyor, File DNR, Division of Soil Conservation Page 1 of 1 Revised 12/09/03 TIN Angelina Conn Fmc 571-2426 _,. j,~mel 57~-2417 , ,, , Fromt Dave Bame~; ..... ~ January 4, 2005 Glen Oaks Subd; ,ision .-- , , C~.-;'.~.;.~= City of Carmel Community Services , _ Pages Innluding,cever sheee 3 Rm TAC notfficabon · ~ Angle: The following "Letter of Transn#ttal". nd site plans were sent to TAC members lister on the included sheet Jar Jary 3, 2005. Several of the members have had the complete set in hand a,. of last week (Ham. County Surveyor, Soil & Water, Highway, etc.) Ple~ re enter this information with your files pertaining to this project. Than~ you. - Dave B. If you are experiencing difficulties In rer, eivlng, plea~;e call 3t71846-66tl or 8001452-6408. Thank you, [0 'd 9~qo ~,8 L[~ [ 'ON ONI S~I~t;INION~I HHI-'4I'114d $S:[0 ~lrl'~"'~OO~-l~O-Nt~£ WEIHE NGINEER$, INC. LETTER OF TRANSMITTAL To: CITY Of CARMEL tac MEMBERS GLEN OAKS SUBDIVi$tOt PY We arc sending you F1 Attached 0 Under separate cover via Shop Drawings Fl Prints Product Data IEl Specifications Samples I"1 Change Order(s) January 3, 2005 0 F1 Sk,tcbcs/Drawings the following items: El Copy of' .otter 12 ~/leeti~ ,[inutes r'l lnspectic t Report rn .~l.i..c~a_t re(s) for P~ym~c,,at i....i ~ ,, .[1111 , I ....-.-----' i i 1 ~., F1 Sets Document Document Description E1Copi,s Date Number ._ 1 TAC comtmction s~t items for abo, r¢ proje. ,, ,ill i -. .... ii Jl iii i ..... i i iii iiii il i ,, i ii i ii ii I"i For Your Kc-view or Use F1 For Your Revi~; & Corr. UI As Requested El For Your Records F1 For Your Approx, al ..... ,,, ir .... These are transmitted as indicated below: D Approved 0 Approved as Noted E1 Not Approved., Revise and Resubmit [=1 Action Not Rcq~ed 0 Action l. adicated on It~:rt Tmsmittcd F'I For Signature. Return ._ Copies to 'Us R'~llark.~ CARMEL TA C MEMBER: The enclosed construction set items w I1 be placed on the January 19, 2005 Carmel TA C agendm Plet~e review these items and ad,!ress at ~ comment~/concerns W ~ Dave Barnes, Weihe Engineers, Inc. At_La,N H, W..m..._H._..~.~_P.F-...L. :.S. "t~,n~sm~:nx ~"0505 NO'I~ COLL~'iE"=AvENUI~ 'iNDIANA'I~i'~'i~; INDtAIRA 46280 t'~17) ~"~"i (8[1{~i ,452- ;408 FAX= gO '~t gl,cio 8~8 L[g [ 'ON X¥:! ONI SYq::INIONSI _~HI_~M N~ SS:J0 ~lfl.l. cioog-l;,O-N~dl' Bill Akers Carmel Clay Communications 31 First Avelauc NW Carmel, IN 46032 Scott Brewer Dept. of Community Service One Civic Square Carmel, IN 46032 $ohn Duffy Carmel City Utiliites 130 First Avenue SW Carmel, IN 46032 Michael Fogarty Office of Police Chief Three Civic Square Carmd, IN 46032 Dick Hill/Mike McBride Dept. of Engineering One Civic Square Carmel, IN ,*6032 Gary Hoyt Of-flee of Fire Chief, Fire Station #1' Two CMo Square Carmel, IN 46032 Teresa Magee/Mark Wood Panhandle Eastern Pipeline Co. P.O. Box 38 Zionsville, IN 46077 Chuck Shupperd Voctr~ Energy P.O. Box 1700 Noblesville, IN ~6061-1700 Sim Blanchard Assistant Building Commissioner One Civic Square Cat, el, IN 46032 Steve Broermann Hamilton County Highway 1700 South 10*~ Street Noblesville, IN 46060 Brighthouse Networks $16 East Carmel Drive Carmel, IN 46032 Dean Groves Cinergy 1441 South Guilford Road Carmel, IN 46032 Brian Houghton Hones & H~mry 2420 N. Coliseum Blvd., Suite 214 Ft. Wayne, I_N 46805 Candy Feltner Clay Township Regional Waste District 10701 North College Ave., Suite A Indianapolis, IN 46280-1098 Ron Morris ~dianapolis Power & Light Co, 3600 North Arlington Averme Indi~. apolis, IN 46218 John South Hamilton County Soil & Water 1108 South 9~ Street Noblesville, IN 46060 Rot Booher Cia cgy PS1 Cus ~mer Project Coordiuator 144 South Guilford Road Car ~el, IN' 46032 Car ael Department of Community Sm' ices On, Civic Square Cm ael, IN 46032 Re: Farrand Cm n¢l Clay Sckools 52( L East 131 ,t Strut Ca: nel, IN 46033 Ro Ha PI~ 17 Nc Gr H~ Oz H~ N( err Henctricks tilton County Local Emergency ming Committee 7 Pleasant Street, Suite 100 ,lesville, IN 46060 g Hoycs ailton County Surveyor's Offlc~ :Hamilton Square, Suite 188 hilton County Judicial Center flesvillc, IN 46060 Ja: m Lcmaster tL hilton County Health Dept- I-~ hilton County Judicial Cemer St tc 30 N, .~lesville, .IN 46060.2229 p( tmastcr Ci ~nel Post Office U: [ted States Postal Service 2; ~ Medical Drive C~ .'reel, IN 46032-9998 Ir ,ianapolis Water Company A .n: Carmel TAC Member P. ). Box 1220 It tianapolis,. IN 46206 Mark Westermeier Carmel Clay Parks Department 1055 Third Avenue SW Carmel, IN a6032 gO 'd 9~,qo t:~,i~ L[a [ 'ON OOC$ ONI SH;I;INION_:{' 5IHi_"q~ l,,lcl I75:[0 ~n£ qOOE-i;,O-N¥.r CIVIL ENGINEERS, LAND SURVEYORS, LAND PLANNERS, LANDSCAPE ARCHITECTS LETTER OF TRANSMITTAL To: CITY OF CARMEL tAC MEMBERS Pmj~ GLEN OAKS SUBDIVISION ,- ~ . , .,;/ '/ '~.I 1 ~'. ~t~: Aanua~ 3, 2005 ~..~c; . _.~ ...... We are sending you Fl Attached [-! Under separate cover via the following items: [2 Shop Drawings [2 Prints [2 Copy of Letter [2 Product Data [2 Specifications [2] Meeting Minutes [2 Samples [2 Change Order(s) [2 Inspection Report Fl [2] Sketches/Drawings [2 Application(s) for Paymem [2 Sets Document Document Description [2 Copies Date Number 1 TAC construction set items for above project. These are transmitted as indicated below: Fl Approved [2 Approved as Noted [2 Not Approved, Revise and Resubmit [2 Action Not Required [2 Action Indicated on Item Transmitted [2 For Signature. Return__ Copies to Us [2 For Your Review or Use [2 For Your Review & Comment [2] As Requested ['3 For Your Records F1 For Your Approval Remarks: CARMEL TA C MEMBER: The enclosed construction set items will be placed on the January 19, 2005 Carmel TA C agendc~ Please review these items and address any comments/concerns to the undersigned and Mr. Jon Dobosiewicz with the City of Carmel Community Developmen~ Thank you. CC: Dave Barnes, Weihe Engineers, Inc. ALLAN H. WEIHE~ P.E., L.$. - PRESIDENT 10505 NORTH COLLEGE AVENUE INDIANAPOLIS, INDIANA 46280 (317) 846-66t t (800) 452-6408 FAX: (3.17)843~D546