HomeMy WebLinkAboutFull Set Electrical.PDFSPECIFICATIONS NOTES DIVISION 16: I GENERAL: A. SCOPE OF WORK: i. PRONDE ALL MATERIALS, TOOLS AND LABOR REWIRED TO INSTALL THE INDICATED ELECTRICA� WORK IN ACCORDANCE W1TH THESE DRAWINGS AND THESE SPECIFICATIONS. THE CONTRACTOR SHALL SECURE AND PAY FOR AlL PERMITS, FEES, INSPECiIONS AND APPROVALS. 2. ALL POWER OUTAGES SHALL BE FOR A MINIMUM DURATION ON OFF HOURS AND CLOSELY COORDINATED W1TH THE OWNEft. ELECTRICAL CONTRACTOR SHALL PROViDE A TYPE4/RITiFN METH00 OF PROCEDURE FOR EACH OUTAGE (ON FORM PROVIDED BY THE OWNER) AND OBTAIN OWNER APPROVA� PRIOR TO EACH OUTAGE. 3. IN ORDER TO MEET THE PROJECi SCHEDULE THE FOLLO'MNG EQUIPMENT HAS BEEN PURCHASED BY OTNERS. 7HE ELECTRICAL CONTRACTOR SHALL RECEI�E iHE EQUIPMENT AT THE JOB SITE CURB AND PROVIDE ALL NECESSARY TOLLS, MATERIAL AND LABOR FOR RECEIVING fROM TRUCKING COMPANY AND INSTALLING THIS EQUIPMENT. THE FOLLOWING IS A LIST OF EQUIPMENT: POWER DISTRIBUTION PANELBOARDS NEW UPS SYSTEMS NEW UPS PO'NER DISTRIBUTION UNITS NEW SEWRITY, ACCESS CON7ROL EOUIPMENT, AND CCN CAMERAS DATA GAINERING SYSTEM PANELS NEW LIGHi1NG FIXNRES, SWITCHES CIRCUIT BREAKERS AUTOMATIC TRANSFER SNITCHES GENERATORS AND ASSOCIATED EQUIPMENT UNDER FLOOR CABLE TRAY SYSTEM 8. NSIT TO SITE: CONTRACTOR SHALL NSIT SITE AND FULLY INFORM HIMSELF OF THE NATURE OF iHE WORK AND CONDITIONS, AND OBTAIN ALL NECESSARY INFORMAiION TO BID AND EXECUTE THE WORK. G CODES: ALL WORK AND MATERIAL SHALL COMPLY WITH THE LAiEST EDITION OF THE NATIONAL ELECTRICA� CODE, NATIONAL ELECTRIC SAFEN CODE, IBC, OSHA, AND LOCAL MUNICIPAL RE6ULATIONS. D. ALL LOCAL FEES, DISPOSAL COSTS, PERMITS, AND INSPECTION COSTS SHALL 8E PAID FOR BY THE CONTRACTOR. E. CONTRACTOR SHALL SUBMIT A GUARANTEE THAT THE INSTALLATION IS IN ACCORDANCE W1TH T}IE DRAWINGS, APPLICABLE CODES, AWD IN ACORDANCE WITH THE MANUFACTURERS RECOMENDATIONS, THAT THE INSTALLATION SHALL BE FREE OF DEFECTS IN MATERIAL AND WORKMANSHIP FOR A PERIOD OF ONE YEAR. F. ALL GROUNDING SHALL BE IN ACCORDANCE WITH NAItONAL ELECTRIC CODE AND ALL CLIENT STANDARDS. G. EQUIPMENT LOCATIONS SHO'hN ON THE DRAMANGS ARE APPROXIMATE. H. ADJUST INSTALLATION IOCATIONS OF CONL�UIT, AND OTHER EQUIPMENT TO PREVENT INTERFERENCE. I. ALL CUTfING, PATCHING ETC. SHALL BE PREPARED BY SKILLED MECHANICS OF THE TRADE AT NO ADDITIONA� COST TO THE OWNER. FIRE SEAL ALL FLOOR, WALL, AND CEILING PENETRATIONS USING APPROVED UL PRODUCTS. J. IN THE EVENT DEMOLITION WORK EFFECTS THE STRUCNRAI SUPPORT OF EXISTING DEVICES THAT IS TO REMAIN IN SERVICE, IT SHALL BE RESUPPORTED IN ACCORDANCE WITH APPLICABLE CODES. K. CONTRACTOR SHALL REMOVE ALL DEBRIS RESULTING FROM CONSTRUCTION FROM iHE AREA EACH DAY AND SHALL KEEP THE PREMISES CLEAN. THE BUILDING OWNER SHALL HAVE PRIORITY FOR THE SELECTION OF SALVAGED MATERIAL AND E�UIPMENT. ANY EQUIPMENT AND MATERIAL SELECTED TO REMAIN THE PROPERTY OF THE OWNER SHALL 8E REMOVED AND DELIVERED TO A LOCATION ON SITE AS OESIGNAIED BY THE OWNER. MATERIAL AND EqUIPMENT NOT RETAINED BY THE 04lNER SHALL BECOME PROPERTY OF THE CONiRACTOR AND SHALL BE PROMPTLY REMOVED FROM SITE BY THE CONTRACTOR. L ALL EQUIPMENT, MATERIALS, ETC., SHALL 8E NEW AND THE INSTALLATION SHALL BE IN ACCORDANCE W1TH ALL APPLICABLE CODES AND ORDINANCES W EFfECT. THIS INC�UDES BUT IS NOT UMITED TO UL, NEC, NfPA, NEMA, ETC. M. FURNISH AND INSTALL PUIL BOXES AS REOUIRED FOR INSTALLATION. N. A CONDUIT 3 4' MINIMUM SHALL BE E.M.T. UNLESS NOTEO OIHERWiSE. FITTINGS SHALL BE LL / SET SCREW TYPE. REXIBLE CONDUIT SHALL BE SINGLE STRIP, CONTINUWS FLEXIBLE INTERLOCKEq GALVANRED IN�DE AND OUT. USE GRS & LJWIDTIIE FIEXIBLE METAL CONDUIT AT EXTERIOR LOCATIONS. THE FEEDER ROUTING INDICATED ON THE DR0.NINGS IS DIAGRAMMATIC ONLY AND THE EXACT RWTINC SHALL BE FIELD VERIFIED AND CLOSELY COORDINATED AT 7HE TIME OF INSTALLATION YnTH ALL OTHER TRADES. 0. CIRWIT BREAKERS INSTALLED IN EXISTING PANELS SHALL BE MOLDED CASE W1iH ELECTROWC OR THERMAL MAGNETIC TRIP, TRIP FREE, iRIP INDICAi1NG, QUICK-MAKE, QUICK-BREAK, VNTFi INVERSE TIME DELAY CHARACTERISTICS TO MATCH EXISTING DENCES. INTERRUPTING CAPACITIES SHALL MATCH THE AIC RATING OF THE OTHER DEVICES IN THE PANEL. MANUFACTURER SHALL BE SAME AS PANEL MANUFACNRER IN WHICH THE BREAKER IS BEING INSTALLED. P. ALL PANELBOARDS CHANGED DURING CONSiFtUCTION SHALL BE PROVIDED WITH UPDATED PANELBOARD SCHEDULES. Q. SAFETY SN7TCHES AND PANELBOARDS SHALL BE MOUNTED AT 6'-0" TO TOP OF iHE E�UIPMENT, S'MTCHES 42° A.F.F., OUTLETS 18° A.F.F. AND ALL UNIT MWNTED DEVICES SHALL BE CONNECTED W1TH A MAX. OF 24" OF FLEX18LE CONDUIT, UNLESS OTHERWiSE INDICATED. II LOW VOLTAGE WIRE AND CABLE: q, W1RE �10 AND SMALLER SHALL BF SOLID AND LARGER THAN �10 SHALL BE STRANDED. ALL CONDUCTORS SHALL BE COPPER, INSULATION SHALL BE THHN/THWN. THE COLOR MAV CONSIST OF COLORED TAPE INSTALLED AT ALl POINTS WHERE CONOUCTORS ARE ACCESSIBLE. MINIMUM POWER WIRE SIZE TO BE �12AWG. 8. WIRE AND CABLE COLOR CODING SHALL 8E AS FOLLOWS: 208/120 VOLT PHASE A - BLACK PHASE B - RE� PHASE C - BLUE NEUTRAL - WHITE GROUND - GREEN 480/277 VOLT PHASE A - BROWN PHASE B - ORANGE PHASE C - YELLOW NEUTRAI - GRAY GROUND - GREEN III SAFETY SN9TCHES: A. SAFETY SWITCHES PROVIOED BY OTHERS AND INSTALLED BY DIV. i6 Z SUBMIT MANUFACNRER'S DATA FOR ALL SAFETY SNITCHES 3. SAFETY SWITCHES A. SAFETY SWITCHES SHALL BE HORSEPOWER RATE4 HEAW-DUTY, SINGLE-THROW KNIFE SWiTCHES YdTH QUICK-MAKE QUICK-BREAK MECHANISM AS SHOWN ON THE DRAN9NG5. B. PROVIDE W1TH CONTACT ARC-�UENCHWG DEVICES, SUCH AS MAGNETIC BLOWOUTS OR SNUFFING PLATES. PROVIDE SELF- ALIGNING SWITCHBLADES W1TH SILVER ALLOY CONTACT AREAS AND DESIGNED SO THAT ARCING UPON MAKING AND BREAKING DOES NOT OCCUR ON THE FINAL CONTACT SURFACES. PROVIDE 'MTH HIGH-PRESSURE, SPRING-LOAOED CONTACiS. MOUNT SN7TCH PARTS ON HIGH-GRADE INSULATING BASE. C. ENCLOSURE SHALL BE NEMA 1 AND/OR NEMA 3R AS INDICATED ON DRAVANGS. SYA7CH SHAIL HAVE A HINGED COVER AND AN INTERLOCK PREVENTING THE DOOR FROM BEING OPENED 1NTH THE SWITCH CLOSED AND THE SWITCH CLOSED WHEN THE DOOR IS OPENED. A MECHANISM SHALL BE PROVIDED TO DEFEAT THESE INTER�OCKS. D. THE OPERATING HANDLE SHALL BE CAPABLE OF BEING PAD LOCKEO ON EITHER THE OPENED OR CLOSED POSITION. E. RATING, FUSING, IF REQUIRED, AND NUMBER OF POLES SHALL BE AS SPECIFIE� OR SHOWN ON ORA4NNGS. F. PROVIDE GROUND KITS FOR ALL SAFETY SWITCHES. G. LUGS MUST BE U.L LISTED fOR ALUMINUM AND/OR COPPER CONDUCTORS AND BE FRONT REMOVABLE. N. ACCEPTABLE MANUFACNRERS: CUTLER-HAMMER, GENERAL ELECiRIC, ANO SQUARE D. IV FUSES 600V AND lESS A. PRONDE AND INSTALL FUSES IF INDICATED BY THE DRAWINGS AND SPECIFICATIONS. B. SUBMIT MANUFACTURER'S DATA FOR FUSES INCLUDING CHARACTERISTIC CURVES FOR ALL FUSES. C. MATERIALS - FUSES 1. qRCUIT BREAKER PANELS SHALL BE PROTECtED 8Y UL CLASS RK1 FUSE. 2. MOTOR CIRCUITS SHALL BE PROTECTED BY UL CLASS RK5 LABELED AS TIME-DELAY TYPE FUSE. 3. ALL FUSES SHALL BE OF THE SAME MANUFACTURER. 4. ALL NSES TO BE OF 7NE REJECTION TYPE. 5. MANUPACNRERS D. BUSSMAN, UTTLE fUSE, GOULO SHAWMUT OR AS APPROVED EQUIVALENT. E. FUSES SHALL NOT BE INSTALLED UNTIL EQUIPMENT IS READY TO BE ENERGIZED. F. ALl FUSES SHALL BE PRONDED BY THE CONTRACTOR. G. PROVIDE TWO (2) SETS OF SPARE FUSES FOR EACH SIZE AND T1PE USED. NRN OVER TO THE OWNER AT COMPLETION OF PROJECT V PANELBOARDS AND SN7TCHBOARDS A. PANELBOARDS AND SWITCHBOARDS PROVIDED BY OTHERS AND INSTALLED BY D�V. i6 B. INSTALLATION i. INSTALL PANELBOARDS OR S'MTCHBOARDS AS SPECIFlED BY THE MANUFACiURER'S WRITIEN INSTALLATiON INSTRUC710NS. 2. PROVIDE CIRCUIT BREAKERS W EACH PANELBOARD OR SWITCHBOARD AS INDICATED ON THE DRAWINGS EXCEPT WHERE "SPACE° IS INDICATED. 3. COORDINATE INSTALlAT10N OF PANELBOARDS WITH CABLE AND RACEWAY INSTALLATION WORK. 4. MOUNT PANElBOARDS AT A HEIGHT OF 6 FEET TO TOP OF PANEL. INSTALL PANELBOARDS TALLER THAN 6 FEET 1NTH BOTTOM NO MORE THAN 41NCHES ABOVE FLOOR. 5. TIGHTEN CONNECTORS AND A TERMINAL, INCLUDING SCREWS AND BOLTS, IN ACCORDANCE WITH EQUIPMENT MANUFACTURER'S PUBLISHED TORQUE VALUES. WHERE THE MANUFACNRER'S REQUIREMENTS ARE NOT INDICATED, TIGHTEN CONNECTORS AND iERMINALS TO COMPLY N1TH TORQUE VALUES SPECIFIED IN UL STANDARDS 486A AND B. 6. MOUNT PANEL80ARDS PWMB AND RIGi� WITHOUT DISTORTtON OF BOX. 7. INSiALL BLANK COVERS IN UNUSED SPACES. PLUG AlL KNOCKOUTS REMOVED AN� NOT UTILIZED. 8. PROV7DE COMPLETED AND TYPED PANEL80ARD DIRECTORY BASED ON THE FINAL INSTALlATION AND LOADS AND DEV�CES CONNECTED. DIRECTORY SHALL BE NUMBERED LEFT HANO SIDE 'OOD' AND RIGHT HAND SIDE 'EVEN'. C. PANELBOARD MARKINGS i. PANELBOARDS AND S'MTCHBOARDS SHALL INCWDE LABELS WITH THE FOLL04NNG INFORMATION: o. °DANGER OF ELECTRICAL SHOCK" LABELS. b. "POTENTIAL ELECTRIC ARC FLASH HAZARD" LABELS. c. UL LISTING. d. DATE OF MANUFACNRE. e. NUMBER OF PHASES. f. VOLTAGE RATING. g. CURRENT RATING. h. SHORT CIRCUIT RATING. 2. PROVIDE A PRE-PRINTED STICKER AFFIXED TO THE INSIDE OF THE PANELBOnRD OR SWITCHBOARD WI7H THE EMERGENCY 24-HOUR TELEPHONE NUMBER EOR PARTS AND/OR SERVICE VI GROUNDING A. INSULATED CONDUCTORS: COPPER K9RE OR CABLE INSULATED FOR 600 V UNLESS OTHER'MSE REWIRED BY APPLICABLE CODE OR AUTHORITIES HAVING JURISOICTION. B. BARE COPPER CON�UCTOftS: 1. SOLID CONDUCTORS: ASTM B 3. 2. STRANDED CONDUCTORS: ASTM B 8. 3� TINNED CONDUCTORS: ASTM B 33. 4. BONDING CABLE: 28 KCMIL, 14 S7RANDS OF N0. 17AWG CONDUCTOR, 1/4 INCH (6 MM) IN D!AMETER. 5. BONDING CONDUCTOR: N0. 4 OR N0. 6 AWG, STRANDED CONDUCTOR. 6. BONDING JUMPER: COPPER TAPE, BRAIDED CONDUCTORS, TERMINATED W1TH COPPER FERRl4ES; t-5/8 INCHES (41 MM) N1DE AND 1/16 INCH (i.6 MM) THICK. 7. TINNtD BONDING JUMPER: TINNED-COPPER TAPE, BRAIDED CONDUCTORS, TERMINATED VATH COPPER FERRULES; t-5 8 INCHES (47 MM) N1DE AND 1/i6 INCH (1.6 MM THICK. C. BARE GROUNDING CONDUCTOR AND CONDUCTOR PROTECTOR FOR WOOD POLES: 1. N0. 4 AWG MINIMUM, SOFT-DRAWN COPPER. 2. CONDUCTOR PROTECTOR: HALF-ROUND PVC OR WOOD MOLDING. IF WOOD, USE PRESSURE-TREATED FIR OR CIPRESS OR CEDAR. D. MECHANICAL CONNECTORS MANUFACNRERS: 1. O.Z. GEDNEY 2. BURNDY 3. HARGER 4. ERICO E EXOTHERMIC CONNECTION MANUFACTURERS: t. CALDWELD. 2. THERMOWELD. F. TESTING AGENCY: ENGAGE A QUALIFlED TESTING AND INSPEC7ING AGENCY TO PERFORM THE FOLLOVNNG FIELD TESTS AND INSPECTIONS AND PREPARE TEST REPORiS: 1. PERFORM THE FOLLOWING TESiS AND INSPECTIONS AND PREPARE TEST REPORTS: a. AFTER INSTALLING GROUNDING SYSTEM BUT BEFORE PERMANENT ELECTRICAL CIRCUITS HAVE BEEN ENERGIZED, TEST FOR COMPLIANCE N91}I REQUIREMENTS. b. TEST COMPLETED GROUNDING SYSTEM AT EACH LOCATION NMERE A MAXIMUM GROUN�-RESISTANCE LEYfL IS SPECIFIED, AT SERVICE DISCONNECT ENCLOSURE GROUNOING TERMINAL, AT GROUND TEST WELLS, AND AT INDIVIDUAL GROUND RODS. MAKE TESTS AT GROUNO RODS BEFORE ANY CONDUCTORS ARE CONNECTED. 1. MEASURE GROUND RESISTANCE N07 LESS THAN TWO FULL DAYS AFTER LAST TRACE OF PRECIPITATION AND WITHWT SOIL BEING MOISTENED BY ANY MEANS OTHER TNAN NANRAL DRAINAGE OR SEEPAGE AND `MTHOUT CHEMICAL TREATMENT OR OTHER ARTIFICIAI MEANS OF REDUCMG NANRAL GROUND RESISTANCE. 2. PERFORM tESTS BY FOUR POINT FALL-OF-POTENTIAL METHOD ACCORDING TO IEEE 81. 3. USE TWO-POINT METHOD RESISTANCE TEST TO DETERMINE RESISTANCE BETWEEN MAIN SYSTEM AND NEUTRAL AND BETWEEN GROUND AND SRG. 3. REPORT MEASURED GROUND RESISTANCES THAT EXCEED THE FOLLON9NG VALUES: a. POWER AND LIGHTING E�UIPMENT OR SYSTEM WITH CAPACITY 500 KVA AND LESS 5 OHMS. b. �OWER AND LIGHTING E�UIPMENT OR SYSTEM W1TH CAPAGTY 500 TO 1000 KVA: 5 OHMS. c. POWER AND LIGHTING EQUIPMENT OR SYSTEM WITH CAPACIN MORE THAN 1D00 KVA: 3 OHMS. 4. PO`NER DISTRIBUTION UNITS OR PANELBOARDS SERVING ELECTRONIC EQUIPMENi: 1 OHMS. a. SUBSTATIONS AND PAD-MOUNiED EQUIPMENT:5 OHMS. b. MANHOLE GROUNDS: 10 OHMS. 5. EXCESSIVE GROUND RESISTANCE: IF RESISTANCE TO GROUND EXCEEDS SPECIFIED VALUES, NOTIFY ARCHITECT PROMPTLY ANO INC�UDE RECOMMENDATIONS TO REDUCE GROUND RESISTANCE. NI. SAFETIME/MOP A. CONTRACTOR SHALL FOLLOW ALL "SAFETIME" PRACTICES WHEN WORKING NITHIN 10--0" OF ANY ACi1VE A.C. OR D.C. POWER EQUIPMENT, SWITCHING EQUIPMENT OR DISTRIBUTION FRAMES. ALLOWABLE TIMES ARE 11:OOPM TO 7:OOAM FOR COMMUNICATION EQUIPMENT; 12:00 MIDNIGHT TO 5:OOAM FOR POWER EQUIPMENT. AN APPROVED METHOD OF PROCEDURE (MOP) W1LL BE REQUIRED BEFORE SUCH WORK SHALL BEGIN. B. THE MOP SHALL BE FOLLOWED IN PROVIDING ANY SERVICES AND/OR WORK IN THE FACILIN. AS A MINIMUM THE MOP SHOULD DETAIL THE FOLLOWING IiEMS FOR ELECTRICAL WORK: i. SCOPE OF WORK. 2� THE DATE CHOSEN FOR THIS SHUT DOWN. 3� IDENTIFY ALL PANELS AFFECTED. 4. IDEN7IFY PHASING OF ALL AffECiED FEEDERS & IARGE BRANCH CIRCUITS USING A PHASE ROTATION METER. PHASING & ROTATION TO 8E DOCUMENTED 'BEFORE' AND 'AFTER' IN ORDER TO VERIFY THAT ALL EQUIPMENT IS ROTATING PROPERLY. 5. TEMF�RARY POWER REQUIREMENTS AND WHERE THESE TEMPORARY POWER FEEDS WiLL BE TAKEN FROM. 6. STEP BY SiEP BREAKDOWN OF THE WORK iHAT IS TO BE PGRFORMFD. 7. INDIV�DUAL RESPONSIBLE FOR EACH ACTIVITY. 8. BACK OUT PROCEDURE FOR THE RESTORATION OF POWER IN CASE OF AN EMERGENCY. 9. SAFEN PRECAUTIONS AND EQUIPMENT. 10. MANPOWER ON HANO, OWNER REPRESENTATI4ES, ELECTRICIANS. 11. EMERGENCY CALL OUT PHONE NUMBERS Z � �� � Z � � � V � � Z a LL W � � _G 1--I ❑ 1� � a � �� =' 'n o � � N � � : m 0 3av�i� � � ; 0 3n�� c r m o �oNa� +..,. ;-, � � ,, � � �� N �j . '1 �� "InV a � � �:e � � � � � � N $ � � a W ��� I�I '� a ��� � z� W az z � � � � N � � NO. DATE RE�9SION o u-z�-�g BIDDINGAND cnxsrxucnox PRQIECTNUMBER: PROJECfDATE: DRAWNBY: CHEC%EDBY: sc,� e: EOH RWM DRAWINGTTfLE ELECTRICAL SPECIFICATIONS DRAWINGN[JMBER EL / % , x x x EXISSING U1ILITY COMPANY iRANSfORMER TO REMAIN 8 u EXISi1NG GENERATOR � I EICISTING GENERATOR � DIS7RIBUiION BOARD � TO REMAIN I i I ' EXISTING POWER � CIRCUIT FROM I I GENtRATOR � SWITCHBOARD TO iATS-j�3 IS TO BE i REPLACED M EXISTING POWER CIRCUIT -ROM ATS #3 TO MAIN SWITCHBOARD #3 ARE TO REMAIN EXISTING SWITCHBOARD 3 5 EXISTING MAIN SWITCHBOARD #3; TO BE MODIFlED � .a� .__ _ "---.�, __— .. — ...- _ m ExisnNc GENERATOR jf3 TO REMAIN .. EXISTING POWER. CONDUCTORS FROM 7HE GENERATOR TO ATS #3 ARE TO'��.. 'BE REPIACED �` • . 1� UTILITY COMPANY PRIMARY EXISTING UTILITY COMPANY TRANSFER 5'MTCH TO BE �' MODIfIED / 8 _Oj EXISi1NG SERVICE CONDUITS AND CONDUCTORS TO BE REMOVED 0000 0000 oo�o ooco �o EXISTING PAD o000 - �-� GOGO AND STUB-UPS pO° EXISTING PONlER AND CONTROL XI� STING CIRCUITS fROM THE GENERATOR Ai5 4 TO ATS (�4 ARE TO BE REMOVED g ATS #3 TO REMAIN � _ �` ..-: � �_ .-- '� _ __. . � . _......... ___ _ __.— '�. � � �I EXISi1NG HOUSE ''�. PANEL DPH-t � 7 EXISIING U7ILITY COMPANY PRIMARY CONDUC?ORS TO REMAIN -EXISTING Ui1lITY COMPANY TRANSFORMER TO REMAIN EXIST7NG UiIIITY COMPANY TRANSFER SWITCH TO BE MODIFIED � � � r � �\ �888 I �'� EXISTING UTILITY COMPANY PRIMARY . , i� CONDUCTORS TO BE REMOVED ; t—pULL �OB X 2 �. �XISTING SERVICE CONDUITS AND � CONDUCTORS TO BE REMOVED i �.� �REMOVE EXISTING PORTABLE CONNECTION PANEL r� EXISTING POWER AND CONTROL �� VCIRCUITS FROM iHE GENERATOR TO _r:�•, _ ATS �4 ARE r0 BE REMOVED - ATS #4 TO REMAIN / �—..' EXISTiNG POWER CIRCUIT '�� FROM ATS #4 TO MAIN � SWITCH80ARD /j4 ARE TO REMAIN 5 �EXISTING MAIN SWITCHBOARD #4 TO � � ���,.BE MODIFIED f°= ----- .._.. ..._ _ __.. r , � - T� IBOARD 4 �'.,.. .. .I. EXISTING UPS BRANCH CIRCUIT FROM TAP SYSTEMS TO REMAIN �� �� BOX TO CONDENSER UNIT ?' __ . ......___—_—_— :I. ....___- `^ 9 RELOCATE DISCONNECT AN� TAP _. ��BOX, BEIOW, FOR RM 117 CRAC UNIT __. _ _ __ — f EXISTING +3 , _CRAC UNIT _ \ � �NCH CIRCUIT DPH-1 �� YARD 2 - DEMOLITION _ SCAIE: 1/8° = 1'-0' BUItAING NORTH ?i _ ......... ___. "; � ��/l 9 DRAWING KEY NOTES Oi THE INDICATED EXISTING SERVICE CONDUITS AND CONDUCTORS BETWEEN THE SERVICE TRANSFORMER AND ATS ARE TO BE DEMOLISHED. DEMOLIiION SHALL INCLUDE THE DISCONNECTION, REMOVAL AND DISPOSAL OF ALL CONDUCTORS. EXISTING CONDUITS ARE TO BE INTERCEPIED, CUT INSIDE OF THE PULL BOX AND THE REMAINING REUSED UNDER THE NEW WORK PHASE OF THE PROJECT. COORDINATE REQUIREMENTS WITH NEW WORK POWER PLANS AND THE NEW WORK SINGLE LINE RISER DIAGRAM. Oz THE EXISTING ATS #3 AND ATS �4 ARE TO REMAIN AND BE REUSED UNDER THE NEW WORK PHASE OF THE PROJECT. DISCONNECT iHE EXISTING COMMERqAI POWER AND STANDBY POWER FROM BOTH ATS j/3 AND jJ4. O REMOVE AND PROPERLY UISPOSE OF THE EXISi1NG POWER AND CONTROL CONDUCTORS FROM THE GENERATOR TO ATS /J4. CONTROL CONDUITS ARE TO ABANDONED IN PLACE. O THE EXISTING GENERATOR #3 DISTRIBUTION BOARD IS TO REMAIN AND BE REUSED UNDER THE NEW WORK PHASE OF THE PROJECT. DISCONNECT 111E EXISTING STANDBY POWER CONDUCTORS FROM THE GENERATOR TO THE SWITCHBOARD AND CONDUCTORS FROM THE SWITCHBOARD TO ATS /J4. CONDUITS FROM THE SWITCHBOARD AND ATS //4 ARE TO BE PARTIALLY REUSED UNDER THE NEW WORK PHASE. COORDINATE W17H NEW WORK DRAWINGS. OMODIFY THE EXISTING SVATCHGEAR BY DISCONNECTING THE MAIN BONDING JUMPER fROM THE NEUTRAI TO iHE GRWND BAR. DISCONNECT 7HE GROUND BAR FROM THE GROUNDING ELECTRODE CONDUCTOR. GROUNDING ELECTRODE CONDUCTOR TO BE EXTENDED TO THE NEW MAIN CIRCUIT BREAKERS UNDER THE NEW W04K PHASE OF THE PROJECT. XI TIN CAM-LOC lEMPORARY CONNECTION PANEL AND O REMOVE ANO PROPERLY DISPOSE OF THE E S G WIRING AT ATS-#4. TURN AlL WIRING OVER TO THE OWNER. O REMOVE AND PROPERLY DISPOSE OF THE EXISTING CONDUCTORS BETWEEN iHE GENERATOR AND GENERATOR DISIRIBUTION SWITCHBOARD. DEMOLIiION SHALL INCLUDE 1}iE DISCONNECTION, REMOVAL AND DISPOSAL OF FEEDER CIRCUIT CONDUCTORS. CONDVITS, HARDWARE AND SUPPORTS. ARE TO BE REUSED. COORDINA7E REQUIREMENTS WIiH iNE DEMOLIiION 51NGLE LINE DIAGRAM, NEW WORK POWER PLANS, AND THE NEW WORK SINGLE LINE RISER DIAGRAM. OREMOVE AND PROPERLY DISPOSE OF THE EXISTING CONDUCTORS BETWEEN THE GENERATOR DISTRIBUTION SWITCHBOARD AND ATS #3. DEMOLITION SHALL INCLUDE THE DISCONNECTION, REMOVA� AND DISPOSAL OF FEEDER CIRCUIT CONDUCTORS. CONDUITS, HARDWARE AND SUPPORTS. ARE TO 8E REUSED. COORDINATE REQUIREMENTS WITH THE DEMOLI110N SINGLE LINE DIAGRAM, NEW WORK POWER PLANS, AND THE NEW WORK SINGLE LINE RISER DIAGRAM. Og REMOVE THE DISCONNECT SWITCH AND TAP BOX AND STORE ON SITE FOR RE INSTALLA1lON UNDER THE NEW WORK PHASE OF THE PROJECT. �Q REMOVE THE CONDENSER CIRCUIT FROM THE TAP 60R AND RETAIN THE CONDUIT AND CONDUCTORS FOR REUSE UNDER THE NEW WORK PHASE OF 1}1E PROJECT. �� REMOVE THE CRAC UNIT CONDUCTORS FROM THE UNIT AND PANEL AND DISPOSE OF. REMOVE THE EXISi1NG CONDUIT BACK TO A POINT NhiERE IT CAN BE INTERCEPTED AND EXTENDED TO THE NEW DISCONNECT LOCATION UNDER THE NEW WORK PHASE OF THE PROJECT. GENERAL NOTES A. ALL OF THE INDICATED DEMOUTION WORK WILL BE PHASED SO THAT THE ELECTRICAL SERVICE TO THE DATA ROOMS IS NOT INTERRUPTED. COORDINATE PHASING REQUIREMENTS WITH EEB. COORDINAIE ALL WORK WITH THE OWNER 2 1t�EK5 PRIOR TO BEGINNING ANY WORK. KEY PLAN �_ BUILDING NORiH Z � W. � zr� � a `� �./ � � ' W � � u � W � w I� � 1-� � m 0 � � N O � Q � � ''F? 3au'� �'�"�- m . 0 4.' 3�'�� ��� o�x � c°vaiaLL �: r. r ��� �:i � � � ^ ,. �',• �p � � • � � v � � �.. ; � � � � � M �� a C W ��� �� oN � ��� W U�w n� z O VI � N � � N0. DATE REVISION o u-si-�3 BIDDINGAND CONSRRUCCION PRQIECL N[1MHEA PAOJBCfDATE: DRAWN&Y: CHECKED BY: scncE: EOH RWM DItAWiNGITCLE YARD TWO DEMOLITION DRAWINGNUMBER ED1 " ,. .. ___ ., . — — , -_ - - __ II C _ _ ;R� .. - 't.�- ., . k� .. ___ ' i2 RELOCATE EXISTiNG LIGHT � ��, �__ FIXNRES IN ROOM 116 SHIPPWG ? ---� - - :, __' . RECEIVING - � -��- � -_,7 L- 116 ; , ._ : ---- � RL�� RL�� RL�� � __ OR .OR OR �.��f.FD - �.._::: � . :�- . C- ROOM 116 _ NEW WORK LIGHTING PLAN , BUILDING SCALE: 1/8" = 1'-0° NORTH - - - - CANOPY MOUNTED FIXTURE WITH o 0 0 RECTANGULAR DISTRIBUTION _ �-- __ C PHOTOCELL MOUNTED AT ROOF ":, � � CANOPY MOUNTED RXTURE WITH TYPE V WIDE SQUARE DISTRIBUTION EXISl1NG OCCUPANCY SENSOR NEW N01 EMERGENCY POWEi � LIGHTING COMMUNICATIONS NEW DUAL TECH'�� OCCUPANCY MOUNTED TO NEW NORMAL LIGHT f NEW SINGLE LIGHTING SYSTEI CONI LIGHTING C � SYSTEM OVERRIDE arri n.n ,NEW EXTE 1MOUNTED � P�7_1�� �AE _ _ .e�'� I ✓ � �p TO �EW 20/i IN PNL H1 ROOM � ii6B I � - .�.... �, .__.. _- _ _ _ _. _�,_____— ___ _.. ...... ___ .-I PC ._-_ _�_ _ ___ ____ . - CONNECT TO EXISTING EXTERIOR '�. . --�� R... LIGHtING CIXRUIT. X� I�' ... � A )C '>� .—.. ' �..= : � . ,,,, ' _ �.. 9 J _._ �R � ' _....... __ _ ___— .__.__. . - . ��p TO NEW 20/1 IN �° � PNL Ht ROOM 116� NEW IOCATION FOR � - 9 RELOCATED PANELS AND � TRANSFORMER ! ` s, • � ' �, , . . • - I I . DRAWING KEYED NOTES ONEW BUILDING MOUNTED EXTERIOR FIXTURE WITH EMERGENCY BATTERY BACK-UP. MOUNT AT SAME ELEVATION AS EXISTING WALL MOUNTED FIXTURES. WIRE TO EXISTING EXTERIOR LIGHi1NG CIRCUIT. ONEW LIGHTING CONTROL SYSTEM, SINGLE RELAY CONTROLLER. SEE LIGHTING CONiF20L SYSTEM TYPICAL DETAIL ON THIS DRAWMG FOR ADDITIONAL INFORMATION. SUPPORT AS RECOMMENDED 8Y THE MANUFACTURE. LIGHTING CONTROL SYSTEM COMPONENTS WIIL BE 8Y OTHERS. REQUIRED, HARDWARE AND RECEIVING THE MATERIAL AT THE CURB AND INSTALLATION WILL BE 8Y DIV.16. ONEW LOW VO�TAGE, DUAL TECHNOLOGY OCCUPANSY SENSOR MOUNiED TO THE CEILING. SEE THE LIGHTWG CONTROL SYSTEM TIPICAL DETAIL ON THIS DRAWING FOR ADDITIONAL WFORMATION. COORDINATE 4YRING TYPE AND CONFIGURATION WITH lNE SELECTED MANUFACTURE PRIOR TO ROUGH IN. LIGHTING CONTROL SYSTEM COMPONENTS WILL BE BY OTHERS, REQUIRED, HARDWARE AND RECEIVING THE MATERIAL AT THE CURB AND �NSTALLAT�ON WILL BE BY DIV.16. ONEW NORMAL POWERED LIGHT FIXTURES. SUPPORT OFF OF CEILING OR BUILDWG STEEL WITH APPROPRIATE HANGERS. SEE FIXNRE SCHEDULE O AND LIGHTWG CONTROL TYPICAL DETAIL FOR ADDITIONAL WFORMATION. EXTEND POWER CIRCUIT TO THE INDICATED PANEL AND CONNECT. ONEW NORMAL / EMERGENCY POWERED LIGHT FIXTURES WIRE EMEftGENCY BALLAST NON-SWITCHED LEG OF THE LIGHTING CIRCUIT. SUPPORT OFF OF CEILING OR BUILDING STEEL WITH APPROPRIATE HANGERS. SEE FIXTURE SCHEDULE AND LIGHTING CONTROL TYPICAL DETAIL FOR ADDI110NAL INFORMATION. EHTEND POWER CIRCUIT TO THE INDICATED PANEL AND CONNECT. OEXIT SIGNS ARE TO BE WIRED TO THE NON-SWITCHED LEG OF THE LIGHTWG CIRCUIT. SEE FIXTURE SCHEDULE AND LIGHTING CONTROL TIPICAI DETAIL FOR ADDITIONAL MFORMATION. EXTEND POWER CIRCUIT TO THE INDICATED PANEL AND CONNECT. ONEW LIGHTING SYSiEM CONTROL CABLES. COORDINNTE CONTRO� CABLE T1PES AND CONNECTION REQUIREMENTS WITH SELECTED MANUFACTURE PRIOR TO ROUGH-IN. CONTROL CABLES WILL BE 8Y DIV. 16 gO OVERRIDE SWITCH TO CONTROL ALL LIGHTS SIMULTANEOUSLY VIA DAISY CHAINED NEPNORK LIGHTING CONTROL BOXES. OEXISTING LIGHT FIXNRES WSIDE THE INDICATED AREA ARE TO REMAIN AND BE RE-CIRCUITED. EXTEND HOME RUNS FROM THE EXISTING PANELS TO THE EXISTING LOCATIONS AND TERMINATE. �� EXTEND THE NEW LIGHTING CIRCUITS TO PANEL H2 LOCATED IN ROOM 1168. PROVIDE A NEW 20 AMP 1-POLE CIRCUIT BREAKER MATCHING THE KAIC RATING OF THE OTHER OEVICES W THE PANELBOARD AND INSTALL FURNISH ANY REQUIRED HARDWARE. PRO�JIDE AN UPDATED, NPED DIRECTORY SHOWING THE FINAL CONFIGURATION OF qRCUIT BREAKERS IN THE PANEL �� EXTEND NEW CONIROL WIRING FROM THE EXISTING OCCUPANCY SENSOR INSTALLED UNDER THE YARD 1 PROJECT TO THE NEW SENSOR AS SHOWN AND PROGRAM 7HE EXISTING SENSOR TO OPERAiE WITH THE NEW FIXTURES. �Z COORDINAiE FI AiLLIOCAT10NUABORDRV.�iSRCON R CTOR PRIORIGHO COMMENCIN6 WORK.ROOM FOR THE INSTA�LATION OF NEW DUCTWORK. GENERAL DRAWING NOTES A. LIGHTING FIXTURES AND CONTROL SYSTEM COMPONENTS WILL BE 8Y OTHERS. REQUIRED, HARDWARE AND RECEIVING THE MATERIAL AT THE � �� p` CURB AND INSTALLATION WILL BE BY DIV.16. � � FUTURE POWER ROOM WALLS � �� � �+EE INTERIOR FIXTURE SCHEDULE � �' ��� r SYMBOL TYPE DESCRIPTION MANUFACTURER LAMP INPUT OPERATING MOUNTING : ' `-� �� � "� & SERIES QUANTITY �AMP WATTAGE, WATTS PER YOLTAGE k .. � E TYPE & K TEMP FIXTURE a � I i. ...... :� .. � ...._ ..... .. � 4", INDUSTRIAL DIRECT/INDIRECT TURRET FOR HIGH COOPER METALUX UNIV. SUSPENDED .._-- �-_- .._ ��� � q CEILINGS. MEDIUM SPECULAR ALUMINUM F-BAY i5 2 28W TS 64W �20/277V . � DISTRIBUTION OPTIC, OPEN SHIELDING, PROGRAM 3500K r - � ��. RAPID START BALLAST, UPLIGHT APERTURES f i = -_ -- .- .. F 4', INDUSTRIAL DIRECT/INDIRECT TURRET FOR HIGH i 4 . .. ... .. � AEM CEILINGS. MEDIUM SPECULAR AL�MINUM 28W T5 COOPER-METALUX � ,, ,, . 0 DISTRIBUTION OPTIC, OPEN SHIELUING, PROGRAM 2 64W y77V SUSPENDED , " � r - RAPID START BALLAST, UPLIGHT APERTURES, IOTA F-BAY i5 3500K � � . � �� .. _ .. .. '�. _. _ ... ... '__. ' . .._ "._-__-__-- -:- -t -__- C . BATTERY PACK � � � •--- -� 4', SUSPENDED DIRECT/INDIRECT VERSION 3, 207 H.E. WILLIAMS UNIV. SUSPENDED � � ,-.. , , ..... .. � ... , .;, . ..... • � g UPLIGHT DISTRIBUTION, 28 CELL RADIAL CRO55 SDi3 2 28W TS 64W 720/277V g' AFF . - � .� BLADE LOUVER, EIECTRONIC PROGRAMMED START 3500K � ... �-., - .. .... . .... BA�LAST ' ___ �� 4', SUSPENDEO DIRECT/INDIRECT VERSION 3, 20� H.E. WILLIAMS UNIV. SUSPENDED ��--- -� �� -----fi �� ����� �� 0 BEM UPLIGHT DISTRIBUTION, 28 CELL RADIAL CRO55 SDi3 2 28W T5 64W 720�277V g' AFF �-- 6 NEW EXIT SIGN i BLADE LOUVER, ELECTRONIC PROGRAMMED SiART 3500K .1.. BALLAST, BATTERY PACK , __--- ------- . AE � ��� � I WHITE EXIT SIGN WITH RED LED'S, BATTERY BACK UP EXITRONIX N/A RED LED SW DU �ZINPUT WALL r__-__ ' � & SELF TESTING OPT10N. VEX ��� ��� � I EXTERIOR ARCHITECTURAL, FULL CUT-O�F W�.LL TRACE-LITE 26W COMPACT , � Q PACK, WIlH INTEGRAL EMERGENCY BALLAST, TL110A z FLUORESCENT 5�H' 120/277V WALL ' FORWARD 11-IROW REFLECTOR & FIELD INSTALLED PHOTCONTROL -����� '� -� EXTERIOR LED CANOPY LIGHT, WHITE DIE CAST ALM. 54W LED HOUSING WITH 7 UGHT BARS. CONTROL iHROUGH COOPER CNC 7 54W 120/277V CANOPY ���� � m � ROOF MOUNTED PHOTO CELL. DISTRIBUl10N AS 3500K ( NOTED ON PLANS. . � - - NOTES: � � � I 1. WIRE EMERGENCY POWER PACKS TO NORMAL POWER CIRCUIT AHEAD OF SWITCHING IN AREA THEY SERVE. . � 2. IDENTIFY EACH BRANCH CIRCUIT AT THE SUPPLYING PANELBOARD WITN QUANTiTY AND LOCATION OF EMERGENCY FIXTURES SERVED. -=_ � 3. CONTRACTOR TO VERIFY ALL PART NUMBERS AND PROVIDE SUBMITTAL CUT SHEETS INCLUDING .--_ ���� --�- ��� ALL CATALOG NUMBERS PRIOR TO PURCHASE. TO SWITCHED CIRCUIT a ... . i �- OCCUPANCY SENSOR OR c IN THE STARLINE � SUPPORTED FROM SYSTEM •-.-' . Q� CEILING WALL SWITCH INVERTER � POWER OR CONNECTOR � � CIRCUIT TO J-BOX AEM OC. SEN. _ �• ' NEXT LCB LCB NON-SWITCHED LEG HOT WHT/REI __ ------- _.. — ' B TO EMG BATTERY � RED i . �-�=s"^;°"'"�� �.. .-- BALLAST _ WHITE VIOLET I pOWfR OCCUPANCY SENSOR � BROWN SOURCE SUPPORIED FROM BLACK I. .i CON?ROL CABLE TO �� CEIUNG NEUTRAL � • LCB COORDINATE B OG2 CHARGING W T BL4 � �_,,,.,, REQUIREMENTS VAiH INDICATOR BODWE t MANUFACNRE S LIGHT BALLAST . � TO NON-SWITCHED i DIGITAL SINTCH DIGITAL SWITCH A C�RWIT b IN THE INTERFACE MODULE STARLINE SYSTEM A� � rI- � DETAIL GENERAL NOTES ; x` A SWITCH TO CONTROL ALL LIGHTS SIMULTANEOUSLY VIA DAISY CHAINED .!I � ' O NETWORK LIGHTING CONTROL BOXES. ' � i - B DAISY-CHAIN ALL CONIROLKEEPER LIGHTING CONTROL BOXES USING CABLE AS '��.I O REQUIRED BY THE MANUFACTURE. COORDINAiE WITH THE LIGHTING CONTROL '.� ������ , . SYSTEM MANUPACTURE PRIOR TO ROUGH-IN. I Q�-0EX�ST�"� F'XT�RES'"S'°E LIGHTING CONTROL SYMBOLS . �--�--------�- � • THE WDICATED AREA I � ARE TO BE RE WIRED TO � �: �HE RE�OCATED PANEL �� DOOPER CNTERFOACESLWITH �COOPER CON R'ON E PORNPADELCCUPANCY SENSOR. � � '�' LCB NETWORK LIGHTING CONTROL BOX. COOPER MODEL CK2, CONTROLKEEPER 2, � �, � OR EQUAL 277 VO�T, 20 AMP 5 DIGITAL WALL SWI?CH. COOPER MODEL DIGITAI OR EQUAL. � f.� p�p DIGITAL SWITCH GATEWAY. COOPER MODEL DG2 OR EQUAL. ONE GATEWAY REQUIRED PER DIGITA� SWITCH NETWORK. POWERED BY NETWORK LIGHTING � �, CONTROL BOX. — ` OC E�, I //�� PARTIAL 1ST FLOOR � NEW WORK LIGHTING PLAN - SCALE: 1/8° = t'-0" � � .� BUILDING _. NoRni 11 � 12 � SINGLE OR MULTI-POLE TOGGLE SWITCH. 20AMP, 120/277V. � DUAL TECHNOIOGY, WALL MOUNTED, LINE VOLTAGE OCCUPAN;Y SENSOft SWITCH. �. � j1, � COOPER CONTROLS MODEL ONW-D NEOSWITCH OR EQUAL. .-:...., � ._... REFER TO PLAN VIEW FOR QUANTITIES OF LIGHT FIXTURE POWER CIRCUITS CONTROILED BY EACH LCB. ALL FIXTURES AND DEVICES, WILL BE BY OTHERS. ALL REQUIRED MOUNTING HARDWARE AND RECEIVING THE MATERIAL AT THE CURB AND INSTALLATION W1LL BE BY DIV.16. LIGHTING CONTROL SYSTEM TYPICAL DETAIL N.T.S. GENERA� DRAWING NOTES R NEW LOCATION OP DENCE TAGGED 'RC N NEW DEVICES XR EXISTING TO REMAIN RL DEVICE TO BE RELOCATED RM DEVICE TO BE REMOVED AND DISPOSED OF —_._....._ __- ._- - - _. EMERG. FLUORESCENT LAMP BALLAST EMERGENCY RED� YELLOW ---�� __� YEL/BLK 3LU/WHT ���. BLUE 70A FLUORESCENT LAMP NORMAL BALLAST RED �:��•,♦ YELLOW GREEN YELLOW �.. WHA EK BLUE _. . .._.. _ � ELECTRONIC PROGRAMMED START BALLAST NOTE: COORDINATE ACTUAL WIRWG CONFIGURATION WITH THE EMERGENCY BALIAST PROVIDED WITH THE FIXTURES. EMERCENCY LIGHTING TYPICAL WIRING DIAGRAM N.T.S = i�tl �,—i . -- a _ -- --� � � - - �� C � - � �. . � KEY PLAN C� BUILDING NoRm Z � A' ~ � W W � � � � � � � p �� �a y� w § � �' F�/ � ❑ � H I� ? m � o � � � � o 0 a � 3 m�� 0 3��� �v� o ��°v�a� 1� � � `� ^ .� . : `7� .�:: v�. . � � � � � � �.�.• � N M �� 7 C O A °�zz W ��oa � ��6 C'J z W oz z O � � N � � N0. DATE RENSION ._._. __ —. — . ____ o v-2�a3 BIDDIN4AND CONSfRUCTION PROJECTNUMBER: ._ _ PROJBCTllATE: _ unnwrv av: EOH CHECKEDBY: R� SCALE: "__ DRAWING TTfLE LIGHTING NEW WORK PLAN DRAWING MIMBER EL1 OTO NEW 20/1 '. . BKR IN L2 IN . � ROOM 1168 �� -_ ___ — _ . _- - - �- '�. ... . " " — " — _ ',�.. _ _ r, :r.-__� .- --.- - -=-� - 47P3.RU a . ............._ ......._ } , __ - _ N _ ik i. -��. ;+-. � EXISTMG MECHANICAL ' � '� ` ' '�� __ _ . _-_. _. ._.- .. ___ � _ — _ — _ -_- _ ��- . -;i - : � EQUIPMENT POWER � � ��� ��� ' �� , ... l-\�CIRCUIT TO BE . .,-� ... . ... _ . q I ._�� ___ - RE FED � �� NEW LOCAiION FOR RELOCATED '. ,__ - � �. PANELS AND TRANSFORMER � � � . uFw PAN�I nPU-a(�� � �.. - _ , I. �,, � . �� ..� : TO 1200 AMP � CB IN MDP-3 IN - - EXISTING Pz' � CONDUIT BANK - - � P' TO 1200 AMP 1201 CB IN MDP-4 IN EXISi1NG CAST EXISTING IN PLACE BOX ' _ _ _ CONDUIT BANK _, �pp� �� __ _ __ __ _— _ _ _ ' .-. SUPPORT CONDUITS FOR DPH3 & - 4 TIE AND UPS 6B AND SB FROM— EXiER10R WAIL NEAR CEILING _ z- P2,1 � a 0 a � - E� TO NEW 800 AMP '�. C8 IN UPS5A & SB FROM EXiERIOR , . NEW PANEL DPH-4� WALL NEAR CEILING � , _ _ __.. _ - _- — _ ' :.. - � 6 800 ' ... EP2. �.__; Og TO NEW 20/1 TO NEW 20/3 _ �. SAW CUT FLOOR AND .: BKR IN L2 IN BKR IN OPH 3 � P�ACE CONDUITS : ROOM 116B ,�-i UNDER SLAB - EXTEND CONDUITS 1�� � ''�, ABOVE SLAB, UNDER NEW MECHA ICAL UNIT `�' , RAISED FLOOR --�,'�, MAU-1 30 AMP. NEMA 1, ... ;�_— _" . _____- - - : ,. � � HD, NFSS � ��� � - TO 125/3 BKR � ;TO 125/3 BKR TO 125/3 BKR O1 2 7 • 1 2 1 2 IN DPH-3 - ' IN DPH- IN DPH-4 EP2.1 � 125 . -� CRAC-10A-1-. CRdC_1f1A-9� 195 CRAC-t0R-3-� /. >r _� L Y�II _ I � J O C> � J O U I OTO NEW 20/1 BKR IN L2 IN ROOM 116B �NEW E�CAL U� EH-1 30 AMP, NEMA i __ HD, NFS` H 0 O o U - •�, ' �� �� ,fi -�� EXlEND CONDUITS 1 TO NEW 20/3 UNDER SLAB BKR IN DPH-4 WAP, MOUNT AT CEILING N � 20/1 CB PDU-2A-3 F- � � � C O O O 2 U = U SA CUT FLOOR AN � PLACE CONDUITS f0 DP 3 UPS58 _ ABOVE SLAB, UNDE RAIS D FLO R � � � � F_ � � O O � = U S C� 1-1�► � J O U TO 125/3 BKR IN�108-6 725 _ E �� _ . .. ,.., _..... ._._.....M._.�_._ _ __. �� 7 2 _.... _ ._ 125/3 BKR �ZS IN DPH-3 UTURE � � 10UPS-5'� � .... '.' . -- __..__ . - �L � - _ �'� . ... .. .—y ._ -I ._.,. ._ � ., � - - � � _. 6 RUN CONDUIT AT CEIUNG AND l �'.. EPZ'� ,) DROP DOWN FOR OUTLETS � � I � ��725 NEW PANEL ` ,�.� -_ . ... .. . . _. -� ... 1 ..: 6 UPS-SB " '�.� ,, - ...-. ... . -� �. ���. :' ......�� . � � I �, ..... . -I� �.. . : � . = :��,..... J � ' ��. � 350 I FUTURE POWER ROOM WALLS ���� �� � �� i 8 P2.1 � �,, . . . . ... ` ,_ � �.'. - , I _ _. EXISTiNG LIGHTING AND ,:. .. � _ - � �� POWER OUTLETS INSIDE � UTURE ' ��� � � THE INDICATED AREA ARE 10 I = �-_� --_-��- ��' - I TO BE RE-FED FROM THE _ UPS-6 -� - - -� RELOCATED PANELS #1 ... . - ,, �.� � : ._. . . . . .... �� AND #2 .. � .. ,:. ,-. „ .� � � � �. � _.. .. ..-- : . . �� ( � �� . I .. - . � ,, � ' ..._ :..� ,- ._ .. . � . -- ,------. . �. � _:.. . ___ .._. • .::.�:.-- _ . .. _-___ , _ .� _.. i ._. ... ., ... ... ....... . ..... .. ........._... . _ . .. ........ � , C .. _ nNEW PANEL � -- `. - . � �,.., . Z/UPS-6B " '� .'" " ' .,_� ..... . .. .. , :� �3 -� . : , NEW MECHAN(CAL UN17 � I -- � �-� -- . EH 2 30 AMP NEMA 1, = , . . -��� ',. -- -�� HD, NFSS ' � TO NEW 20/3 � . . -- , � � BKR IN DPFI-4 � - - ��, -= - -. ...:::.:: . .� .. _ ,.,. '.. _ -- . �......_._ -= I . .. �- , I. _. .. __ . . .. . � TO 125/3 BKRO � 1-: ,. /7' � ...� .... � - � . I IN DPH-4 � .. rr � EXISTING MECHANICAL �� r �, � 4 EQUIPMENT POWER CIRCUIT . � CRAC-108 4. 125 -- TO BE RE-FED �� ' � - � E . _`-� ..... ...... . . . . . 1 - I � .. �.. --�- �- . . . _. _ � . .... .... .. , . � I � � ..... . . . . . ( , �: � u � � . . . . e .. . I . JF- I ........ . . . . ..... . . . . . � .. � O O � C iu ur UPS68 � O S , �— -_ �,_ �-- • � _-= _'....._.__ . _ � .. _ _"_— ..." _ - -__ ' c „r � — � - _ — �� � J O ' CJ — � — I_ _ I_ _ --- — � .-- __. __ ���. L._ _ � ��FIRE PROTECl70N SYSTEM � � � � � . ....8 CONTROL PANE� .. �� ���... ��L ..-.. -- - - � . _ B I�,.. . ..... _. � ._� .. , ���� iJ NEW 20/1 � . .._. .. ..... . . BKR IN L2 W .) � � ROOM 1168 � � � ; . ...... .......... . �___... __.... �I,. .......... _. . .. .. .. � � � � , � . . . � .____ . __ _-__. ____ ___. . ...__..... H O _ i, � � � � 1 � � �i � � I.... .. .. S �'. � � �. __.. T.-�-�_-� . , �. � I' � (;I(Al;-1 VC- / � \ �' l - _' � i .�__., _ � � . 25/3 BKR 125 1 �O '... ..� IN DPH 3 `r - -- - - _-�.__J ::_ .:-..— _ . ---� - . . _ - -- - — - --. . :. - _- - — --- -- _ - - - : , _-- q C= PART!AL 1Si FLOOR NEW WORK PLAN BUILDING SCALE: 1/8" = i'-0` NORTH _ .._._ - — - _ - RELOCATED MECHANICAL '�. � EQUIPMENT POWER 4 CIRCUITS TO BE RE-FED �'� , COND- COND - ----- --��� ---� 108-6 108-7 FUTRUE FUTRUE PU7RUE FUTRU �� TO 20�3 BKR - � .� i. IN DPH 3 �. 20 '� �' M1 �. �' �� . COND- �_ � E . 108-1 - 11 � TO 20/3 8KR Z� , IN_ DPH-4 � � � � COND- - _ E 1 1 E ' 1 1 E.r 11 . . . � ' . .'. . �.'.. ��8-2 __ ZQ 20 FUIRUE FUTRUE FUiF2UE �. �Y�� TO 20�3 ',�� TO 20�3 BKR IN BKR IN �- � � DPH 4 � DPH 3 �� _ / TO NEW - 20/1 . _ COND � WND - BKR IN . � 108-3 ' 108 4 - � IN . COND-: - : ROOM - 108 5�: ii6B � . �. �. .: E E E 20' 20' GFI 20' '�, � ���� TO 20/3 BKR TO 2Q/3 BKR TO 20/3 BKR '� ....._ (N�-DPH 3 (N,-6PF��7FT6FFr_3_--- __ __ --____.. TO NEW 15/3 BKR IN DPH-3 20 NEW MECHANICAI UNIT � � CU-1 30 AMP, NEMA 3R, HD, NfSS ON ROOF �� - • C C- �� � PARTIAL ROOF NEW WORK PLAN BUIL ING SCALE: 1/8" = 1'-0° NORTH NEW WORK DRAWING KEY NOTES I A IN I A . X ND WIRING FROM INDICATED PANELS TO THE INTEGRAI DISCONNECTS ON UNITS AND CONNECT. EXTEND Oj NEW CRAC UNITS TO BE CRCUITED 5 DC iED E TE CONDUITS UNDER SLAB / RAISED FLOOR FROM THE PANELS TO THE UNITS. FURNISH AND INSTALL, 1-CAT 5e CABLE 70 THE SITE LME PANEL AND 2-CAT Se CA8LE5 TO THE NETWORK hWM PANEL COORDINATE LOCATION OF CON7ROL PANELS 'MTH DIV 15. SEE TYPICAL BUILDING ALARM/DATA GATHERING PANEL DIAGRAM ON E203 FOR ADDITiONAI INFORMATION. O PRONDE 3/4" EMPTY CONDUIT WITH PULL TAPE FOR HVAC SYSTEM CONTROL WIRING BY DN. 15. EXTEND FROM CRAC UNIT TO ASSOCIAiED ACCU. FOLLOW POWER AN� REFRIGERATION PIPING PATH / RACKING INSTALLED BY DIV. 15 TO iHE UNITS. COORDINATE ROUTING AND UNIT LOCATIONS VNTH DIV. 15 PRIOR TO ROUGH-IN, O3 NEW PDU, UPS POWER. E%tEND CIRWITS UNDER THE RAiSED FLOCft / SLAB TO PANEL UPS-58 OR UPS-68 AS INDICATED. SEE THE NEW WORK SINGLE LINE DIAGRAM, PANEI ELEVATIONS ON EXX FOR ADDIiIONAL INFORMATION. PDU FURNISHED BY OTHERS RECEIVED AT THE CURB AND INSTALIED AND WIRED BY DIV. i6. O4 RELOCATED CONDENSING UNITS TO BE RE WiRED TO RELOCATEO PANEL jji OR /J2. INTERCEPT EXISTING BRA!ICH qRCUIT RETAINED UNDER THE DEMOLITION PHASE AND EXTEND THEM TO THE NEW UNIT AND PANEL IOCATI0N5 AND TERMINATE ONTO THE EXITING CIRCUIT BREAKERS. O5 NEW 1200 AMP, 277/480 VOLT, 3-PHASE, 4 WIRE, MECHANICAL DISTRIBUTION PANELS FURNISHED BY OTHERS RECEIVED AT THE CURB, INSTALLED, AND WIRED BY DIV�SION i6. PRO�DE ALL HARDWARE. CONDUITS, SUPPORTS, ETC, NECESSARY FOR A COMPLETE INSTALLATION. SEE THE NEW WORK SINGLE IINE DIAGRAM AND PANEL ELEVATIONS FOR ADDITIONAL INFORMATION. O6 NEW 1600 AMP, 480 VOLT, 3-PHASE, 3 W1RE, UPS DISTRIBUTtON PANELS fURNISNED BY OTHERS RECEIVED AT THE CURB, INSTALLED, AND WIRED 8Y DIVISION 16. PROVIDE ALL HARDWARE, CONDUITS, SUPPORTS, ETC, NECESSARY FOR A COMPLETE INSTALLATION. SEE THE NEW WORK SINGLE LINE DIAGRAM AND PANEL ELEVATIONS FOR ADDITIONAL INFORMATION. O7 PROVIDE ALL MATERIAL AND LABOR REQUIRED TO RELOCATE EXISTING PANELS �1 AND y2 WITH ASSOCIATEO TRANSFORMER WHERE SHOWN. THESE PANELS N'ERE REMOVED AND RETAINED UNDER THE DEMOLITION PHASE OF THE PROJECT. OS NEW FIRE SUPPRESSION CONTROL PANEL FURNISHED AND INSTALLED BY DIV. 15, POWERED BY DIV. 16. PROVIDE ALL MATERIAL & LABOR TO ExTEND CIRCUIT TO A NEW 20/1 CIRCUIT BREAKER IN F'ANEL L2 LOCATED IN ROOM 116B AND TERMINATE. NEW CIRCUIT BREAKER IS TO MATCH KAIC RATWG OF THE OTHER DEVICES IN THE PANEL. O9 NEW OUTLET CIRCUIT. PROVIDE ALL MATERIAL & LABOR TO EXTEND CIRCUIT TO A NEW 20/i CIRCUIT BREAKER IN PANEL L2 LOCATED IN ROOM 1168 AND TERMINATE. NEW CIRCUIT BREAKER IS TO MATCH KAIC RATING OF THE OTHER DEVICES IN THE PANEI. ERISTING POWER OUTLETS INSIDE THE INDICATEO AREA ARE TO REMAIN AND BE RE-CIRCUITED. EXTEND HOMt RUNS FROM THE RELOCATED PANELS TO THE FXISTING OUTLETS AND TERMINATE. �Q FUTURE UPS AND BATTERY CABWETS WITH NEW 3 1/2" DEEP CONCRETE PAD. COORDINATE GONDUIT LOCATIONS WITH THE MANUFACTURER PRIOR TO ROUGH IN. PAD SHALL BE 4" MINIMUM LARGER THAT THE EQUIPMENT. � � NEW CONDENSING UNITS TO BE CIRCUITED AS INDICATEO. EXTEND NIRING FROM THE INDICATED PANELBOARD TO INTEGRAL DISCONNECT ON UNIT. INSTALL AN EMPTY }" CONDUIT `MTH PULL TAPE FROA1 THE CRAC UNIT TO iHE ASSOCIATED ACW. CONiROI YdRING 9Y DIY 15. GENERAL DRAWING NOTES A. COORDINATE ALL WORK W1iH BUILDMG MANAGEMENT AND OWNER PRIOR TO BEGINNING WORK. 8. ALL TRENCHING, BACKFILLING, PATCHING TO BE BY OTHERS. �� �.,�' � �r_ ��%_/ i p d � I . M V KEY PLAN �: BUILDING NORTH Z � � ' G� z� v � ~�h � � �./ p LL� W� p� I-� � m o � N � N O 0 3a�m N � � m 0 3n�� C I� � o =' � � c°�Na� '�r� 1 � . � � �� � �� � � � � � � sen� tVO. 10606023 � M �� 7 � �30Yi A� � a �Ga z�o°a � ~z�j W p q �� � � W N � � N0. DATE RENSION o u-2�a3 BIDDINGAND� CANSTBUCI'ION PRQIE(.TNUMBEA: _ .._ PRQIECI DA'I'E: _- _ - . _ DanmvBY: EOH cxEC�n�: RWM sc�.e: __ DkAWINGTTILE NEW WORK PLAN DRAWINGNUMBER EP2