HomeMy WebLinkAboutE201.PDFSPECIFICATIONS: (APPLY TQ ALL ELECTRICAL SHEETS) 1. PROVIDE AND INSTALL NEW GREEN INSULATED COPPER GROUNDING CONDUCTORS AS THE EQUIPMENT GROUNDING MEANS FOR ALL ELECTRICAL DEVICES AND EQUIPMENT. 2. ALL COVERPLATES AND WIRING DEVICES SHALL SHALL MATCH EXISTING. 3. PROVIDE LABELING FOR ALL PANELBOARDS AND DISCONNECT SWITCHES TO INCLUDE AN ENGRAVED PLASTIC LABEL IDENTIFING THE EQUIPMENT AND WHERE IT IS FED FROM. ALL BRANCH DEVICES IN THE MAIN SWITCHBOARD SHALL HAVE AN ENGRAVED PLASTIC LABEL. ALL PANELBOARDS SHALL INCLUDE A TYPEWRITTEN DIRECTORY. ALL RECEPTACLES SHALL HAVE CIRCUIT NUMBERS WRITTEN QN THE INSIDE �F THE COVERPLATE. ALL JUNCTION B�X COVERS SHALL BE IDENTIFIED TO INDICATE CIRCUITS CONTAINED. WHERE MULTIPLE SWITCHES ARE GANGED TOGETHER THE SWITCHES SHALL BE IDENTIFIED. 4. ALL CONDUIT INSIDE THE BUILDING SHALL BE A ELECTRICAL METALLIC TUBING �EMT) AND SHALL BE A MINIMUM 3/4" UNLESS OTHERWISE NOTED. ALL CONDUIT INSTALLED ABOVE GRADE OUTSIDE THE BUILDING SHALL BE RIGID STEEL. NO PVC CONDUIT SHALL BE USED ABOVE THE FL40R SLAB. 5. SWITCHES SHALL BE 20 AMPERE RATED, 120/277 VOLT, HUBBELL 1121 SERIES OR APPROVED EQUIVALENT. 6. RECEPTACLES SHALL BE 20A, 120V GROUNDING TYPE LIKE HUBBELL 5342 SERIES. 7. ALL ELECTRICAL CONNECTORS, LUGS, BREAKERS, EQUIPMENT, ETC. SHALL BE RATED AT A MINIMUM OF 75 DEG. C. 8. WIRING METHODS: MC TYPE CABLING MAY BE USED FOR ALL INSTALLATIONS IN EXISTING WALLS. SUPPORT MC CABLE EVERY 6 FEET MINIMUM OR AS REQIUIRED BY CODE. MC CABLE MAY NOT BE USED FOR ANY EXPOSED WIRING �R PANELBOARD FEEDERS. ALL EXPOSED BRANCH CIRCUIT WIRING AND PANELB4ARD FEEDERS SHALL BE TYPE THHN/THWN WIRING INSTALLED IN CONDUIT AND/OR WIREMOLD 500 SERIES METALLIC RACEWAY. ALL WIRING SHALL BE COPPER. NO ALUMINUM WIRING WILL BE ALLOWED. 9. EXTEND EXISTING FIRE ALARM CONTRaL PANEL. PROVIDE ALL NECESSARY COMPONENTS, PROGRAMMING, WIRING ETC FOR A COMPLETE SYSTEM. (APPLY TO ALL ELECTRICAL SHEETS} 1. PROVIDE SUPPORT WIRES AS SHQWN IN DETAIL BELOW FOR ALL LIGHT FIXTURES. 2. ALL WORK SHALL CONFORM TO OR EXCEED THE MINIMUM REQUIREMENTS OF THE CURRENT ANSI/NFPA 70 WITH STATE OF ARIZONA AMENDMENTS, ANSI/IEEE C2 AND ALL FEDERAL, STATE, LOCAL, AND MUNICIPAL CODES AND QRDINANCES. THE ELECTRICAL SUBCONTRACTOR SHALL COMPLY WITH THE DIRECTI�NS OF ALL AUTHORITIES HAVING JURISDICTION. 3. INSTALL WORK USING PR4CEDURES DEFINED IN NECA STANDARDS OF INSTALLATION. ALL WORK SHALL PRESENT A NEAT MECHANICAL APPEARANCE WHEN COMPLETED. 4. THE ELECTRICAL SUBCONTRACTOR SHALL PROVIDE ALL FLOOR, WALL, AND CEILING PENETRATIONS TO COMPLETE HIS WORK. PROVIDE PROPER FIRE SAFEING FOR ALL PENETRATIONS MADE. 5. COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES TO ENSURE EFFECTIVE AND EFFICIENT OVERALL INSTALLATION. 6. C�ORDINATE ALL ELECTRICAL SYSTEM D�WNTIME WITH THE OWNER, PERFORMANGE SERVICES, AND OTHER TRADES. DOWNTIME OF THE SYSTEM SHALL BE MINIMIZED. WEEKEND AND AFTER HOUR W�RK SHALL BE REQUIRED TO PREVENT OR MINIMIZE INTERFERENCE WITH THE OWNER'S OPERATION. 7. THE LOCATIONS OF NEW RECEPTACLES, PHONE/DATA JACKS, AND ROOM EQUIPMENT SHOWN ON THESE DRAWINGS ARE APPROXIMATE. FINAL LOCATIONS WILL BE DETERMINED DURING THE CONSTRUCTION PHASE. 8. ALL NEW EQUIPMENT SHALL BE SUBMITTED FOR APPROVAL PRIOR TO ORDERING. 9. ELECTRICAL EQUIPMENT, DEVICES, CONQUIT, WIRE, UTILITY TRANSFORMER, ETC. COMPLETE. FIELD VERIFY EXACT REQUIREMENTS PRIOR TO BID. �....� � � 10. PROVIDE APPROPRIATE SEALANT (I.E. FIRESAFEING} TO MAINTAIN CONSTRUCTION INTEGRITY FOR ANY PENETRATIONS THROUGH FLOORS, STRUCTURAL CEILINGS, AND FIRE WALLS. 11. ALL RECEPTACLE BRANCH CIRCUITS SHALL UTILIZE SEPARATE INDEPENDENT NEUTRAL CONDUCTORS. DO N�T COMBINE NEUTRAL CONDUCTORS. 12. ALL FEEDER NEUTRAL/GROUNDED CONDUCTORS SHALL BE CONSIDERED CURRENT CARRYING. DERATE MULTIPLE CONDUCTORS IN A RACEWAY ACCORDINGLY WITH NEC TABLES. 13. INSTALL ALL CONDUITS, RACEWAYS, AND CABLE TRAY FOR MAXIMUM HEAD CLEARENCE IN MECHANAICAL AREAS, AND ATTIC. CODRDINATE CLEARANCES WITH PERFORMANCE SERVICES AND THE OWNER. 15. ALL ELECTRICAL SERVICE WORK SHALL COMPLY WITH THE LOCAL UTILITY. COORDINATE ALL REQUIREMENTS PRIOR TO BID AND INCLUDE ALL NECESSARY MATERIAL AND LABOR REQUIRED F4R THE NEW ELECTRICAL SERVICE. 17. CONTRACTOR SHALL DEMQLISH ANY REMAINING EXISTING ELECTRICAL EQUIPMENT, DEVICES, C4NDUIT, WIRE, UTILITY TRANSFORMER, ETC. C�MPLETE. FIELD VERIFY EXACT REQUIREMENTS PRIOR TO BID. NEW CEILING M4UNTED EXHAUST FAN CONNECT TO AN EXISTING SPARE 120V 20A CIRCUIT CONNECT DUCTWORK TO EXISTING EXHAUST DUCT MAIN SCALE: 1 /8" = 1'-4" S CAL E: 1/$" = 1'-�" GENERAL NOTES: 1. ALL QIMENSIONS AND LOCATIONS SHOWN ON THESE DRAWINGS ARE APPROXI MATE. FI NAL LOCATIONS SHALL BE FIELD VERIFY AND COORDINATED WITH OTHER TRADES AND OWNER/ARCHITECT/ENGINEER. 2. DO NOT COMBINE NEUTRALS ON ANY RECEPTACLE CIRCUITS. ALL CIRCUITS SHALL HAVE DEDICATED NEUTRAL CONDUCTORS. 3. COORDINATE ALL CIRCUIT NUMBERS SHOWN FOR NEW CIR�UITS T4 BE INSTALLED IN EXISTING PANEL BOARDS WITH CIRCUIT BREAKER SPACES MADE AVAILABLE FROM DEMOLITION. MAINTAIN CIRCUIT QUANTITIES SHOWN AS THE MINIMUM REQUIRED. 4. ALL NEW DEVICES SHALL BE I NSTALLED FLUSH I N WALLS. PATCH AND PAINT WALLS AS NECESSARY. 5. DEVICES DENOTED WITH 'EX' AND SHADED LINE WEIGHT ARE EXISTING TO REMAIN. 6. ELECTRICAL CONTRACTOR SHALL VERIFY AVAILABILITY AND CAPACITY OF EACH CIRCUIT ANQ DISTRIBUTION SYSTEM PRIOR TO INSTALLATION. 7. COORDINATE INSTALLATION OF LIGHT FIXTURES WITH DUCTWORK, SUPPORTS, PIPING, EQUIPMENT, AND ARCHITECTURAL REFLECTED CEILING PLAN. 8. ALL FIRE COATINGS DISTURBED BY WORK RELATED TO THIS PROJECT SHALL BE RETURNED TO ORIGINAL CONDITION AS REQUIREQ. 9. DEVICES DENOTED WITH 'EXR' ARE EXISTING TO BE RELOCATED. SHOWN IN NEW LOCATION. PLAN NOTES: 1 NO WORK IN THIS AREA. 2 NEW SINGLE POLE SWITCH M4UNTED IN EXISTI NG BOX 3 3/4" CONDUIT TO ACCESSIBLE CEILING. TERMINATE WITH PLASTIC BUSHING. PROVIDE PULL STRING. 4 EXISTING ELECTRICAL PANELS LOCATED IN THIS ROOM TO REMAIN. CONTRACTOR SHALL COORDIANTE NEW CIRCUITING OUT OF THESE PANELS. 5 NEW LOCATI4N OF EXISTING LIGHT FIXTURES. CONNECT TO EXISTING LIGHTING CIRCUIT AS REQUIRED. CONNECT TO NEW SWITCHING PATTERN SHOWN. 6 CONNECT NEW LIGHTING CIRCUITS TO EXISTING LIGHTING CIRCUIT AS REQUIRED. CONNECT TO NEW SWITCHING PATTERN SHOWN. 7 DEVICE(S) INSTALLED ABOVE COUNTERTOP OR SINK +2 ABOVE BACKSPLASH TO BOTTOM OF DEVICE. COORDINATE EXACT MOUNTING HEIGHT WITH CASEWORK SUPPLIER. 8 CIRCUITS SHOWN ARE FOR GROUPING. COORDINATE ALL CIRCUIT NUMBERS SHOWN FOR NEW CIRCUITS TO BE INSTALLED IN EXISTING PANEL BOARDS WITH CIRCUIT BREAKER SPACES MADE AVAILABLE FROM DEMOLITION. MAI NTAI N CI RCU IT QUANTITI ES SHOWN AS THE MINIMUM REQUIRED. 9 RECEPTACLE FOR REFRIGERATOR, +36" A. F. F." 10 RECEPTACLE FOR MICROWAVE. COORDINATE MOUNTING HEIGHT WITH CABINETS TO BE INSTALLED. 11 COORDINATE LIGHTING WITH REVISED CASEWORK/FURNITURE AND BULKHEAD. RELOCATE POWER AND DATA OUTLETS TO ACCOMODATE LARGER WORK STATI ONS/CASEWORK. R! 0 � � d' ��ro .��I'Cfl � d' � � � � w _ V � . �] CYj C� O � � � � � � � n , � �] �] � � � � �� \\\����11111lIII/���� ��C � ° �J% ���i �`�\�- _`�o�°°°°000ao,00J!/� �i/i ��� v °� �°% �� �� %`Qo p � o�i � v� % _�o�� 0 � �-o � o � 0 2 o J, _ - � �o . o - � _�°~ � O W a°a- Z- = o%'n� Z � a oo = . . �� av N (~ �o O� � � i �( o vi � o � m ��a�. O o�� o � � o000 � oo ��\�. W ///�/ �/ o��°OOOOOOO°°�� ♦ �\\ � ���i� o �� ���� � %,, P ���� W ���11111111�� U Z J � J V _ � H V W J W � J � 0 � � .. � w H � � .. - o � .. o � � Q r � � v !� v O � � I � � 00 o O z 0 � � � V Cn W � W a 0 > w � � w 0 � � � J 0 Lt� M W w J � � � � � � � N _ . m �, a o� Z � � � � W R �a cr� z _ (/� a � Q 0 � Z Z _ � J J a J W - _ Lt� � N � '` a = r Z � r � .. � m °D m � z Q W Q� O a w � w Z� � w m r� � V p � DRAWING NUMBER: