HomeMy WebLinkAboutM-1.pdf1. CONTRACTOR SHALL VISIT SITE TO VERIFY THE CONDITION AND SPACE ALLOWED FOR THE INSTALLATION OF WORK. MAKE ALL NECESSARY ROUTING, RTTING AND DUCTWORK MODIRCATIONS AS REQUIRED TO AVOID ANY INTERFERENCE. 2 ALL WORK SHALL MEET THE TOWN OF ZIONSVILLE CODES. 3. REVIEW MECHANICAL LAYOUT WITH OWNER AT BEGINNING OF MECHANICAL DUCT L4YOUT. 4. ALL DUCTWORK SHALL BE GALVANIZED STEEL IN ACCORDANCE WITH SMACNA STANDARDS. 5. VERIFY AND SERVICE THE EXISTING FURNACE, TO PUT THE UNIT IN GOOD OPERATION INCLUDING RA., NEW RLTER, REGISTERS, ETC. 6. PROVIDE BALANCING DAMPER AT EACH DUCT TAKEOFF FROM MAIN DUCTWORK TO OBTAIN THE SPECIRED CFMS- PROVIDE LOCKING DEVICEFOR EACH BALANCING DAMPER- 7. BAL4NCE ALL CFM TO EACH REGISTER AND LOUVER TYPE DIFFUSERS. 8. CLEAN ALL DEBRIS W EACH REGISTER, DIFFUSER AND DUCTWORK. 9. REMOVE EXPANSION VALVE AND REFRIGERANT DEVICE FROM AIR STREAM. ALL PIPING SHALL BE BRAZED. 10. PROVIDE NEW CONTROL WIRING AND PROGRAMABLE ROOM THERMOSTAT WITH SUBBASE. 11. ALL OUTDOOR AIR INTAKE SHALL BE MIN. 15FT FROM EXHAUST OR PER CODE REQ. 12- DRYER EXHAUST DUCTS SHALL BE CONSTRUCTED OF MINIMUM 0-016-INCH-THICK(0-4MM) RIGID METAL DUCTS, HAVING SMOOTH INTERIOR SURFACES WITH JOINTS RUNNWG IN THE DIRECTION OF AIR FLOW. 13. PROVIDE CEILWG MOUNTED EXHAUST FANS AS INDICATED, COMPLETE WITH DUCTWORK, BACKDRAFT DAMPER, AND ROOF VENT CAPS AS INDICATED. 14. ALL REXIBLE DUCT SHALL BE Ul. LISTED AND INSULATED WITH RBERGLASS- FOIL FACED WSULATION. MAXIMUM 5 FT. LONG 15. HEAT ALL ROOMS TO A MINIMUM OF 70' WHEN OUTDOOR TEMPERATURE IS -10'. 16. PROVIDE SMOKE DEfECTOR UNIT TO STOP THE RTU OPERATION AND SOUND ALARM AS PER CODE. 17. PROVIDE A TEST AND BALANCING REPORT AT THE TIME OF RNAL INSPECTION. 18. ALL HVAC CONTRACTORS SHALL BE REGISTERED WITH THE CITY OF BLOOMWGTON. 19. NO HVAC WORK SHALL BEGIN PRIOR TO THE ISSUANCE OF AN HVAC PERMIT. 20. ALL DUCTWORK SHALL BE SEALED IN AN APPROVED MANNER (IMC 603.9� 21. ALL WORK SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM JOB COMPLETION. VENTILATION SCHEDULE ACTUAL CODE REQUIREMENTS MECHANICAL VENT. OCCUPANT LOAD O.AI. CFM O.A.I. ROOM FLR AREA C.F.M. C.F.M. PERSON�1000 CFM�PERSON SUPPLY EXHAUST SUPPLY EXHAUST DESCRIPTION SQ. FT. AIR SUPPLY EXHAUST SQ. FT. C.F.M. C.F.M. UNIT UNIT LOBBY 187 600 - - - - - RTU-A - RECEPTION 136 200 - 60 15 125 - RTU-A - PHYSICAL THERAPY 847 450 - 20 15 255 - RTU-A - WOMEN"S 50 100 160E - - - 50E RTU-A TE-A MEN'S 50 100 160E - - - SOE RTU-A TE-A LAUNDRY 74 150 - 10 25 20 - RTU-A - 1600 400 VENTILATION SCHEDULE ACTUAL CODE REQUIREMENTS MECHANICAL VENT. OCCUPANT LOAD O.A.I. CFM O.A.I. ROOM FLR AREA C.F.M. C.F.M. PERSON�1000 CFM�PERSON SUPPLY EXHAUST SUPPLY EXHAUST DESCRIPTION SQ. FT. AIR SUPPLY EXHAUST SQ. FT. C.F.M. C.F.M. UNIT UNIT PHYSICAL THERAPY 947 1000 - 20 15 285 - RTU-B - OFRCE 90 200 - 7 20 15 - RTU-B - Mr. DeCarlo's OFFICE 63 100 - 7 20 10 - RTU-B - MANAGER'S OFFlCE 63 100 - 7 20 10 - RTU-8 - STAFF OFRCE 167 200 - 7 20 25 - RTU-B - 1600 - - 345 EXISTING ROOF TOP AIR CONDITIONING UNIT SCHEDULE TAG SERVICE CFM ES.P FAN HP HEATWG COOLWG REMARK� TOTAL # OF WEIGHT OF INPUT OUTPUT TOTAL SENS. NOTE # UNITS UNIT EXISTWG PHYS. THERAPY� 1600 0.50 1�2 115 93 49.1 37.5 NOTE 1, 2 1 EXISTING RTU-A OFFlCES EXISTING PHYS. THERAPY� 1600 Q50 1�2 115 93 49.1 37.5 NOTE 1, 3 1 EXISTING RTU-B OFFlCES NOTE: L EXISTING 1d' HIGH ROOF CURB, ECONOMIZER CONTROL, 100% OAI MOTORIZED DAMPER, 2" THICK FlBERGLASS FlLTERS, INDUCED �RAFT FAN AND PROGRAMABLE ROOM THERMOSTAT WITH ALL CONTROL WIRING. 2 SET UNIT RTU-A TO HAVE A MINIMUM O.A.L(400 CFMJ 3. SET UNIT RTU-B TO HAVE A MINIMUM O.A.L(345 CFM) EXHAUST FAN SCHEDULE TAG SERVICE CFM S.P. W.C. MOUNTING FAN HP REMARK� NOTE # TE-A TOILET ROOM 160 0.10 CBLING 100 W BROAN L-150, NOTE #1 NOTE: 1. VERTICAL DISCHARGE WITH BACKDRAFT DAMPER, BIRD SCREEN AND ROOF CAP. DI FFUSER/GRILLE/REGISTER TAG N0. SERVICE SUPPLY RETURN TYPE STEEL STEEL MODULE SIZE 24x24 INDICATED ON PLAN DAMPER YES YES FlNISH BY G.C. BY G.C. MANUFACTURER TITUS TITUS MODEL OMNI 350RL NOiES: 1. PROVIDE VOLUME DAMPER FOR AIR FLOW BALANCING PURPOSES W EACH TAKE-OFF TO A DIFFUSER, REGISTER OR GRILLE. 2 COORDINATE BORDER iYPES, PLASTER FRAMES, AND MOUNTING MEfHODS WITH THE CEILING TYPE AND WALL CONSTRUCTION AT EACH DIFFUSER, REGISTER, AND GRILLE LOCATION. 3. DIFFUSERS SHALL BE LOUVER iYPE LAY-W 2 X 4 CEILING TILE. 4_ ALL DIFFUSERS AND GRILLES ARE TO BE PRIMED AND PAIMED. COORDINATE FlNISH WITH OWNER. RECEPTION NEW 7°0 NK SUPPLY DIFF. 200 CFM 8"m NK 'LY DIFF. CFM EXISTING 16"0 - LOBBY NEW 8°4 NK SUPPLY DIFF. 300 CFM NEW 8"m NK SUPPLY �IFF. 300 CFM TYPICAL BALANCING DAMPER EXISTING 16"0 - 24 X 24 R.A. REGISTER 1600 CFM � PHYSICAL THERAPY r � i I I I RTU I II �24 X 24 A L_____J RA. REGISTER EXISTING 1600 CFM EXISTING 16"� NEW 8"4 NK SUPPLY DIFF. 250 CFM EXISTWG 12"0 - NEW 10 X 4 6'6 TOILET EXHAUST SUPPLY REG. uP 1HRU RooF ro WOMEN'S �oo cFM ROOF JACK(TYP-) 7 V NEW 10 X 4 SUPPLY REG 100 CF MEN'S � TYPICAL BAL4NCING DAMPER EXISTING 16"0 NEW 7"0 NK SUPPLY DIFF. 200 CFM LAUNDRY NEW 6°9 NK SUPPLY DIFF. 100 CFM 4°m DRYER VENT UP THRU ROOF TO ROOF JACK(iYP.) r -� i i I I I I RTU I B L___ EXISTING � NEW 7'D NK SUPPLY DIFF. 200 CFM EXISTING 16"0 - STAFF �FF��E 1 PARTIAL FLOOR PLAN i� SCALE: 1/4"=1'-0" NEW 8"0 NK SUPPLY DIFF. 300 CFM � NEW 7"0 NK SUPPLY DIFF. 200 CFM NEW 7"0 NK SUPPLY DIFF. 200 CFM OFFICE Mr. DeCarlo's OFFI�E NEW 6"0 NK SUPPLY DIFF. 100 CFM MANAGER'S �FF�CE NEW 6"0 NK SUPPLY DIFF 100 CFM NEW 7°0 NK SUPPLY DIFF. 200 CFM EXPIRATION DATE 12/01/2013 Nabil zahran AR 11300009 a � c� L � � � -o N � o � o r V � � c � • �i � o � � � ^ U i � z � z � � � N Qi�� 0 }' � N � L � � U U Q 0 � .�� � � � � - a � 0 � Z � � �w � �o O z � O � �,�w � z � � Q Q o = w r U � _ � � � � 2013-1047