Loading...
HomeMy WebLinkAboutE0.1 010714.pdfELECTRICAL SPECIFICATIONS GENERAL REQUIREMENTS DRAWINGS ARE DIAGRAMMATIC AND DO NOT INDICATE ALL FITTINGS, JUNCTION BOXES, ETC. REQUIRED. PROVIDE ALL REQUIRED EQUIPMENT, CONDUIT, FITTINGS, WIRING, BOXES, ETC. FOR A COMPLETE AND OPERATIONAL INSTALLATION. WORK AND EQUIPMENT SHALL COMPLY WITH STATE AND LOCALLY ADOPTED CODES AND STANDARDS, INCLUDING THE NATIONAL ELECTRICAL CODE (NEC), INTERNATIONAL CODES (I-CODES), AND LOCAL AMENDMENTS. ANYTHING DRAWN OR SPECIFIED SHALL NOT BE CONSTRUED TO CONFLICT WITH STATE AND LOCALLY ADOPTED CODES AND STANDARDS, INCLUDING THE NATIONAL ELECTRICAL CODE, WHICH GOVERNS THE INSTALLATION OF ANY ELECTRICAL WORK. ITEMS SHALL NOT BE INSTALLED IN CONFLICT WITH THE NEC. RESOLVE ANY AND ALL CONFLICTS PRIOR TO INSTALLATION. BECOME THOROUGHLY ACQUAINTED WITH THE CONDITIONS UNDER WHICH WORK IS TO BE PERFORMED. EXAMINE ALL SERVICES, EQUIPMENT, AND EXISTING CONDITIONS, WHICH THIS WORK IS IN ANY WAY DEPENDENT UPON, AND BRING ANY DISCREPANCIES OR OMISSIONS FOUND IN THE DRAWINGS TO THE ELECTRICAL ENGINEER'S ATTENTION PRIOR TO SUBMITTING BID. THE LOCATION OF OUTLETS AND EQUIPMENT SHOWN ON THE DRAWINGS ARE APPROXIMATE. THE ARCHITECT AND ENGINEER SHALL HAVE THE RIGHT TO ADJUST THE LOCATION OF OUTLETS OR FIXTURES, WITHIN 10' OF THE SPECIFIED LOCATION, BEFORE THEY ARE INSTALLED AND WITHOUT ADDITIONAL COST. PROVIDE DRAWINGS TO LOCAL BUILDING AUTHORITY AND OBTAIN A PERMIT PRIOR TO STARTING ANY WORK. NOTIFY ELECTRICAL ENGINEER OF ANY CHANGES REQUESTED BY THE LOCAL BUILDING AUTHORITY IMMEDIATELY AND PRIOR TO STARTING WORK. VERIFY AND COMPLY WITH UTILITY COMPANY REQUIREMENTS. PROVIDE METERING, CONNECTION CABINETS, CT CABINETS, AND TRANSFORMER AND CONNECTION CABINET PADS PER LOCAL UTILITY COMPANY REQUIREMENTS. PROVIDE A REDLINED AS-BUILT SET OF ELECTRICAL DRAWINGS TO OWNER UPON COMPLETION OF WORK. ELECTRICAL WORK SHOWN LIGHT OR MARKED "E" IS EXISTING, SHOWN DARK IS NEW, AND SHOWN DASHED IS EXISTING TO BE REMOVED OR RELOCATED UNLESS OTHERWISE INDICATED. DASHING MAY ALSO INDICATE UNDER FLOOR OR UNDER GROUND CONDUIT. IF UNCLEAR, CONTACT ELECTRICAL ENGINEER FOR CLARIFICATION. EQUIPMENT, WIRING, AND DEVICES SHOWN ARE NEW UNLESS OTHERWISE NOTED. MAINTAIN CIRCUITING TO EXISTING EQUIPMENT AND DEVICES TO REMAIN. REFERENCE ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION. INSTALL EQUIPMENT AND DEVICES PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. NOTIFY ELECTRICAL ENGINEER, PRIOR TO INSTALLING EQUIPMENT AND DEVICES, IF MANUFACTURER'S INSTALLATION INSTRUCTIONS CONFLICT WITH ELECTRICAL INFORMATION ON THE THESE DRAWINGS. ELECTRICALLY OPERATED EQUIPMENT SHOWN ON PLANS, AND NOT CIRCUITED ON THE ELECTRICAL PLANS, WILL REQUIRE ELECTRICAL SERVICE. CONTACT ELECTRICAL ENGINEER FOR CONNECTION REQUIREMENTS AND CLARIFICATION PRIOR TO BID. THE COST FOR THIS WORK SHALL BE INCLUDED IN THE BID. PROVIDE HANGERS AND SUPPORTS TO ADEQUATELY AND SECURELY SUPPORT ELECTRICAL SYSTEM COMPONENTS IN A NEAT AND WORKMANLIKE MANNER. MAINTAIN THE FIRE RATING OF THE ASSEMBLY (CEILING, WALL, OR FLOOR) IN WHICH EQUIPMENT, WIRING, AND DEVICES ARE TO BE INSTALLED. ALL EQUIPMENT SHALL BE FULLY RATED FOR THE AMBIENT CONDITIONS (ELEVATION, TEMPERATURE, ETC) AT THE PROJECT LOCATION. SUBMITTALS AND SUBSTITUTIONS PROVIDE PRODUCT DATA SHEETS AND SHOP DRAWINGS FOR EQUIPMENT, FIXTURES, AND DEVICES TO ELECTRICAL ENGINEER PRIOR TO PURCHASING. REVIEW, STAMP AND INITIAL ALL ELECTRICAL SUBMITTALS AND SHOP DRAWINGS CERTIFYING THAT THE SUBMITTALS HAVE BEEN REVIEWED PRIOR TO SUBMITTING TO ELECTRICAL ENGINEER FOR REVIEW. EQUIPMENT AND FIXTURES SPECIFIED REPRESENT REQUIRED QUALITY AND PERFORMANCE. PROVIDE PRODUCT DATA SHEETS AND SHOP DRAWING OF PROPOSED SUBSTITUTIONS TO SPECIFIED EQUIPMENT TO ELECTRICAL ENGINEER FOR REVIEW. ELECTRICAL ENGINEER SHALL DETERMINE THE ACCEPTABILITY OF SUBSTITUTIONS TO SPECIFIED EQUIPMENT. REVIEW, STAMP AND INITIALED ALL ELECTRICAL SUBMITTALS AND SHOP DRAWINGS CERTIFYING THAT SUBMITTALS HAVE BEEN REVIEWED PRIOR TO SUBMITTING TO ELECTRICAL ENGINEER FOR REVIEW. SUBMITTALS AND SHOP DRAWINGS ARE TO INCLUDE THE FOLLOWING: KEY TO PLAN DESIGNATIONS, MANUFACTURER, MODEL NUMBER, DATA SHEETS, QUANTITIES, COLORS, LABELS, DIMENSIONS, INSTALLATION INSTRUCTIONS, AND ANY ADDITIONAL INFORMATION REQUIRED TO DETERMINE IF THE PRODUCT MEETS THE DESIGN INTENT. CONSTRUCTION PHASE REVIEW REQUIREMENTS INSTALL POWER, LIGHTING, COMMUNICATIONS AND SPECIAL SYSTEM (FIRE ALARM, SECURITY, BUILDING AUTOMATION, ETC) BOXES PRIOR TO RUNNING CABLE OR CONDUIT TO BOXES. ARRANGE FOR OWNER, ARCHITECT, AND ENGINEER TO REVIEW BOX LOCATIONS PRIOR TO RUNNING CABLE OR CONDUIT TO BOXES. ADJUST BOXES AS DIRECTED BY OWNER, ARCHITECT, AND ENGINEER. REQUESTS FOR MODIFICATIONS TO THE CONTRACT (CHANGE ORDERS) REQUESTS BY CONTRACTOR FOR ADDITION OR REDUCTION TO THE CONTRACT AMOUNT SHALL BE ACCOMPANIED BY THE FOLLOWING FOR EVALUATION BY THE OWNER AND ENGINEER: 1.ORIGIN AND DATE OF CLAIM 2.QUANTITIES OF PRODUCTS, LABOR, AND EQUIPMENT 3.DOLLAR AMOUNT OF TAXES, OVERHEAD, AND PROFIT 4.JUSTIFICATION FOR ANY CHANGE IN CONTRACT TIME 5.CREDIT AMOUNT FOR DELETIONS (WITH DOCUMENTATION) 6.DATES AND TIMES OF WORK PERFORMED, AND BY WHOM 7.TIME RECORDS AND WAGE RATES PAID 8.INVOICES AND RECEIPTS FOR PRODUCTS AND EQUIPMENT SUBMIT ALL DOCUMENTATION TO ENGINEER AND OWNER, AND OBTAIN WRITTEN APPROVAL PRIOR TO STARTING ANY WORK THAT AFFECTS THE CONTRACT AMOUNT OR COMPLETION DATE. EXISTING CONDITIONS THESE DRAWINGS CONTAIN INFORMATION REGARDING EXISTING CONDITIONS. THIS INFORMATION WAS COMPILED FROM EXISTING DRAWINGS OR CASUAL FIELD OBSERVATIONS. IN SOME CASES, ASSUMPTIONS WERE MADE WHEN FIELD OBSERVATIONS OR EXISTING DRAWINGS DID NOT PROVIDE NECESSARY INFORMATION (I.E. LOCKED DISCONNECTS, NO WIRE SIZE INDICATED, NAMEPLATE DATA MISSING, INACCURATE AS-BUILT DRAWINGS, ETC.). EXISTING CONDITIONS SHALL BE VERIFIED AND ALLOWED FOR PRIOR TO BID AND CONSTRUCTION. NOTIFY THE ELECTRICAL ENGINEER OF ANY DISCREPANCIES WITH THESE DRAWINGS IMMEDIATELY AND PRIOR TO COMMENCING ANY FURTHER WORK. COORDINATION THE ELECTRICAL DRAWINGS ARE ONLY ONE PART OF A COMPLETE SET OF CONSTRUCTION DOCUMENTS. EXAMINE THE ARCHITECTURAL, MECHANICAL, PLUMBING, AND CIVIL DRAWINGS PRIOR SUBMITTING BID AND STARTING WORK TO DETERMINE THE FULL EXTENT OF ELECTRICAL WORK REQUIRED. COORDINATE WORK WITH OTHER TRADES PRIOR TO ROUGH-IN. COORDINATION SHALL INCLUDE REVIEWING THE ARCHITECTURAL, MECHANICAL, PLUMBING, ETC. DRAWINGS AND SHOP DRAWINGS PRIOR TO BID AND CONSTRUCTION. OBTAIN AND REVIEW SHOP DRAWINGS, PRODUCT DATA, MANUFACTURER'S WIRING DIAGRAMS AND MANUFACTURER'S INSTRUCTIONS FOR EQUIPMENT PROVIDED BY OTHERS. THE FINAL LOCATION OF EQUIPMENT SHALL BE COORDINATED IN THE FIELD, PRIOR TO ROUGH-IN, TO MEET APPLICABLE LOCATION, HEIGHT AND CLEARANCE REQUIREMENTS. WIRING AND CONDUIT NEW WIRING SHALL BE THHN/THWNƒ&,NSULATED COPPER UNLESS OTHERWISE NOTED. ALUMINUM CONDUCTORS SHALL BE XHHW-2, INSULATED COMPACT STRAND. THE CONDUCTORS FOR 15A AND 20A BRANCH CIRCUITS SHALL BE #12 THHN/THWN-2, ƒ& INSULATED COPPER. BRANCH-CIRCUIT CONDUCTORS GREATER THAN 20A SHALL BE AS INDICATED ON PLANS OR REQUIRED PER CODE. 20 AMPERE BRANCH CIRCUIT HOMERUNS OVER 75' SHALL BE #10AWG CU AND OVER 150' SHALL BE #8AWG CU. 7+(0$;,080180%(52)&21'8&7256,1$&21'8,7)25$‘6<67(06+$//%(7+5(( $‘ %‘&‘ 127,1&/8',1*1(875$/$1'(48,30(17*5281',1*&21'8&725681/(66 OTHERWISE INDICATED. CONDUIT SIZE SHALL BE BASED UPON NEC CHAPTER 9 AND ANNEX C. MORE THAN 3 CURRENT-CARRYING CONDUCTORS MAY BE INSTALLED IN A RACEWAY IF THE APPROPRIATE AMPACITY-DERATING FACTORS ARE APPLIED. PROVIDE A DEDICATED NEUTRAL FOR EACH LINE-TO-NEUTRAL CIRCUIT UNLESS A MULTI-POLE BREAKER, WHICH DISCONNECTS ALL PHASE CONDUCTORS THAT SHARE A NEUTRAL, IS PROVIDED (LISTED BREAKER-TIES ARE PERMITTED). PROVIDE AN INSULATED EQUIPMENT GROUNDING CONDUCTOR WITH ALL FEEDERS AND BRANCH-CIRCUIT WIRING. INCREASE CONDUIT SIZE AS REQUIRED TO ACCOMMODATE EQUIPMENT GROUNDING CONDUCTOR. CONDUIT SHALL BE CONCEALED IN WALLS, FLOOR OR CEILING IN FINISHED AREAS UNLESS OTHERWISE INDICATED. IN FINISHED AREAS, WHERE CONDUIT AND CABLE CAN NOT BE CONCEALED IN WALLS OR CEILINGS (I.E. EXISTING MASONRY CONSTRUCTION), PROVIDE WIREMOLD OR EQUAL SURFACE MOUNTED RACEWAY AS APPROVED BY ARCHITECT OR ENGINEER. THE TYPE OF CONDUIT SHALL BE AS FOLLOWS FOR ALL FEEDERS AND BRANCH CIRCUITS, UNLESS OTHERWISE SPECIFIED OR REQUIRED. REFERENCE THE NEC FOR ADDITIONAL APPLICATION REQUIREMENTS. APPLICATION TYPE OF CONDUIT IN CONCRETE OR MASONRY EMT, GRC OR PVC OUTDOORS (ABOVE GRADE)EMT OR GRC BRANCH CIRCUITS (EXPOSED) EMT OR GRC INTERIOR BRANCH CIRCUITS (CONCEALED BEHIND DRYWALL)MC CABLE OR EMT INTERIOR BRANCH CIRCUITS (ABOVE DROPPED CEILINGS)EMT SUPPLY TO DISTRIBUTION PANELS EMT OR GRC UNDERGROUND PVC SCHED. 40 OR 80 AS REQ'D FINAL CONNECTIONS TO LIGHT FIXTURES SHALL BE MADE WITH FLEXIBLE METAL CONDUIT WITH A MAXIMUM LENGTH OF 6'. FINAL CONNECTIONS TO MECHANICAL OR VIBRATING EQUIPMENT, SUCH AS MOTORS AND TRANSFORMERS, SHALL BE MADE WITH FLEXIBLE METAL CONDUIT. INSTALL CONDUIT EXPOSED TO SUNLIGHT ON ROOFTOPS A MINIMUM OF 12" ABOVE ROOF SURFACE. PROVIDE PVC COATED GRC FOR ELBOWS IN PVC CONDUIT RUNS. ALL CONDUITS AND CABLES PASSING THROUGH RATED WALLS, FLOORS OR CEILINGS SHALL BE FIRE STOPPED WITH APPROVED FIRE BARRIER CAULK. INSTALL CAULK PER MANUFACTURE'S INSTRUCTIONS AND MAINTAIN THE RATING OF THE WALL, FLOOR, OR CEILING BEING PENETRATED. DEVICES DEVICE AND FACEPLATE COLOR SHALL BE AS SPECIFIED BY THE ARCHITECT OR TO MATCH EXISTING. COORDINATE FACEPLATE AND DEVICE COLORS WITH ARCHITECT, INTERIOR DESIGNER AND OWNER PRIOR TO PURCHASING AND INSTALLING DEVICES AND FACEPLATES. PROVIDE COMMERCIAL SPECIFICATION GRADE SWITCHES AND RECEPTACLES. PROVIDE GFI PROTECTION FOR 120V, 15A AND 20A RECEPTACLES INSTALLED IN THE FOLLOWING NON-DWELLING LOCATIONS: BATHROOMS, KITCHENS, ROOFTOPS, OUTDOORS, SINKS (WITHIN 6' OF OUTSIDE EDGE OF SINK), FEEDING ELECTRIC WATER COOLERS, AND LOCATIONS INDICATED ON POWER PLAN. PROVIDE GFI RECEPTACLE, FACELESS GFI DEVICE FEEDING STANDARD RECEPTACLE, OR GFI CIRCUIT-BREAKER. THE GROUND-FAULT CIRCUIT-INTERRUPTER SHALL BE INSTALLED IN A READILY ACCESSIBLE LOCATION. PROVIDE WEATHER-RESISTANT RECEPTACLES FOR RECEPTACLES INSTALLED IN DAMP OR WET LOCATIONS. PROVIDE HUBBELL RECEPTACLES WITH THE APPROPRIATE NEMA CONFIGURATION FOR RECEPTACLES SHOWN ON THE ELECTRICAL PLAN. PROVIDE 6' CORD AND PLUG FOR SPECIAL-PURPOSE RECEPTACLES IF EQUIPMENT TO BE INSTALLED IS NOT SUPPLIED WITH A CORD AND PLUG. PROVIDE FLOOR-MOUNTED DEVICE COVERS MOUNTED FLUSH WITH THE FINISHED FLOOR SURFACE. PROVIDE WIRING DEVICES AS MANUFACTURED BY HUBBELL, PASS AND SEYMOUR, LEVITION, WATT-STOPPER, LUTRON OR EQUAL. COORDINATE MOUNTING HEIGHTS OF SWITCHES, RECEPTACLES, PHONE OUTLETS, DATA OUTLETS, TV OUTLETS, AND LIGHT FIXTURES WITH ARCHITECTURAL DRAWINGS. THE MOUNTING HEIGHT FOR DEVICES SHALL BE AS INDICATED BELOW, UNLESS OTHERWISE NOTED. MOUNTING HEIGHTS ARE TO CENTER OF DEVICE, UNLESS OTHERWISE NOTED. MATCH MOUNTING HEIGHT OF EXISTING DEVICES IF APPLICABLE. GENERAL RECEPTACLES (COMMERCIAL) @18" AFF LIGHT SWITCHES @ 44" AFF PROVIDE "IN-USE" WEATHERPROOF COVER FOR EXTERIOR RECEPTACLES. COMPLY WITH ADA STANDARDS FOR MOUNTING HEIGHTS AND LOCATIONS. DEVICES IN THE SAME LOCATION AND AT THE SAME MOUNTING HEIGHT SHALL BE MOUNTED UNDER A COMMON WALL PLATE. DISTRIBUTION EQUIPMENT PROVIDE DISTRIBUTION PANELS, DISCONNECTS, CONTACTORS, ETC. OF VOLTAGE, AMPERAGE, PHASE, AND SHORT-CIRCUIT RATINGS AS INDICATED ON PLANS. 7(50,1$7,2166+$//%(5$7('ƒ&0,1,080&8$/ FUSES SPECIFIED ARE AS MANUFACTURED BY BUSSMANN. THE SAME CLASS OF FUSE AS MANUFACTURED BY LITTELFUSE AND GOULD-SHAWMUT MAY BE SUBSTITUTED. ENCLOSURES FOR EQUIPMENT AND DEVICES SHALL BE SUITABLE FOR THE INSTALLED LOCATION. PROVIDE 3 5/8" DEEP LOAD CENTERS FOR PANELS INSTALLED IN 4" STUD WALLS. PROVIDE PANELBOARDS FOR ALL OTHER INSTALLATIONS, UNLESS OTHERWISE NOTED. PROVIDE A 3/4"C FROM PANEL ENCLOSURES TO NEAREST ACCESSIBLE CEILING SPACE FOR EACH (3) SPARE BREAKERS AND SPACES IN PANELBOARDS AND LOAD CENTERS THAT ARE RECESSED IN A WALL. PROVIDE PANELS AND SWITCHBOARDS BUSSING AND FINGERS TO ACCOMMODATE BREAKERS OR SWITCHES IN ALL AVAILABLE SPACES. PROVIDE A HINGED COVER FOR PANELBOARDS. PROVIDE A LISTED BREAKER-TIE OR MULTI-POLE BREAKER FOR EACH MULTIWIRE (SHARED NEUTRAL) BRANCH CIRCUIT. PROVIDE DISTRIBUTION EQUIPMENT AS MANUFACTURED BY AMERICAN MIDWEST POWER, SQUARE D, ELECTRO-MECHANICAL INDUSTRIES, CUTLER-HAMMER, SIEMENS, ERICKSON ELECTRIC, GE OR METRON. THE MOUNTING HEIGHT FOR DISTRIBUTION EQUIPMENT SHALL BE AS INDICATED BELOW, UNLESS OTHERWISE NOTED. PANELS/LOADCENTERS - 6' AFF MAX TO CENTER OF TOP HANDLE CT CANS - 2' AFF MIN, 6' AFF MAX TO CENTER OF CTs DISCONNECT SWITCHES - 6'-6" AFF MAX TO CENTER OF HANDLE SINGLE UTILITY METER - 4' MIN, 6' MAX TO CENTER OF METER METER CENTER - 3' MIN, 6' MAX TO CENTER OF METERS PROVIDE BRASS TAG (ATTACHED WITH BRASS SCREWS), INDICATING UNIT SERVED ON SERVICE DISCONNECTS, FEEDER DISCONNECTS, AND METERS SERVING MULTI-TENANT FACILITIES. PROVIDE A TYPED PANEL SCHEDULE WITH LOAD DESCRIPTIONS FOR PANELS AFFECTED BY THIS PROJECT. PROVIDE A PHENOLIC LABEL ON EACH NEW OR RENAMED PANEL INDICATING THE PANEL NAME. IDENTIFICATION FOR ELECTRICAL SYSTEMS PROVIDE IDENTIFICATION LABELS OR HANDWRITTEN TEXT USING INDELIBLE MARKER TO IDENTIFY CIRCUITS ENCLOSED IN BOXES. USE IDENTIFICATION LABEL OR ENGRAVED FACEPLATE TO IDENTIFY BRANCH CIRCUITS FEEDING RECEPTACLES AND SWITCHES. PROVIDE IDENTIFICATION ON INSIDE SURFACE OF FACEPLATE FOR RECEPTACLES AND SWITCHES IN PUBLIC AREAS OR IN AREAS AS DIRECTED BY ARCHITECT OR OWNER. USE IDENTIFICATION LABEL TO IDENTIFY RECEPTACLES PROTECTED BY UPSTREAM GFI PROTECTION. LABEL CONDUCTORS AND CABLE WITH POWER SOURCE AND CIRCUIT NUMBER OR OTHER REQUIRED DESIGNATION. USE WRAP-AROUND SELF-ADHESIVE VINYL CLOTH, WRAP-AROUND SELF-ADHESIVE VINYL SELF-LAMINATING, HEAT-SHRINK SLEEVE, PLASTIC SLEEVE, PLASTIC CLIP-ON, OR VINYL SPLIT SLEEVE TYPE MARKERS SUITABLE FOR THE CONDUCTOR OR CABLE TO BE IDENTIFIED. USE FACTORY PRE-PRINTED OR MACHINE-PRINTED TEXT, ALL CAPITALIZED UNLESS OTHERWISE INDICATED. IDENTIFY EACH PIECE OF ELECTRICAL EQUIPMENT WITH AN IDENTIFICATION NAMEPLATE. PROVIDE THE FOLLOWING INFORMATION ON THE NAMEPLATE: SWITCHBOARDS: AMPERE RATING, VOLTAGE AND PHASE, POWER SOURCE AND CIRCUIT NUMBER, LOADS BEING SERVED. PANELBOARDS AND LOAD CENTERS: AMPERE RATING, VOLTAGE AND PHASE, POWER SOURCE AND CIRCUIT NUMBER, LOADS BEING SERVED (TYPED CIRCUIT DIRECTORY). ENCLOSED SWITCHES AND CIRCUIT BREAKERS: AMPERE RATING, VOLTAGE AND PHASE, POWER SOURCE AND CIRCUIT NUMBER, LOAD BEING SERVED. CONDUCTOR INSULATION SHALL BE COLOR CODED AS FOLLOWS: 9‘3+$6($%/$&.3+$6(%5('3+$6(&%/8( PROVIDE UNDERGROUND WARNING TAPE 12" BELOW GRADE FOR POWER AND COMMUNICATIONS CONDUIT AND CABLE. USE NON-DETECTABLE TYPE POLYETHYLENE TAPE SUITABLE FOR DIRECT BURIAL, 6" WIDE MINIMUM, AND INDICATE THE TYPE OF SERVICE CONTINUOUSLY REPEATED OVER THE FULL LENGTH OF TAPE. TAPE FOR BURIED POWER LINES: BLACK TEXT ON RED BACKGROUND. TAPE FOR BURIED COMMUNICATIONS: BLACK TEXT ON ORANGE BACKGROUND. IDENTIFY EXISTING ELEMENTS TO REMAIN THAT ARE NOT ALREADY IDENTIFIED. PROVIDE TYPEWRITTEN CIRCUIT DIRECTORY TO IDENTIFY LOADS SERVED FOR PANELBOARDS AND LOAD CENTERS. MECHANICAL EQUIPMENT REFERENCE MECHANICAL DRAWINGS FOR EXACT LOCATION AND REQUIREMENTS OF MECHANICAL EQUIPMENT. ELECTRICALLY OPERATED EQUIPMENT SHOWN ON THE MECHANICAL PLANS AND NOT SHOWN ON THE ELECTRICAL PLANS WILL REQUIRE ELECTRICAL SERVICE. CONTACT ELECTRICAL ENGINEER FOR CONNECTION REQUIREMENTS PRIOR TO BID. THE COST FOR THIS WORK SHALL BE INCLUDED IN THE BID. VERIFY MECHANICAL EQUIPMENT NAMEPLATE DATA (VOLTAGE, PHASE, FLA, MCA, MOCP, ETC.) PRIOR TO ROUGH-IN. NOTIFY ELECTRICAL ENGINEER IN WRITING OF ANY DISCREPANCIES WITH THESE DRAWINGS IMMEDIATELY AND PRIOR TO COMMENCING ANY FURTHER WORK. MECHANICAL CONTRACTOR SHALL PROVIDE STARTERS FOR MECHANICAL EQUIPMENT. MECHANICAL CONTRACTOR SHALL PROVIDE CONDUIT, WIRE, AND DEVICES FOR MECHANICAL EQUIPMENT CONTROLS, UNLESS OTHERWISE INDICATED ON THE ELECTRICAL DRAWINGS. ELECTRICAL CONTRACTOR SHALL PROVIDE MECHANICAL EQUIPMENT CONTROL WIRING, CONDUIT, AND DEVICES IF INDICATED ON THE ELECTRICAL DRAWINGS. NOTIFY ELECTRICAL ENGINEER IN WRITING OF ANY DISCREPANCIES WITH THESE DRAWINGS IMMEDIATELY AND PRIOR TO COMMENCING ANY FURTHER WORK. REFERENCE MECHANICAL DRAWINGS FOR LOCATIONS OF FIRE SMOKE DAMPERS AND CONTROL REQUIREMENTS OF MECHANICAL EQUIPMENT. PROVIDE 120V TO FIRE SMOKE DAMPERS AND PROVIDE EITHER DUCT OR SMOKE DETECTORS AS REQUIRED. RETURN AIR SYSTEMS OVER 2000CFM REQUIRE A SMOKE DETECTOR TO SHUT UNIT OFF MECHANICAL EQUIPMENT UPON ACTIVATION OF SMOKE DETECTOR. CONNECT DETECTORS TO FIRE ALARM SYSTEM IF APPLICABLE. PROVIDE EW201B FOR MECHANICAL EQUIPMENT CONTROLLED BY A TIME SWITCH. PROVIDE CONTACTORS RATED FOR THE MECHANICAL LOAD BEING CONTROLLED. LIGHTING PROVIDE LIGHT FIXTURES AS INDICATED ON LIGHTING PLAN OR FIXTURE SCHEDULE. THE MOUNTING HEIGHT FOR LIGHT FIXTURES SHALL BE AS INDICATED ON THE FIXTURE SCHEDULE, ARCHITECTURAL ELEVATIONS, OR AS SHOWN BELOW, UNLESS OTHERWISE NOTED. MATCH MOUNTING HEIGHT OF EXISTING LIGHT FIXTURES IF APPLICABLE. INSTALL EXIT AND EMERGENCY LIGHTS @ 6" BELOW CEILING TO TOP OF FIXTURE WITH A MAXIMUM MOUNTING HEIGHT OF 10' AFF. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH LIGHTING CIRCUIT. CONNECT EXIT AND EMERGENCY LIGHTING TO NON-SWITCHED LEG OF LOCAL LIGHTING CIRCUIT UNLESS OTHERWISE NOTED. MAKE CONNECTIONS TO LIGHT FIXTURES USING BUILDING WIRE WITH INSULATION SUITABLE FOR TEMPERATURE CONDITIONS WITHIN THE LUMINAIRE. PROVIDE 30A LIGHTING CONTACTOR WITH NUMBER OF POLES AS REQUIRED FOR LIGHTING CONTROLLED BY A TIME SWITCH OR PHOTOCELL. TIME SWITCH: TORK EWZ201 TIME SWITCH WITH PHOTOCELL: TORK DGLC SERIES ELECTRIC UTILITY COMPANY SUBMIT ELECTRICAL DRAWINGS AND SERVICE APPLICATION TO ELECTRIC UTILITY COMPANY PRIOR TO STARTING ANY WORK. COORDINATE WITH THE ELECTRIC UTILITY COMPANY TO ARRANGE FOR PERMANENT AND TEMPORARY ELECTRICAL SERVICE TO BE PROVIDED TO THE SITE AS REQUIRED. OBTAIN WRITTEN APPROVAL FROM THE LOCAL ELECTRIC UTILITY COMPANY INDICATING THAT THE SERVICE DESIGN IS ACCEPTABLE. PROVIDE LETTER TO ELECTRICAL ENGINEER PRIOR TO PURCHASING ANY ELECTRICAL SERVICE EQUIPMENT OR STARTING ANY WORK ON THE ELECTRICAL SERVICE. NOTIFY ELECTRICAL ENGINEER IMMEDIATELY OF ANY DESIGN CHANGES REQUESTED BY THE UTILITY COMPANY. TELEPHONE SERVICE PROVIDE ONE 4" CONDUIT AND ONE 2" CONDUIT FROM THE TELEPHONE PEDESTAL TO BUILDING TELEPHONE BOARD. VERIFY THE LOCATION OF THE PEDESTAL AND THE SIZE OF THE CONDUIT REQUIRED WITH THE TELEPHONE COMPANY. PROVIDE 1" CONDUIT FROM BUILDING TELEPHONE TERMINAL BOARD TO TELEPHONE BOARD IN TENANT'S SPACE. COORDINATE EXACT LOCATION WITH TENANT PRIOR TO ROUGH-IN. PROVIDE #6 GROUND FROM BUILDING GROUNDING ELECTRODE SYSTEM TO TELEPHONE BACKBOARD. PROVIDE GROUND BAR AT PHONE BOARD. BRANCH-CIRCUIT WIRING SCHEDULE (UNLESS OTHERWISE NOTED) 15 A #12 AWG #12 AWG #12 AWG 1/2" 20 A #12 AWG #12 AWG #12 AWG 1/2" 25 A #10 AWG #10 AWG #10 AWG 1/2" 30 A #10 AWG #10 AWG #10 AWG 1/2" 35 A #8 AWG #8 AWG #10 AWG 3/4" 40 A #8 AWG #8 AWG #10 AWG 3/4" 45 A #6 AWG #6 AWG #10 AWG 1" 50 A #6 AWG #6 AWG #10 AWG 1" 60 A #4 AWG #4 AWG #10 AWG 1 1/4" 70 A #4 AWG #4 AWG #8 AWG 1 1/4" 80 A #3 AWG #3 AWG #8 AWG 1 1/4" 90 A #2 AWG #2 AWG #8 AWG 1 1/2" 100 A #1 AWG #1 AWG #8 AWG 1 1/2" NOTES: 1.FOR MOTOR LOADS, USE MCA (MINIMUM CIRCUIT AMPACITY) TO SIZE PHASE AND NEUTRAL CONDUCTORS AND USE MOCP (MAXIMUM OVER-CURRENT PROTECTIVE DEVICE) TO SIZE EQUIPMENT GROUNDING CONDUCTOR. 2.INCREASE PHASE, NEUTRAL, AND EQUIPMENT GROUNDING CONDUCTOR SIZES BY 1 STANDARD CONDUCTOR SIZE PER EACH 75' OF CONDUCTOR LENGTH. INCREASE CONDUIT SIZE ACCORDINGLY. A A PROVIDE CLEAR SPACE EQUAL TO THE WIDTH OF EQUIPMENT OR 30", WHICHEVER IS GREATER. B PROVIDE THE FOLLOWING CLEAR SPACE IN FRONT OF EQUIPMENT: 3' FOR 0-150 L-G VOLTAGE AND 4' FOR 151-600 L-G VOLTAGE. C PROVIDE CLEAR SPACE, FOR THE WIDTH OF THE EQUIPMENT, FROM GRADE, FLOOR OR PLATFORM TO A HEIGHT OF 6-1/2' OR THE HEIGHT OF THE EQUIPMENT, WHICHEVER IS GREATER. D THE SPACE EQUAL TO THE WIDTH AND DEPTH OF THE EQUIPMENT AND EXTENDING FROM THE FLOOR TO A HEIGHT OF 6' ABOVE THE EQUIPMENT OR TO THE STRUCTURAL CEILING, WHICHEVER IS LOWER, SHALL BE DEDICATED TO THE ELECTRICAL INSTALLATION - NO PIPING, DUCTS, LEAK PROTECTION APPARATUS, OR OTHER EQUIPMENT FOREIGN TO THE ELECTRICAL INSTALLATION SHALL BE LOCATED IN THIS ZONE. SUSPENDED CEILINGS WITH REMOVABLE PANELS SHALL BE PERMITTED WITHIN THE 6' ZONE. SPRINKLER PROTECTION SHALL BE PERMITTED FOR THE DEDICATED SPACE WHERE THE PIPING COMPLIES WITH THIS SECTION. A DROPPED, SUSPENDED, OR SIMILAR CEILING THAT DOES NOT ADD STRENGTH TO THE BUILDING STRUCTURE SHALL NOT BE CONSIDERED A STRUCTURAL CEILING. E THE AREA ABOVE THE DEDICATED SPACE SHALL BE PERMITTED TO CONTAIN FOREIGN SYSTEMS, PROVIDED PROTECTION IS INSTALLED TO AVOID DAMAGE TO THE ELECTRICAL EQUIPMENT FROM CONDENSATION, LEAKS, OR BREAKS IN SUCH FOREIGN SYSTEMS. B C D D E E CLEAR SPACE/WORKING SPACE ABOUT ELECTRICAL EQUIPMENT THE FINAL LOCATION OF EQUIPMENT SHALL BE COORDINATED IN THE FIELD, PRIOR TO ROUGH-IN, TO MEET APPLICABLE LOCATION, HEIGHT AND CLEARANCE REQUIREMENTS. THE ELECTRICAL CONTRACTOR SHALL STOP WORK IMMEDIATELY, AND ADVISE OTHERS TO STOP WORK IF THERE IS A CONFLICT WITH THE ELECTRICAL CLEARANCE AND WORK SPACE REQUIREMENTS PER THE ABOVE INFORMATION AND THE NEC. D FRONT VIEW OF EQUIPMENT SIDE VIEW OF EQUIPMENT 130168 RE V I S I O N S CE R T I F I C A T I O N DR A W N B Y : B E K CH E C K E D B Y : B E K CL I E N T S I G N O F F : IS S U E D A T E : 1 1 / 4 / 1 3 TH I S D R A W I N G A N D T H E I D E A S , D E S I G N S A N D CO N C E P T S C O N T A I N E D H E R E I N A R E T H E E X C L U S I V E IN T E L L E C T U A L P R O P E R T Y O F C U R R A N A R C H I T E C T U R E , AN D A R E N O T T O B E U S E D O R R E P R O D U C E D , WH O L E O R I N P A R T , W I T H O U T T H E W R I T T E N CO N S E N T O F C U R R A N A R C H I T E C T U R E . C O P Y R I G H T 2 0 1 2 , C U R R A N A R C H I T E C T U R E 31 7 . 2 8 8 . 0 7 5 3 F A X 31 7 . 2 8 8 . 0 6 8 1 V O I C E IN D I A N A P O L I S , I N 4 6 2 5 0 69 2 5 E A S T 9 6 T H S T . , S U I T E 1 0 5 C U R R A N WW W . C U R R A N - A R C H I T E C T U R E . C O M E0.1 AD D E N D U M # 1 1 1 / 2 7 / 1 3 A A